Ampac EV3000 4210-0030 Installation guide

Type
Installation guide

This manual is also suitable for

ADVANCED WARNING
SYSTEMS
EV3000 Visual Output Board
Installation Guide
Item Numbers: 4210-0030 (XENON)
4210-0031 (LED)
MAN2983-1
N1236
Page 1
WORLD LEADER OF INNOVATIVE SOLUTIONS IN FIRE DETECTION AND ALARM SYSTEMS
Ampac Technologies Australia Tel: +61 8 9201 6100 Europe Tel: +44 (0) 1302 833 522 New Zealand Tel: +64 9 443 8072 www.ampac.net
General:
The Visual Output Board (EV3000) Fast Fit Kit consists
of:
1 x Visual Output Board
4 x 4K7 EOL (RES1096) LED STROBES
4 x 10K EOL (RES1010) XENON STROBES
1 x 26 Way Ribbon Cable 1280mm (260-0029)
4 x M3 x 6mm screws (HW1585)
4 x M3 Rivnut (HW2323)
4 x M3 x 8mm Spacer (HW2274)
Description:
The BRDEV3VOB3-A / BRDEV3VOB3-B or the 302-
623B / 302-623C cater for field connections of Visual
Warning Strobes. Each board will terminate four (4)
zones of Visual Warning Strobes.
Each Zone Output on a BRDEV3VOB3-A / 302-623C
board can cater for up to four pairs of LED strobes.
Each Zone Output on a BRDEV3VOB3-B / 302-623B
board can cater for up to forty pairs of XENON strobes.
NOTE: XENON strobes and LED strobes can not be
inter-changed. Use the appropriate board when
configuring your system.
BRDEV3VOB3-A = LED STROBES
302-623C = LED STROBES
BRDEV3VOB3-B = XENON STROBES
302-623B = XENON STROBES
Installation:
Mount Board on appropriate standoffs and fit to rear
backpan using existing mounting points if available.
Visual Warning Strobes must be capable of operating
on 24V DC (nominal). See approved Visual Warning
Strobes.
If no Visual Warning Strobes are fitted to an output,
terminate with 10K EOL for XENON STROBES or 4K7
EOL for LED STOBES. Otherwise terminate the last
Visual on a line with the correct EOL (see Figures 3 and
4 )
Each visual output from the EV3000 will operate a pair
of indicators, i.e. an Alert (Amber) and Evac (Red)
Strobe. Visual pairs are fitted in reverse polarity.
Observe anti-static precautions at all times
Connections
Field
Connections
Use
TB1 - 1, 2 Output Pair Zone 1
TB2 - 1, 2 Output Pair Zone 2
TB3 - 1, 2 Output Pair Zone 3
TB4 - 1, 2 Output Pair Zone 4
Factory
Connections
Use
TB5-1,2 +24V
TB5-1,2 0V
CN1 Control Cable to 302 4220 board.
CN2 Control Cable to next 302-623B/C
board or BRDEV3VOB3-A/B
Fuse Ratings:
BRDEV3VOB3-A/B
Fuse Use Rating
F1-4 +24V Output 1 3 amp M0205
302-623B/C
F1-4 +24V Output 3 3 amp 3AG
NOTE: Circuit to Visual Strobes are polarised refer to
Figures 3 and 4 for more detail.
Approved Visual Warning Strobes:
Item
Number
Description
208-0011 24v Xenon Strobe
Combined Red/Amber
208-0060 SONOS LED Strobe Red
208-0061 SONOS LED Strobe Amber
208-0062 SONOS LED Strobe Clear Lens
208-0063 SONOS LED Strobe
Combined Red/Amber (Flush Mount)
208-0064 SONOS LED Strobe Deep Base IP65
208-0065 SONOS LED Strobe
Combined Red/Amber IP65
208-0066 SONOS LED Strobe
Combined Red/Amber (Surface Mount)
ADVANCED WARNING
SYSTEMS
EV3000 Visual Output Board
Installation Guide
Item Numbers: 4210-0030 (XENON)
4210-0031 (LED)
MAN2983-1
N1236
Page 2
WORLD LEADER OF INNOVATIVE SOLUTIONS IN FIRE DETECTION AND ALARM SYSTEMS
Ampac Technologies Australia Tel: +61 8 9201 6100 Europe Tel: +44 (0) 1302 833 522 New Zealand Tel: +64 9 443 8072 www.ampac.net
27V27V0V0V
O/P1
O/P2
O/P3 O/P4
VISUAL OUTPUT BOARD
302 6230B/C
TO MAF
TB5
+
+
Q10
Q7
Q1
Q4
IC1
Q2
RL1
///
N/C
C
N/O
RL2
///
N/C
C
N/O
F1 3A
CN1
CN2
Q3
TB1
TB2
TB3
TB4
RL3
N/O
C
N/C
///
RL4
N/O
C
N/C
///
Q6
Q5 Q8
Q9 Q12
Q11
LINK
IC2
SIL3
F2 3A
F3 3A
F4 3A
TO NEXT 302-6230
Figure 1: 302-623C Visual Output Board (LED STROBES) /
302-623B Visual Output Board (XENON STROBES)
29/07/09
27V27V0V0V
O/P1 O/P2
O/P3
O/P4
VISUAL OUTPUT BOARD
BRDEV3VOB3-
+-
- + -
+
-
+
TB5
+
+
Q10
Q7
Q1
Q4
IC1
Q2
M3
///
N/C
C
N/O
RL1
///
N/C
C
N/O
RL2
F1F2
F3
F4
CN1
CN2
Q3
TB1 TB2 TB3 TB4
N/O
C
N/C
///
RL3
N/O
C
N/C
///
RL4
M6
Q5 Q8
Q9
Q12
Q11
IC2
SIL3
TO MAF
TO NEXT BRDEV3VOB3
Figure 2: BRDEV3VOB3-A Visual Output Board (LED STROBES) /
BRDEV3VOB3-B Visual Output Board (XENON STROBES)
-
V
E
I
N
/
O
U
T
+
V
E
I
N
+VE
O
UT
L
E
D
-
ALERT
(AMBER)
EVAC
(RED)
N1236
OUT
-
V
E
I
N
/
O
U
T
+
V
E
I
N
+
VE
OUT
L
E
D
-
N1236
GND GND
FROM 302-623C /
BRDEV3VOB3-A
VISUAL OUTPUT
BOARD (OWIS)
TO NEXT
STROBE or
TERMINATE
WITH 4K7 EOL
10K
Figure 3: Visual Warning Strobe Connections (LED STROBES) 208-0063
FROM 302-623B /
BRDEV3VOB3-B
VISUAL OUTPUT
BOARD (OWIS)
ALERT
(AMBER)
EVAC
(RED)
1
2
3
4
OUT
TO NEXT
STROBE or
TERMINATE
WITH 10K EOL
10K
Figure 4: Visual Warning Strobe Connections (XENON STROBES) 208-0011
  • Page 1 1
  • Page 2 2

Ampac EV3000 4210-0030 Installation guide

Type
Installation guide
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI