GOST Measurement Application User Manual (for FloBoss 107)
Revised May-2016 Configuration 15
2. Review the values in the following fields:
Mole
Enter the mole percent of each gas
component. The Total Mole % should equal
100% after all the component mole
percentages have been entered.
Notes:
For VNIC-SMV calculations, all mole %
fields must be entered.
For GERG-91 and NX19 calculations, only
CO2, Nitrogen, and Base Density need to
Sets how the system determines the heating
value for a specified quantity of gas. Valid
values are Calculate (allow the system to
calculate the heating value from the gas
composition data) or Enter (use the value
specified in the energy calculation).
Value
Sets/displays, in MJ/m3, the inferior heating
value based on the Monitor Heating Value
selection. If the Heating Values field is set to
Calculate, this read-only field shows the
inferior heating value calculated by the
program. If the Heating Values field is set to
Enter, sets a user-defined inferior heating
Superior Heating
Value
Sets/displays, in MJ/m3, the superior heating
value based on the Monitor Heating Value
selection. If the Heating Values field is set to
Calculate, this read-only field shows the
superior heating value calculated by the
program. If the Heating Values field is set to
Enter, sets a user-defined superior heating
Value
Sets which heating value is used for energy
calculations and archives. Valid selections are
Sets/displays, in kg/m3, the density of the
selected product at base conditions. For
VNIC-SMV, this read-only field shows the
program calculated base density. For GERG
and NX19, sets a user-defined base density.
3. Click Apply to save any changes you have made to this screen.
4. Proceed to Section 3.1.3 to review calculated values.
3.1.3 GOST Properties – Calculated Values tab
Use this tab to view all property values calculated by the program.
To access this screen:
1. Select the Calculated Values tab on the GOST Properties screen.