3) Set parallel parameters.
⚫ Inv Parallel Num: Total numbers of the inverters.
⚫ Parallel Master/Slave: In a parallel system, the master unit broadcasts the BMS and other information to the
slaves. Make sure only one unit is configured as master.
⚫ Inv Parallel Addr: Local unit address. The master’s address should be 1, and the slave should be from 2
onwards.
⚫ Common Battery Enable: Common battery or independent battery. If the batteries are connected in parallel
and the master battery connected only to the master inverter (Configuration 1) please select “ON”.
If each inverter is connected to a separate master battery (Configuration 2), please select "OFF".
⚫ Common Grid CT Enable: Common CT or independent CT, if all AC inputs are connected in parallel and a
set of CTs is used, please select 'ON'.
⚫ 3 Phase Enable: It needs to be open during three-phase installation, please select "OFF" when single-phase
parallel connection.
⚫ Parallel Charge Current: Total battery charge current command under shared battery, only be settable in
master unit in parallel mode.
⚫ Parallel Charge Current: Total battery discharge current command under shared battery, only be settable in
master unit in parallel mode.
⚫ Inv Parallel Enable: Enable/Disable the parallel function. It needs to be turned on in parallel mode.
After setting up, if you need to change the working mode of the system, please modify the "Work Mode" of the host. The
slave does not need to change it and will run according to the working mode of the host.