WECO Deye SUN Single Phase User guide

Category
Power adapters & inverters
Type
User guide
DEYE SUN SINGLE PHASE QUICK GUIDE
DEYE
HYBRID INVERTER
SUN single Phase
Whole Power Range
Deye Single Phase Inverter Configuration
Deye SUN Hybrid 220Vac Single Phase Inverter
Quick Configuration Guide
DEYE SUN SINGLE PHASE QUICK GUIDE
Preparations:
Open the connection lid to access the connection board of the inverter, CAN port, CT terminal and Battery Power
Connection Terminal are all located here.
General Connection Layout
USE ONLY THE CAN PORT
(RS485 is not supported)
DO NOT CONNECT THE
BATTERY TEMPERTURE
SENSOR.
CT FOR SINGLE PHASE TO
BE CONNECTED ON PORT
5-6
DIP 7 Enables
CAN 120 Ohm Resistor
DEYE SUN SINGLE PHASE QUICK GUIDE
Inverter Connection Hub
CT communication Line
CT connection: CT is connected to pins 5 and 6 of the inverter end, with white connected to pin 5 and black
connected to pin 6. The arrow direction of the CT points towards the power grid.
DEYE SUN SINGLE PHASE QUICK GUIDE
Step 1. Safety Preparation
For Safety reason it is forbidden to install any power inputs such as PV, GRID or BATTERY before having completed
all the data wiring connection as explained below.
The PV cables cannot be conneted at this stage
Grid and Generator wires cannot be conencted at this stage
Baery must kept OFF while performing the connecon operaons, power cables to be connected at last.
Ground the Inverter immediately aer xing it on the wall
KEEP THE INVERTER OFF
DEYE SUN SINGLE PHASE QUICK GUIDE
Step 2. Battery Preparation
Keep the BMS switch on “0” OFF.
Set the DIP Switch of the battery in accordance with the relevant manual.
Connect the provided CAN cable RJ45 to the CAN A port.
The RJ45 Terminal on the other side needs to be crimped to match inverter PIN OUT.
Do not connect the power cables at this stage.
5K3 XP EXAMPLE
DIP switched are set all OFF (00000000). Only DIP of last slave must be set differently (00000100).
4K4 LT EXAMPLE
DIP switched are set all OFF (00000000). Only DIP of last slave must be set differently (00000100).
DEYE SUN SINGLE PHASE QUICK GUIDE
Step 2.1. Can Connection
WeCo Provides an RJ45 cable Type T568B with any battery Kit.
BMS CAN PIN OUT at battery side is the same for any WeCo battery.
The RJ45 Terminal on the inverter side needs to be crimped to match inverter PIN OUT
ATTENTION DEYE CAN BMS CABLE TO BE MODIFIED LOCALLY
Terminal
Battery Side
RJ45
DEYE Side
RJ45
GND
PIN 3
PIN 2
CAN -L-
PIN 2
PIN 5
CAN -H-
PIN 1
PIN 4
BATTERY RJ45
INVERTER RJ45
BATTERY SIDE KEEP THE
ORIGINAL RJ45 TERMINAL
INVERTER SIDE MAKE A
NEW TERMINAL PIN OUT
DEYE SUN SINGLE PHASE QUICK GUIDE
Multiple batteries connected in parallel with inverter
Master and Slave configuration of 5K3XP and 4K4LT can be done up to 15 batteries without accessories.
From the Master to the 14th battery (slave 13) the DIP SWITCH to be set all OFF.
The last battery must have the DIP 7 ON to enable the Termination of CAN BUS line.
For more details follow the batteries manuals.
DIP7 ON
TERMINATOR
DEYE SUN SINGLE PHASE QUICK GUIDE
Step 3. Battery Power Connection
Keep Inverter and Battery OFF.
Connecting the power Cables from the battery to the Inverter.
Use a Torque Wrench to secure the cables bolt.
KEEP THE BATTERY OFF
Battery Torque: 9.5 Nm
Inverter Torque: 11 Nm
INVERTER OFF
BATTERY OFF
Same configuration applies to the 4k4 LT model.
5K3 XP
model
DEYE SUN SINGLE PHASE QUICK GUIDE
Step 4. Battery FW Upgrade and Protocol Set
Download the WeCo Bluetooth APP from Google Play of from APP Store.
The Bluetooth APP will allow you to inspect the battery, set the battery and monitor the BMS functions during the
commissioning phase.
As good practice, it is always required to search for the latest FW for the battery.
The 5K3 XP Model has a built in WiFi/BT device and it is possible to find the battery Bluetooth Signal (in the form
