Ampac 8 Zone Conventional Board Installation guide

Category
Fire protection
Type
Installation guide
ADVAN CED WAR NING
SYSTEMS
8 Zone Conventional Board
Installation Guide
Item Numbers: 4310-0082
MAN2982-1
Page 1
Introduction:
The 8 Zone Conventional Board Fast Fit Kit consists of:
1 x 8 Zone Conventional Board
1 x 220mm RJ45M Comms / power Cable
1 x 250mm 2 way IDT Power Cable
4 x 3 x 6mm self tap screws (only required for the
ABS cabinet)
4 x M3 x 6mm screws (only required for the metal
cabinet)
4 x standoffs (only required for the metal cabinet)
8 x 3K3 EOL resistors
8 x 10uF 50V Bi-Polar EOL Capacitors
Description
The 8 Zone Conventional Board provides 8 monitored
conventional zones. Each zone can accommodate up to
40 conventional detectors (32 in UK) and can be
programmed to function in one of the following modes:
Normal (Latching)
Non-Latching
Self Reset
Dependency A, B and C
Investigation
The board has a programmable End Of Line (EOL)
feature that allows either a 3K3Ω, 4K7Ω, 6K8Ω or 10KΩ
resistor value to be used on all zones. Alternatively the
EOL can be a 10uF capacitor which is required to
support the head removal feature when Apollo diode
bases are used on the conventional zone.
Note: If using 10uF EOL with NZ 1997 MCPs the
Alarm activation time will be outside the NZS 4512
standards
Installation
Observe anti-static precautions at all times
Power down and disconnect the batteries
ABS Cabinet (new battery cabinet may be required if a
lower backpan mounting position is used)
1. Mount the board on suitably spaced moulded
backpan bosses using the 4 x 6mm self tap
screws.
Metal Cabinet (standoffs fitted to lower left hand side of
the backpan)
1. If necessary fit the stand offs to the suitably spaced
captive nuts in the lower right hand side backpan
position
2. Mount the board onto the standoffs using the 4 M3
x 6mm screws
Connecting to the FACP
1. Using the supplied Comms cable connect CN2 on
the 8 Zone Board to the RS485 Comms out of the
CIE main board or previous internal backpan
board.
2. Connect power cable from CN8 of Main Brd to CN4
of the Zone Brd. See Figure 1
3. Bring the field cabling into the FACP through a
suitable knockout and terminate to the required
Zones (TB1, TB2).
4. Set Address SW (Addresses 1 to 15 can be used).
See Figure 2
5. Power up the panel and reconnect the batteries
6. Program the 8 Zone Board using LoopMaster or
ConfigManager Tool.
7. Test
CAB2121 (+27v POWER)
POWER
+27V
0V
CN2
CN3
POWER
+27V
0V
CN1
CN2
8 ZONE CONVENTIONAL BOARD
A BATT BOX IS REQ
IF THIS BRD IS FITTED IN A
ABS ENCLOSURE
CAB2200
PSU1887
OPTIONAL FITMENT POINT
CN4 CN5 CN3 CN4
A
N
CAB2200
TB6
K1
CN6
CN1
CN7
CN4
CN5
CN10
CN2
CN8
TB4 TB5
SW1
CN9
K3
USB
0V
AUX OUT1
3
2
1
OUT2
OUT1
+VE
EARTH MON .
COMMS
SGD
+VE +VEA+
0V+27V
INPUTS S UPERV ISED O/P S
LOOP 1 LOOP 2
B-RS485+ RS485- SHD 2+ 3+ 4+COM 1+ 2+
AUX OUT2
2- 3- 4-3+1+ 4+1-
ETH+27V 0V
PWR OUT
PSU CONTROL
DIAGNOSTICS
RS485
TERM
LOAD
RESET
CONTROLS
PWR IN
N/O C N /C N/O C N/C N/O C N/C
RELAY 1 RELAY 2 RE LAY 3
COMMS
A- B+ B+A- B-A+
DONGLE
1
2
3
DIAGNOSTICS
RS232
SWxxxx
CONFIG
RESET
PRINTER
KEYSWITCH
PWR LINK PWR LINK
SERIALPARALLEL
COMMS
BUZZER
SILENCE
LCD CONNECTOR
LCD BL
FRONT PANEL
INTERFACE
LK1
CN10CN9
CN6
CN4
CN3
CN2
CN8
SW28
SW27
BRD82ZICC3 BRD82MBA5
CN5
Figure 1: Example of Internal Cabling of the Loopsense (ABS cabinet)
ADVAN CED WAR NING
SYSTEMS
8 Zone Conventional Board
Installation Guide
Item Numbers: 4310-0082
MAN2982-1
Page 2
Connection and Settings
CN2 RS485 Comms In from the previous RS485 Comms output or CN10 (Comms out) of the Main Control Card
CN3 RS485 Comms Out to RS485 Comms In of the next RS485 Add-On board.
CN4 27 Volts from available internal Power Connector.
CN5 Optional 27 Volts to the next RS485 Add-On board
TB1/2 8 Zone circuits
SW1 Address set SW as shown in Figure 1
LK1 EOL Link fitted to the last board in the chain
1 2 3 4
ON
1 2 3 4
ON
+ - -+ -+ -+ -+ -+ -+ -+
Z1 Z2 Z3 Z4 Z5 Z6 Z7 Z8
EOL
TB1 TB2
C
N
2
C
N
3
RS485 Comms In From RS485 Comms Out
Previous Board or Comms Out of the Main Board
RS485 Comms Out to RS485 Comms in
of the next Board or Link 1 EOL is Applied
CN4 CN5
LK1 EOL Termination
SW1
ON
Address SW
To Zones 1 to 4 + / - To Zones 5 to 8 + / -
27V IN
+
-
27V OUT
+ - -+ -+ -+ -+ -+ -+ -+
Z1 Z2 Z3 Z4 Z5 Z6 Z7 Z8
TB1 TB2
To Zones 1 to 4 + / - To Zones 5 to 8 + / -
Note 1:Each Zone cct MUST be terminated with either
3K3, 4K7, 6K8, 10K Ohm resistor or
10uF 50V Bi-Polar Capacitor EOL.
Note 2: If Diode Bases are used ONLY the 10uF CAP
can be used
ON
Address Switch Setting (SW1)
Add 1234
1
2
3
4
1000
0100
1100
0010
Address 1 shown
PRESS HERE
TO BREAK
FIRE
ALARM
Maximium of 40
devices per Zone
EOL
Add 1234
5
6
7
8
1010
0110
1110
0001
Add 1234
9
10
11
12
1001
0101
1101
0011
Add 1234
13
14
15
1011
0111
1111
Figure 2: 8 Zone Conventional Board PCB Layout
  • Page 1 1
  • Page 2 2