FläktGroup REPLACEMENT KIT OJ-DRHX for EQRO Installation guide

Category
Signal cables
Type
Installation guide
FläktGroup FG_DC-10567-GB 2021-05-17_R0 Specifications are subject to alteration without notice
REPLACEMENT KIT OJ-DRHX,
ROTOR DRIVE UNIT FOR EQRO
INSTALLATION
IMPORTANT!
The controller is configured at delivery. The necessary settings are made for the delivered controller/
motor combination and the rotation speed is set to 20 rpm when the control signal is over 9.5 V. The
settings are based on the ordering code.
ORDERING CODE
EQRO-99-13-cc-ddd-d-e-f
cc (Unit type)
10 = eQ Prime, 270 mm rotor for mounting in casing. Unit sizes 005, 008, 011, 018.
11 = eQ Prime, 270 mm rotor for mounting in casing. Unit sizes 023, 032, 041, 050.
20 = eQ Master, 200 mm rotor for mounting in casing. Unit sizes 005–054, 063, 072.
21 = eQ Master ,270 mm rotor for mounting in casing. Unit sizes 005–054, 063, 072.
ddd (Unit size)
005–054, 063, 072
e (Variant)
0
f (Material)
1 = Fzv
2 = Rst 304
4 = Rst 3016L
8 = AlZn
WARNING!
Ensure safety before installation
Read this related document before installation:
10554 – Installation of DRHX Controller
2
FläktGroup FG_DC-10567-GB 2021-05-17_R0 Specifications are subject to alteration without notice
Replacement kit OJ-DRHX
INSTALLATION
1. Lock the pulley (A) to the motor shaft with the stop screw.
2. Make sure that the stop screw locks in the groove of the motor
shaft.
3. For ddd = 020–072, install a spacer (B) between the motor and the
bracket.
4. The motor (C) is delivered mounted on an L-shaped bracket. If f = 1
or 8, attach the motor with the L-shaped bracket and the existing
screws.
8. Replace the belt (D) with the delivered replacement belt.
9. Connect the ends of the replacement belt with the delivered splice
pin.
10. Use delivered self-drilling screws (E) to attach the controller to the
existing bracket.
A
D
D
B
F
C
5. If f = 2 or 4, remove the L-shaped bracket from the motor and attach
the motor to the delivered bracket. Replace the existing screws with
the delivered screws in stainless steel.
6. Install a cable anchor (D) with a screw.
7. Attach the motor cable to the cable anchor with a cable tie.
11. Install the motor with the bracket into the rotor (F).
12. Attach the motor cable (G) to the wall of the rotor with delivered
cable anchors, cable ties and screws.
13. Connect the motor cable. Refer to page 3.
ddd = 020–072 ddd = 005–018
A
CD
E
G
G
3
FläktGroup FG_DC-10567-GB 2021-05-17_R0 Specifications are subject to alteration without notice
Replacement kit OJ-DRHX
TO CONNECT THE MOTOR CABLE BETWEEN THE MOTOR AND THE CONTROLLER
CAUTION!
Make sure that the motor cable is cut to the correct length before you
connect it. There must not be any surplus cable and the cable must not
be rolled up.
1. Cut the motor cable to the correct length.
2. Put the delivered yellow and green shrink tube (A) on the cut PE
wire (B). The PE wire is yellow.
3. Put the delivered end sleeves (C) on the wires of the motor cable.
A
BC
D
4. Connect the wires of the motor cable to the controller as shown in
the table below.
5. Connect the quick connector (D) to the motor.
Upward Downward
Wire Terminal Terminal
Brown U U
Blue V W
Black W V
Green/yellow PE PE
  • Page 1 1
  • Page 2 2
  • Page 3 3

FläktGroup REPLACEMENT KIT OJ-DRHX for EQRO Installation guide