of battery Serial Number) directly from the in-APP list.
Open the BT APP
Turn On the Battery
Access the APP using the password 1010.
Select Battery Module.
Scroll Down and tap on the Serial Number of your battery.
Once the main page will display your battery info, scroll down and tap on the FW upgrade button if
available (if not displayed means the battery is UP to Date).
APP STEPS
01
02
03
04
05
06
Same procedure applies to the 4k4 LT model, with the exception that an external WiFi/BT dongle is
needed. In this case, in the step of screen 04 you will have to select the dongle’s MAC Address.
DEYE SUN SINGLE PHASE QUICK GUIDE
Protocol Set Up
Wait until pop up confirms that the update process is successful, then proceed to set the inverter protocol.
ATTENTION
Turn Off the battery to proceed with the remaining operations.
Keeping the battery ON will damage the BMS an potentially the inverter power protection circuit.
Step 5. Inverter Wiring
Now it is possible to wire the GRID and PV cables into the inverter and reinstall the protection cover.
Then press the battery ON/OFF button and turn on the PV Switch to enable the PV.
Now the inverter will Initiate the Start Up process and the Battery can be turned ON.
Swipe UP to
reach the bottom
of the page.
SET 00CAN
DEYE SUN SINGLE PHASE QUICK GUIDE
Step 6. Inverter Protocol Set up
Initially the inverter LCD might display a communication error between battery and inverter (central
icon error F56)
This is normal, as it is necessary to set the correspondent protocol on the inverter by using the LCD
Functions.
Enter the menu and then press Battery Settings.
In this page select “Lithium” and set the capacity of your system (each 5K3XP has a capacity of 100Ah, each
4K4LT of 86Ah).
Use the arrows Keys to write the correct value and press ENTER key to confirm the value.
Now scroll down to “Batt Set3” and then set “Lithium mode: 00”.
Battery is now recognized by the inverter and parameters are visible on the main display.
c
DEYE SUN SINGLE PHASE QUICK GUIDE
ATTENTION, IMPORTANT
To ensure that all the information are properly displayed and received by the inverter it is necessary to
make a double control by tapping on the Battery ICON and accessing to the Battery BMS information.
In the Screen it Is possible to see the correct information received by the inverter from the Battery BMS,
such AS: (Image A)
SOC %
Voltage
Current
Power
Temperature
Click on the lower right corner of the LCD on Li-BMS area to access to further battery data.
A
DEYE SUN SINGLE PHASE QUICK GUIDE
In the Screen it Is now possible to see other important information, such the charge and discharge limit
(Current) requested from the battery: (Image B)
BMS COMM Priority (STOP if No data reply from the BMS)
To ensure addition safety between the Battery and the BMS it is suggested to flag the BMS ERROR STOP
function on the inverter LCD into the same Setting Area
This function will not allow the inverter to charge and discharge the battery if the communication between
the two (inverter and battery) is not successful.
If after the BMS ERROR STOP the main screen still display the energy flowing from and to the battery,
means that the BMS can successfully communicate with the inverter and lead the charging and discharging
process.
B
DEYE SUN SINGLE PHASE QUICK GUIDE
Now the system is set and ready to work:
PV POWERS THE LOAD AND CHARGES THE BATTERIES
NO PV - BATTERIES POWER THE LOAD
DEYE SUN SINGLE PHASE QUICK GUIDE
NO LOAD PV CHARGES THE BATTERIES
To enable the WeCo WiFi Monitoring App, please follow the relevant manual available on our Web Site
https://wecobatteries.com/download-area/
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15

WECO Deye SUN Single Phase User guide

Category
Power adapters & inverters
Type
User guide

Ask a question and I''ll find the answer in the document