ADVANCED WARNING
SYSTEMS
ACP-02 Addressable Manual Call Point
Installation Guide Item Numbers: 4255-0250
MAN2878-1
N1236
Page 1
WORLD LEADER OF INNOVATIVE SOLUTIONS IN FIRE DETECTION AND ALARM SYSTEMS
Ampac Technologies Australia Tel: +61 8 9201 6100 Europe Tel: +44 (0) 1302 833 522 New Zealand Tel: +64 9 443 8072 www.ampac.net
Description:
The AMPAC ACP-02 double action re-settable Manual
Call Point (MCP) eliminates the possibility of accidental
operation and the cost and labour of replacement of
frangible elements.
Features:
Testing of operation without removal of front cover
Resettable operation
LED indication
Suits standard mounting control wall box
Installation:
Observe anti-static precautions at all times
Flush Mounting
1. Remove the securing screw from the front of MCP
while at the same time pulling the top of the facia
away from the backing plate
2. Set the address of the MCP (See Figure 2)
3. Place the spacer to the back of the MCP as shown
above and terminate the cables (See Figure 1)
4. Fix the backing plate and spacer to the wall box
using two (2) appropriately sized fixing screws
5. Set the address of the MCP (See Figure 2)
6. Remove the two (2) thread protection plugs from
the mounting box and fix the backing plate to it
using the two (2) fixing screws supplied
7. Replace the facia by inserting the two (2) bottom
locating pegs of the facia up into the bottom of the
locating holes of the backing plate, close at the top,
tighten the retaining screw then insert the key (as
shown) to reset the operation element
Testing of MCP Operation
1. Isolate the FACP from calling the fire brigade
2. Press on the clear ABS operation element in the
location indicated, PUSH HERE to drop the
element down
3. Operate the switch, the MCP LED should illuminate
and an alarm at the FACP should be indicated
4. To reset the operation element firmly push the key
up into the slot in the bottom of the facia
Note 1: Set the device type in FireFinder
ConfigManager to S90 MCP
Note 2: To ensure line monitoring integrity always use
one (1) set of terminals for “IN” and one (1) set for
“OUT”.
FACIA WITH THE
OPERATION ELEMENT
IN THE RELEASED POSITION
+
+
-
-
ON
1 2 3 4 5 6 7 8
LOOP
+ -
IN
PCB LAYOUT & WIRING
LOOP
+ -
OUT
ADDRESS SWITCH
ON
1 2 3 4 5 6 7 8
INSERT KEY
TO RESET
FACIA RETAINING
SCREW
KEY
BACKING PLATE
EXAMPLE
WALL BOX
AMPAC
PCB
SPACER TO ADD 10mm
TO THE DEPTH OF THE
MCP FOR FLUSH MOUNTING
CLEAR ABS
OPERATION
ELEMENT
FRONT ASSEMBLY
FACIA
OPERATION ELEMENT
PRESSURE SPRINGS
Figure 1: General Wiring Diagram
ADVANCED WARNING
SYSTEMS
ACP-02 Addressable Manual Call Point
Installation Guide Item Numbers: 4255-0250
MAN2878-1
N1236
Page 2
WORLD LEADER OF INNOVATIVE SOLUTIONS IN FIRE DETECTION AND ALARM SYSTEMS
Ampac Technologies Australia Tel: +61 8 9201 6100 Europe Tel: +44 (0) 1302 833 522 New Zealand Tel: +64 9 443 8072 www.ampac.net
ON
1 2 3 4 5 6 7 8
0
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
1
2
4
3
5
6
7
8
ON
ON
ON
9
10
11
12
13
ON
ON
14
15
ON
16
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
17
18
20
19
21
22
23
24
ON
ON
ON
25
26
27
28
29
ON
ON
30
31
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8
32
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
33
34
36
35
37
38
39
40
ON
ON
ON
41
42
43
44
45
ON
ON
46
47
ON
48
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
49
50
52
51
53
54
55
56
ON
ON
ON
57
58
59
60
61
ON
ON
62
63
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8
64
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
65
66
68
67
69
70
71
72
ON
ON
ON
73
74
75
76
77
ON
ON
78
79
ON
80
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
81
82
84
83
85
86
87
88
ON
ON
ON
89
90
91
92
93
ON
ON
94
95
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8
96
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
97
98
100
99
101
102
103
104
ON
ON
ON
105
106
107
108
109
ON
ON
110
111
ON
112
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
113
114
116
115
117
118
119
120
ON
ON
ON
121
122
123
124
125
ON
ON
126
127
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Figure 2: Address Switch Settings