WarmlyYours Qtran Transformer Installation guide

Category
Dimmers
Type
Installation guide
INSTALLATION Q6S/Q6M
© 2020 Q-Tran Inc. All rights reserved | 155 Hill St. Milford, CT 06460 | 203-367-8777 | [email protected] | www.q-tran.com Specification subject to change. Rev-09-29-20
Mounting Options
MOUNT unit in any of the following configurations:
Do not recess. If you need a recessed unit, you need to order our QT series.
VOLTAGE DROP
To minimize voltage drop the proper gauge wire must be pulled between
the Q-Tran power supply and the load.
Q-Tran offers a free voltage drop calculator on our website
(www.q-tran.com) or you can download our free voltage drop app for
iPhone, iPad or android devices (click link on our site).
Below is a quick reference chart of minimum acceptable wire gauges.
(Q-Tran urges each installer to view our full calculator.)
BEFORE INSTALLING DOOR
Please make sure the output voltage at the lamps is between 11.4–12 volts
for a 12V system or 22.824 volts for a 24V system. Check this voltage with
a true RMS volt meter & take voltage reading at the lamps.
CONNECT SECONDARY
(For detailed look at secondary, see Diagram B)
Connect low voltage fixtures in one of the following methods:
CONNECT PRIMARY
(For detailed look of primary, see Diagram A)
NOTE: Voltages are fixed and can only be changed at the
factory. Voltages come in 120V, 230V or 277V.
1
3
5
4
2
Rod Suspension
Surface Wall
Surface Ceiling
Surface Floor
NOTE: Rods not included.
120V input
Switch
120V input
Dimmer
114V output
120V output
NEU
GND
HOT
GND
NEU
12V
NEU
GND
11V
12V
13V
11V
12V
13V
GND
NEU
{
HOT
{
GND
OR
24V
26V
TAP 1
TAP 2
13V
Secondary
Circuit Breaker
2.5A
4 A
5 A
14 AWG
14 AWG
14 AWG
-
60W
120W
60W
100W
120W
L.V.
Gauge
Max Load
12V
Max Load
24V
Secondary Breaker Amperage
*
* L.V. = wiring per NEC - wire must be sized to be equal to or greater than shown.
#14 12V
#14 TYP.
#14
#14
#12
#12
#10 #10 #10 #10
#14
#14
#12
#12
#12
#14
25A #10
25A #10
100W
100W
12V
12V 12V
A. B.
C. D.
24V
Equal Gauge - Equal Length
Equal Gauge - Equal Length
Vary Wire Gauge to Keep Voltage Equal
Vary Wire Gauge to Keep Voltage Equal
200W
Transformer
15’
15’
35’
35’
15’
15’
15’
15’
Diagram A. Diagram B.
Diagram C. Diagram D.
DO NOT USE THIS METHOD TO WIRE YOUR LOW-VOLTAGE FIXTURES!
INSTALLATION Q6S/Q6M
© 2020 Q-Tran Inc. All rights reserved | 155 Hill St. Milford, CT 06460 | 203-367-8777 | [email protected] | www.q-tran.com Specification subject to change. Rev-09-29-20
Rough In Wiring
Example:
25A max per NEC 411: use #10 AWG min
For 20A, use #12 AWG min
For 15A use #14 AWG min
Please note amperage may increase with higher taps.
L.V. = Class 1 wiring per NEC - wire must be sized to be
equal to or greater than shown.
When the voltage goes down by a factor of 10 (120V to 12V) the
amperage goes up by a factor of 10 (2.5A to 25A)
Primary Secondary
Secondary
Circuit Breaker
5A
10A
15A
20A
25A
L.V.
Gauge
14 AWG
14 AWG
14 AWG
12 AWG
10 AWG
Max Load
12V
60W
120W
180W
240W
300W
Max Load
24V
120W
240W
360W
480W
600W
12V
25A
120V
2.5A
Transformer
300VA #10 AWG min
= 2.5A = 25A
300VA
120V
300VA
12V
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
NOTE: Switch or dimmer are always on the primary
15A circuit breaker
use #14 AWG minimum
20A circuit breaker
use #12 AWG minimum
The neutral must be clean.
Run a “virgin” neutral for each PSC.
Low Voltage Runs = High Amps Secondary Breaker Amperage
Keep Runs Short! Get The Tap Right!
Get The Wire Gauge Right
Both primary and secondary wiring to be Class 1 per
NEC unless Class 2 option is ordered
Download our Voltage Drop Calculator at:
www.Q-Tran.com
120V Primary 12V Secondary2.5A Primary
114V when dimmer
is @ full bright 25A max
per L.V. load
300VA 300VA
120V switch
INSTALLATION Q6S/Q6M
© 2020 Q-Tran Inc. All rights reserved | 155 Hill St. Milford, CT 06460 | 203-367-8777 | [email protected] | www.q-tran.com Specification subject to change. Rev-09-29-20
Rough In Wiring
Equalizing Voltage Drop
When installing multiple fixtures or loads from a single remote PSC,
it is important to have approimately the same voltage at each lamp.
Many installations require different length runs to the loads which
may require different wire gauges to equalize the voltage. It is
important to have approximately the same voltage at each lamp so
the light output appears to be the same. Use Q-Tran’s Voltage Drop
Calculator to easily determine the correct wire gauge.
3 Key Points you must know:
1 - The voltage of the lamp specified
2 - The amperage rating of the product
3 - The maximum wire gauge that can be terminated at the load. A
number 6 or 8 gauge wire, for instance, can not be terminated on
most L.V. products.
Diagram A - For 12V track, rail, or cable system that is rated for
25A requires a minimum of #10 gauge wire. Runs should be
approximately the same length.
Diagram B - For LV cove lighting, the VDC might show you to vary
the wire gauge to equalize the voltage at the lamp. Running the
same gauge wire to all runs may be wrong.
Diagram C - For recessed or mono point fixtures powered from a
single PSC, it is a recommended that all secondary runs be the
same length and the same gauge; EQUAL LENGTH - EQUAL
GAUGE. All surplus wire must not be coiled but made into a long
loop.
Diagram D - For commerical installations requiring conduit, this
diagram shows an alternate wiring method. Also applicable to
residential installations.
Diagram A.
Equal Gauge - Equal Length
Vary Wire Gauge to Keep Voltage Equal
Equal Gauge - Equal Length
Vary Wire Gauge to Keep Voltage Equal
Diagram B.
Diagram C.
Must go back to the PSC as shown in example C or D.
DO NOT USE THIS METHOD!
Diagram D.
INSTALLATION Q6S/Q6M
© 2020 Q-Tran Inc. All rights reserved | 155 Hill St. Milford, CT 06460 | 203-367-8777 | [email protected] | www.q-tran.com Specification subject to change. Rev-09-29-20
Connecting and Configuring
B
E
A
C
B
D
PRIMARY (Input Wires)
SECONDARY (Output Wires)
CHOKE
Standard on all units
TRANSFORMER
Small – 50W - 300W
DIVIDER
A
B
C
D
E
Input voltage is fixed and can only be changed
at the factory. Input voltage is indicated on side
of the housing.
Medium – 500W - 750W
Large – 900W - 1800W
Secondary Circuit Breakers
Secondary Common
DO NOT EXCEED TOTAL AMPS OF SECONDARY
CIRCUIT BREAKERS
Output voltage is wired as ordered (12V or 24V)
but can be changed by a licensed electrician.
CHOKE
GREEN
GND
NEU
HOT
GND
NEU
HOT
GND
WHITE
TAP1 (120V)
BLACK
ORANGE
(277V)
WHITE BROWN
BLUE
YELLOW
VIOLET
Tp
Bkr(s).
PRIMARY
VOLTAGE
12V
WIRING DIAGRAM
24V
WIRING DIAGRAM
SECONDARY
12 VAC
Ɣ USE WIRE NUTS OR TERMINAL BLOCKS FOR LOAD CONNECTIONS
Ɣ DASHED LINES INDICATE ELECTRICAL CONTRACTOR WIRING
L
O
A
D
L
O
A
D
OR
TAP2
(120V)
GREY
RED
(277V)
CHOKE
GREEN
GND
WHITE
TAP1 (120V)
BLACK
ORANGE
(277V)
WHITE BROWN
BLUE
YELLOW
VIOLET
Tp
Bkr(s).
PRIMARY
VOLTAGE SECONDARY
24 VAC
Ɣ USE WIRE NUTS OR TERMINAL BLOCKS FOR LOAD CONNECTIONS
Ɣ DASHED LINES INDICATE ELECTRICAL CONTRACTOR WIRING
L
O
A
D
L
O
A
D
OR
TAP2
(120V)
GREY
RED
(277V)
4.50"
Q6 WIRING DIAGRAM
3.50"
If a transformer is wired from the factory for 12V,
for 24V secondary wiring: Disconnect the blue and
yellow wires from terminal blocks and connect
together with wire nut. The brown wire now
becomes the common side of the load, and the
violet wire should be connected to the secondary
circuit breaker, which is the line side of the load.
Please refer to the wiring diagrams on this page.
12 24
If a transformer is wired from the factory for
24V, for 12V secondary wiring: Disconnect the
blue and yellow wires from terminal block.
Connect yellow and brown wire into terminal
block, which becomes the common side of the
load. Connect blue and violet wires into
terminal block, which should be connected to
the secondary circuit breaker(s) which
becomes the line side of the load Please refer
to the wiring diagrams on this page.
24 12
Auto reset thermal circuit breaker mounted to core of toroid Hydraulic magnetic manual reset circuit breakers
Tp
Terminal block connection
Polarity
Choke or inductor on primary
to reduce inrush current.
INSTALLATION Q6S/Q6M
© 2020 Q-Tran Inc. All rights reserved | 155 Hill St. Milford, CT 06460 | 203-367-8777 | [email protected] | www.q-tran.com Specification subject to change. Rev-09-29-20
Troubleshooting and Warnings
Risk of Fire / Electric Shock
Transformer should be installed by a
Licensed electrician in accordance with
the N.E.C. and all local codes in force.
Wear rubber shoes and work on a sturdy wooden or fiberglass ladder.
This power supply must be installed according to the National Electric
Code and local codes and ordinances.
This power supply is to be installed and serviced only by an licensed
electricians.
This power supply is to be installed so that it is not likely to be contacted
by people.
To avoid a hazard to children, account for all parts and destroy all
packaging materials.
This power supply is to be installed and serviced only by an licensed
electrician.
Do not install in wet locations.
1Panel Adjustments 2Dimmer or Switch
Adjustments
3Transformer
Adjustments
4Load
Adjustments
Dimmer
Lighting
Panel
Q-Tran (PSC)
Power Supply Center Load
SecondaryPrimary Primary
Primary
circuit breaker
Secondary
circuit breaker
Switch
Circle oneWire gauge Wire gauge
Impedance is important and used to calculate the maximum short circuit current which is need for sizing, circuit breakers and fuses.
Lower values of impedance will provide a reduction in regulation for a given load. The regulation is the ration of output voltage at a specified load,
compared to the output voltage at no load.
Q-TRAN’S TRANSFORMERS HAVE IMPEDANCE IN THE RANGE OF 2 % - 5 %
Impedance is expressed as a percent. This percentage represents the amount of normal rated primary voltage which must be applied
to the Transformer to produce full rated load current when the secondary windings is short circuited.
The Impedance of most ordinary transformers runs between 3% and 6%.
The maximum short circuited current is limited by the impedance of the transformer
If the load impedance is too low this will increase the current in the transformer windings. This also reduces the primary impedance that the output sees which increases tube current flow.
If the load impedance is too high, this reflects a higher than normal impedance in the primary for the output.
If the transformer has 5 % (.05) impedance, the reciprocal of .05 is 20 and maximum short circuit current is 20 times the full load current.
If the transformer has 10 % (.1) impedance. The reciprocal of .1 is 10 therefore the maximum short circuit current is 10 times the full load current.
Wire gauge
Model number
Watts per run
Total watts
Wire length
Primary feed circuit breaker
Manufacturer:
Model number:
Amperage:
Note: To properly assist you with any trouble shooting support, please fill out your information on the lines provided.
Manufacturer:
Model number:
*
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Risk of Fire / Electric Shock
Transformer should be installed by a
Licensed electrician in accordance with
the N.E.C. and all local codes in force.
Wear rubber shoes and work on a sturdy wooden or fiberglass ladder.
This power supply must be installed according to the National Electric
Code and local codes and ordinances.
This power supply is to be installed and serviced only by an licensed
electricians.
This power supply is to be installed so that it is not likely to be contacted
by people.
To avoid a hazard to children, account for all parts and destroy all
packaging materials.
This power supply is to be installed and serviced only by an licensed
electrician.
Do not install in wet locations.
1Panel Adjustments 2Dimmer or Switch
Adjustments
3Transformer
Adjustments
4Load
Adjustments
Dimmer
Lighting
Panel
Q-Tran (PSC)
Power Supply Center Load
SecondaryPrimary Primary
Primary
circuit breaker
Secondary
circuit breaker
Switch
Circle oneWire gauge Wire gauge
Impedance is important and used to calculate the maximum short circuit current which is need for sizing, circuit breakers and fuses.
Lower values of impedance will provide a reduction in regulation for a given load. The regulation is the ration of output voltage at a specified load,
compared to the output voltage at no load.
Q-TRAN’S TRANSFORMERS HAVE IMPEDANCE IN THE RANGE OF 2 % - 5 %
Impedance is expressed as a percent. This percentage represents the amount of normal rated primary voltage which must be applied
to the Transformer to produce full rated load current when the secondary windings is short circuited.
The Impedance of most ordinary transformers runs between 3% and 6%.
The maximum short circuited current is limited by the impedance of the transformer
If the load impedance is too low this will increase the current in the transformer windings. This also reduces the primary impedance that the output sees which increases tube current flow.
If the load impedance is too high, this reflects a higher than normal impedance in the primary for the output.
If the transformer has 5 % (.05) impedance, the reciprocal of .05 is 20 and maximum short circuit current is 20 times the full load current.
If the transformer has 10 % (.1) impedance. The reciprocal of .1 is 10 therefore the maximum short circuit current is 10 times the full load current.
Wire gauge
Model number
Watts per run
Total watts
Wire length
Primary feed circuit breaker
Manufacturer:
Model number:
Amperage:
Note: To properly assist you with any trouble shooting support, please fill out your information on the lines provided.
Manufacturer:
Model number:
*
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5

WarmlyYours Qtran Transformer Installation guide

Category
Dimmers
Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI