Xtreme Switched XPDU User manual

Category
Power distribution units (PDUs)
Type
User manual

Xtreme Switched XPDU is an intelligent current-meter equipped device designed to help you monitor and manage your power consumption. It features a built-in web server for remote monitoring of current consumption, audible alarms for warning and overload situations, and the ability to send email and traps when power consumption exceeds trigger values. The XPDU also provides per outlet power protection by circuit breaker and real-time control of outlets.

Xtreme Switched XPDU is an intelligent current-meter equipped device designed to help you monitor and manage your power consumption. It features a built-in web server for remote monitoring of current consumption, audible alarms for warning and overload situations, and the ability to send email and traps when power consumption exceeds trigger values. The XPDU also provides per outlet power protection by circuit breaker and real-time control of outlets.

Switched XPDU
15A Model
User & Installaon Manual
www.xpcc.com | © 2014 Xtreme Power Conversion Corporaon. All rights reserved. (Rev 10/02/14)
Xtreme Power Conversion Corporaon
Switched XPDU Users Manual
Page 2
Power Distribuon Unit
Table of Contents
Introducon.................................................................................................4
PDU Package................................................................................................4
Funcon.......................................................................................................4
Interface..........................................................................................................................................4
Installaon...................................................................................................5
Rack Mount Instrucons..................................................................................................................5
Diagram...........................................................................................................................................6
Hardware.........................................................................................................................................6
Web Interface..............................................................................................7
Xtreme Power Conversion Corporaon
Switched XPDU Users Manual
Page 3
Power Distribuon Unit
Introducon
The PDU is an Internet ready device designed and is equipped with an intelligent current- meter (True RMS) that
will indicate the total power consumpon of a power strip.
The PDU oers an easy set up and user-friendly communicaon soware. This soware provides the funcon that
assistant manager to remotely monitor the mulple PDU power consumpon to realize the total current power
consumpon and ulizaon for the enterprises.
Features:
Built-in web server, manager can real me to monitoring the current consumpon of the power strip.
Build-in true RMS current meter.
Setup easily, meter can read the IP address directly.
Homepage support SSL.
Provide audible alarm when the power consumpon over the threshold of warning and overload.
Send the email and traps when the power consumpon exceed the trigger value of warning or overload
to the PDU.
Provide ulity, it can monitor a large mount of PDU at the same me.
Support the SNMP and provide MIB for the PDU to be monitored by NMS.
Provide per outlet power protecon by the circuit breaker.
Real me to control outlets of PDU.
Indicate outlets status with LED.
Support power on sequence.
Opon accessory can support temperature and humidity detecon.
PDU Package
The standard PDU package contains a Power Distribuon Unit with supporng hardware and soware. The com-
ponents of the package are:
Power Distribuon Unit
Rack mount Brackets. CD-ROM, it contains:
User Manual
PDU Soware
MIB: Management Informaon Base for Network (PDUMIB.mib)
Adobe Acrobat Reader
Funcon
Interface
Xtreme Power Conversion Corporaon
Switched XPDU Users Manual
Page 4
Power Distribuon Unit
Funcons Descripon
Ethernet RJ45 port for network communicaon port.
Audible Alarm
Warning- 1 beep in 1 second.
Overload- 3 beeps in 1 second.
Note: The audible alarm will keep beeping unl the current gets back to normal
and the current is lower than the threshold to 0.5 amps.
Funcon Buon
Press and release to turn o the warning beeping. The overload beeping can
not be cancelled.
Press and hold the key aer 2 beeping; it can let the meter to show up the IP
address
Press and hold the key aer 4 beeping; it can change the way to get IP by DHCP
or xed IP.
Press and hold the key aer 6 beeping; it can reset PDU back to default seng.
Meter 3 digits to display current and IP Address.
ID The idencaon of power bank or PDU.
LED Indicator
SSL (yellow): Light on means web access is protected by SSL.
DHCP (Green): Light on means PDU gets IP address by DHCP.
PDU (Green): Indicate each output power status.
Status (Red): Indicate each circuit status. (by model)
ENV RJ11 for ENV probe aached.
Circuit Breaker Overload power protecon.
Installaon
This secon will provide a quick instrucon to install the PDU.
Rack Mount Instrucons
A. Elevated Operang Ambient - If installed in a closed or mul-unit rack assembly, the operang ambient tem-
perature of the rack environment may be greater than room ambient. Therefore, consideraon should be
given to installing the equipment in an environment compable with the maximum ambient temperature
specied by the manufacturer.
B. Reduced Air Flow - Installaon of the equipment in a rack should be such that the amount of air ow required
for safe operaon of the equipment is not compromised.
C. Mechanical Loading - Mounng of the equipment in the rack should be such that a hazardous condion is not
achieved due to uneven mechanical loading.
D. Circuit Overloading - Consideraon should be given to the connecon of the equipment to the supply circuit
and the eect that overloading of the circuits might have on over current protecon and supply wiring. Ap-
propriate consideraon of equipment nameplate rangs should be used when addressing this concern.
E. Reliable Earthing - Reliable earthing of rack-mounted equipment should be maintained. Parcular aenon
should be given to supply connecons other than direct connecons to the branch circuit (e.g. use of power
strips).
Xtreme Power Conversion Corporaon
Switched XPDU Users Manual
Page 5
Power Distribuon Unit
Diagram
Hardware
1. Install mounng brackets.
2. The PDU comes with brackets for mounng in a rack. To mount the PDU into a rack performs the following
procedure:
3. Aach the mounng brackets to the unit, using the four retaining screws provided for each of the brackets.
4. Choose a locaon for the brackets.
5. Align the mounng holes of brackets with the notched hole on the vercal rail and aach with the retain-
ing screws.
6. Connect input and output power.
7. Connect Ethernet cable to the PDU.
8. Switch on the PDU.
Note: The default seng for the way to get IP address is DHCP. If PDU can not get the IP from
DHCP server, the IP address will stay at 192.168.0.216
Note: TO SETUP THE NETWORK SYSTEM FOR PDU, STRONGLY RECOMMEND TO BUILD UP THE POWER MONITOR-
ING NETWORK SYSTEM ISOLATED WITH THE OTHERS, IN ORDER TO KEEP THE STABILITY OF GETTING POWER IN-
FORMATION AND SYSTEM OPERATION.
Xtreme Power Conversion Corporaon
Switched XPDU Users Manual
Page 6
Power Distribuon Unit
Web Interface
Login:
Input the PDU IP address in the web browser
Default ID is snmp
Password is 1234
Xtreme Power Conversion Corporaon
Switched XPDU Users Manual
Page 7
Power Distribuon Unit
Informaon: PDU
Display total PDU and each outlet power consumpon.
When plug the opon device - ENV probe, it will display temperature and humidity informaon
Xtreme Power Conversion Corporaon
Switched XPDU Users Manual
Page 8
Power Distribuon Unit
Informaon: System
Indicate PDU system informaon, including:
Model No.
Firmware
Version
MAC Address
System Name
System Contact
Locaon
Xtreme Power Conversion Corporaon
Switched XPDU Users Manual
Page 9
Power Distribuon Unit
Control: Outlet
Indicate PDU outlet on/o status and control outlet.
Select the outlet by checking the box and then click ON or OFF buon to control output power for PDU
Monitored PDU series does not support this funcon.
ON: Press the icon to turn on the assigned outlets.
OFF: Press the icon to turn o the assigned outlets.
OFF/ON: Press the icon to reboot the assigned outlets.
Xtreme Power Conversion Corporaon
Switched XPDU Users Manual
Page 10
Power Distribuon Unit
Conguraon: PDU
Set the outlet name and delay me.
Name: Rename the outlet.
ON: Set delay me for power on sequenal.
OFF: Set delay me for power o sequenal.
Note: The maximum delay me is 255 seconds.
Note: Aer PDU is plugged into main power, PDU system will start to sequenally turn on the output socket ac-
cording to the pre-set delay me in PDU web interface. The factory default seng for delay me is one second for
each outlet; therefore the 8 ports PDU will take 8 seconds, 24 ports PDU will take 24 seconds to complete start-up
procedure.
Before the sequence procedure is completed, if a PDU is unplugged from the power source, the outlets which
are not turned on will be regarded as remaining at the power-o status. Next me the PDU is plugged into main
power, these outlets will not be automacally turned on. These outlets can only be turned on by web interface.
Xtreme Power Conversion Corporaon
Switched XPDU Users Manual
Page 11
Power Distribuon Unit
Conguraon: Threshold
Set the warning and overload threshold for each circuit.
Set lower and upper threshold for temperature and humidity.
Xtreme Power Conversion Corporaon
Switched XPDU Users Manual
Page 12
Power Distribuon Unit
Conguraon: User
Change ID and password.
Default ID is snmp and password is 1234.
Xtreme Power Conversion Corporaon
Switched XPDU Users Manual
Page 13
Power Distribuon Unit
Conguraon: Network
PDU network informaon
Enable DHCP: Change the way to get IP address for PDU.
Xtreme Power Conversion Corporaon
Switched XPDU Users Manual
Page 14
Power Distribuon Unit
Conguraon: Mail
When event occurs, PDU can send out email message to pre-dened account.
Email Server: The Email Server only support to be input domain name, not IP address.
Senders Email: Input the sender email address.
Email Address: Input the recipient email address.
The message in the email:
Indicate OutletA~H-XXXXXXXX status in order
X=0 : means the power o. X=1 : means the power on.
Note: Make sure DNS server can resolve the Email Servers domain name.
Xtreme Power Conversion Corporaon
Switched XPDU Users Manual
Page 15
Power Distribuon Unit
Conguraon: SNMP
When event occurs, PDU can send out trap message to pre-dened IP address.
Trap Nocaon: Set receiver IP for trap.
Community: Set SNMP community.
Read Community is public and xed.
Default Write Community is “public” and can be modied by user.
Xtreme Power Conversion Corporaon
Switched XPDU Users Manual
Page 16
Power Distribuon Unit
Conguraon: SSL
Enable SSL for web communicaon.
User must input the correct ID and password to enable SSL funcon. The ID and password must be the same with
the seng in “User.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16

Xtreme Switched XPDU User manual

Category
Power distribution units (PDUs)
Type
User manual

Xtreme Switched XPDU is an intelligent current-meter equipped device designed to help you monitor and manage your power consumption. It features a built-in web server for remote monitoring of current consumption, audible alarms for warning and overload situations, and the ability to send email and traps when power consumption exceeds trigger values. The XPDU also provides per outlet power protection by circuit breaker and real-time control of outlets.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI