STIEBEL ELTRON WPM G_COMMISSIONING Operation Instruction

Type
Operation Instruction
COMMISSIONING
Programming unit
» WPM G
2 | WPM G www.stiebel-eltron.com
CONTENTS
COMMISSIONING
1. General information �����������������������������������������3
1.1 Relevant documents_____________________________________________ 3
1.2 Safety instructions _______________________________________________ 3
1.3 Other symbols in this documentation _______________________ 3
1.4 Units of measurement __________________________________________ 3
2. Safety ���������������������������������������������������������� 3
2.1 Instructions, standards and regulations ____________________ 3
2.2 General safety instructions ____________________________________ 3
2.3 Notes _______________________________________________________________ 3
2.4 Test symbols ______________________________________________________ 3
3. Appliance description ���������������������������������������4
3.1 Accessories ________________________________________________________ 4
4. Operation �����������������������������������������������������4
4.1 Symbols ____________________________________________________________ 4
5. Commissioning �����������������������������������������������4
5.1 Setting the language ____________________________________________ 4
5.2 Setting date and time ___________________________________________ 4
5.3 Network connection _____________________________________________ 5
5.4 Commissioning cascades _______________________________________ 6
5.5 Manual test _______________________________________________________ 8
6. Controller menu ����������������������������������������������8
Notification list ___________________________________________________ 8
Settings ____________________________________________________________ 9
Language __________________________________________________________ 9
System settings __________________________________________________ 9
SMART GRID ______________________________________________________ 9
Heat pump _______________________________________________________ 10
Heating ___________________________________________________________ 11
DHW _______________________________________________________________ 11
Dynamic allocation setting ___________________________________ 12
Booster heater __________________________________________________ 12
Hot gas ____________________________________________________________ 13
DHW draw-off control _________________________________________ 13
Water charging system ________________________________________ 14
Pool ________________________________________________________________ 14
Mixing valves ____________________________________________________ 15
Cooling ____________________________________________________________ 16
Cascade control _________________________________________________ 18
Building management system (BMS) _______________________ 19
Buffer cylinder __________________________________________________ 19
Alarm control/central alarm __________________________________ 20
Circulation pumps ______________________________________________ 20
Stage speed setting ____________________________________________ 21
Energy management ___________________________________________ 21
Modbus ___________________________________________________________ 21
Manual test ______________________________________________________ 21
Communication analysis ______________________________________ 24
Process data _____________________________________________________ 24
Operating mode _________________________________________________ 25
7. Additional menus ������������������������������������������ 25
7.1 Heat settings _____________________________________________________ 25
7.2 DHW settings ____________________________________________________ 26
COMMISSIONING
General information
www.stiebel-eltron.com WPM G | 3
1. General information
These instructions are intended for qualified contractors.
1.1 Relevant documents
Operating instructions for the programming unit
Heat pump operating and installation instructions
Operating and installation instructions for system
components
Note
Please see appliance operating instructions for infor-
mation on the “Guarantee” and “Environment and re-
cycling”.
1.2 Safety instructions
1.2.1 Structure of safety instructions
!
KEYWORD Type of risk
Here, possible consequences are listed that may result
from failure to observe the safety instructions.
Steps to prevent the risk are listed.
1.2.2 Symbols, type of risk
Symbol Type of risk
Injury
Electrocution
1.2.3 Keywords
KEYWORD Meaning
DANGER Failure to observe this information will result in serious
injury or death.
WARNING Failure to observe this information may result in serious
injury or death.
CAUTION Failure to observe this information may result in non-seri-
ous or minor injury.
1.3 Other symbols in this documentation
Note
General information is identified by the adjacent symbol.
Read these texts carefully.
Symbol Meaning
Material losses
(appliance damage, consequential losses and environmen-
tal pollution)
Appliance disposal
This symbol indicates that you have to do something. The ac-
tion you need to take is described step by step.
 These symbols show you the software menu level (in
this example level3).
1.4 Units of measurement
Note
All measurements are given in mm unless stated oth-
erwise.
2. Safety
Only a qualified contractor should carry out installation, commis-
sioning, maintenance and repair of the appliance.
2.1 Instructions, standards and regulations
Note
Observe all applicable national and regional regulations
and instructions.
2.2 General safety instructions
We guarantee trouble-free function and operational reliability only
if original accessories and spare parts intended for the appliance
are used.
2.3 Notes
- The appliance should only be operated once it is fully in-
stalled and all safety equipment has been fitted.
2.4 Test symbols
See type plate on the appliance.
!
!
COMMISSIONING
COMMISSIONING
Appliance description
4 | WPM G www.stiebel-eltron.com
3. Appliance description
The appliance is responsible for the processes that control and
regulate the heat pump. The appliance allows remote monitoring
and heating system control via the internet.
If multiple heat demands exist simultaneously, the appliance
switches back and forth between the demands. If a booster heater
is activated, DHW heating can run at the same time as the heating
mode and swimming pool heating.
3.1 Accessories
The following accessories can be installed for additional control
of the heat pump.
- Extension module
4. Operation
4.1 Symbols
Additional symbols are explained in the corresponding chapter.
Symbol Meaning
Call up main menu
Call up start screen
Authorisation code required
Confirm settings
Unconfirmed settings are reset to the previous
value.
Cancel settings
Scroll back one page
Scroll forward one page
Back
Reset to factory settings
The values on the current menu page are reset
to the factory settings.
Activate or deactivate functions
The symbol shows the activated function.
Activate or deactivate functions
The symbol shows the deactivated function.
Select one of two options
Symbol Meaning
Select one of two options
5. Commissioning
Note
If a restart of the heat pump is required, the symbol is
displayed on the appliance.
Note
Some setting options are only available in safe mode.
Once you have entered the access code, it does not need
to be re-entered for eight hours. The remaining time is
displayed top left of the screen.
Press the button on the start screen to open the main
menu.
Press the button to access safe mode.
Enter the following access code: 607080
Confirm the selection.
5.1 Setting the language
Press the button on the start screen to open the main
menu.
Press the button.
Press the “Language” menu.
Press the button to access the required language.
Select the required language.
either
Press the button to return to the higher ranking
menu.
or
Press the button to return to the main menu.
5.2 Setting date and time
Note
The primary heat pump transfers the date and time set-
tings to the secondary heat pumps.
ON
OFF
0
1
COMMISSIONING
Commissioning
www.stiebel-eltron.com WPM G | 5
Press the button on the start screen to open the main
menu.
Press the button.
Press the “System settings” menu.
Press the “Date/time” menu.
Make the required changes.
Confirm the selection.
either
Press the button to return to the higher ranking
menu.
or
Press the button to return to the main menu.
5.3 Network connection
Note
Please note that, for example, firewalls and faulty
connections may cause problems that prevent full
functionality.
If problems occur, contact your internet provider or
network administrator.
The appliance can be used to monitor the heating system via the
internet. For monitoring, you will need an internet connection,
a router and the Internet Service Gateway (ISG). Refer to the ISG
operating and installation instructions. Use of the ISG is only pos-
sible in conjunction with dynamic assignment of the IP address.
5.3.1 Connecting to the internet
Connect a patch cable to the RJ45 connector (see chapter
“Commissioning / Connecting to the internet” in the operat-
ing and installation instructions for the heat pump).
5.3.2 Network settings
Note
If multiple heat pumps are installed, the network
settings must be entered separately for each heat
pump.
Note
If settings are required on a router or other network
component, contact the network administrator.
The connection can be established via DHCP or a static IP address.
Ensure that you select the same connection for all heat pumps.
Press the button on the start screen to open the main
menu.
Press the button.
Select the “System settings” menu.
Select the “Network settings” menu.
Connection via DHCP
Note
Use dynamic assignment of the network address if
the heat pump is integrated in a network.
Slide the switch to the corresponding position.
Enter the required information in the corresponding
fields.
either
Press the button to return to the higher ranking
menu.
or
Press the button to return to the main menu.
0
COMMISSIONING
Commissioning
6 | WPM G www.stiebel-eltron.com
Connection via a static IP address
Note
Use static assignment of the network address if the
heat pump is not integrated in a network.
Note
The router is only needed for setup via an external net-
work connection and for multiple secondary heat pumps.
Note
Do not change the setting in the network mask
(255.255.255.0).
Slide the switch to the corresponding position.
Enter the required information in the corresponding
fields.
Confirm the selection.
either
Press the button to return to the higher ranking
menu.
or
Press the button to return to the main menu.
5.4 Commissioning cascades
Note
Only one heat pump can be defined as the primary heat
pump in the heating system.
5.4.1 Setting up the primary and secondary heat pump
Note
When connecting heat pumps of a different series, ob-
serve the instructions regarding the “SETTINGS”/ “Cas-
cade control” menu.
Press the button on the start screen to open the main
menu.
Press the button.
Tap the button to access the “Cascade control” menu.
Select the “Cascade control” menu on the primary
heat pump.
Set the DIP switch to “Master=1”.
Adjust the necessary settings.
Confirm the selection.
Select the “Cascade control” menu on the secondary
heat pump.
Set the DIP switch to “Slave=0”.
Assign a heat pump ID ≥1 to the secondary heat
pump. Assign IDs in chronological order for further
secondary heat pumps.
Adjust the necessary settings.
Confirm the selection.
Follow the same sequence for additional secondary
heat pumps.
either
Press the button to return to the higher ranking
menu.
or
Press the button to return to the main menu.
Press the button.
Restart the primary heat pump.
Restart the secondary heat pumps.
If there is communication between the primary and secondary
heat pump, the heat pump ID is displayed on the secondary heat
pump screen.
Example: Without external network connection (for cascades
with only one secondary heat pump)
Note
Monitoring via the internet is not possible.
If you want to set up monitoring via the internet,
refer to the example “With external network con-
nection (for cascades with one or more secondary
heat pumps).
Use an Ethernet cable (Standard Cat 5 network cable, RJ45
connector).
Connect the heat pumps via the connection on the program-
ming unit. Observe chapter “Installation/ Removing the cas-
ing parts” in the operating and installation instructions for
the heat pump.
1
COMMISSIONING
Commissioning
www.stiebel-eltron.com WPM G | 7
D0000084758
1 2
1 Primary heat pump (e.g. IP address: 192.168.0.100)
2 Secondary heat pump (e.g. IP address: 192.168.0.101)
Example: With external network connection (for cascades with
one or more secondary heat pumps)
D0000084757
1
2
6 7 8 9 x
4
3
5
1 Router/ Switch
2 Internet access via router
3 Online web browser
4 Online webserver and database
5 Internet Service Gateway (ISG)
6 Primary heat pump (e.g. IP address: 192.168.0.100)
7 Secondary heat pump (e.g. IP address: 192.168.0.101)
8 Secondary heat pump (e.g. IP address: 192.168.0.102)
9 Secondary heat pump (e.g. IP address: 192.168.0.103)
x Secondary heat pump (e.g. IP address: 192.168.0.xxx)
5.4.2 Notifications
If one of the following messages appears, the primary heat pump
will no longer control the corresponding secondary heat pump for
the duration of the message.
Message Cause Remedy
Version error
The software version
of the secondary heat
pump is not identical
to the software ver-
sion of the primary
heat pump.
Have our customer
support install the
correct software ver-
sion.
Message Cause Remedy
Heat pump al-
ready registered
The secondary heat
pump is registered
under a different ID.
In the settings,
change the ID to the
first assigned ID or re-
start the primary heat
pump.
ID already regis-
tered
The ID has been as-
signed to another sec-
ondary heat pump.
Change the ID.
Multiple errors Several of the above
messages are active.
Remedy the errors
one after the other.
The corresponding secondary heat pump must be reconnected
manually to the primary heat pump. The connection can be es-
tablished in two ways.
either
Press the button.
or
Check the settings.
Make any necessary changes.
Press the button to return to the main menu.
Press the button.
Restart the primary heat pump.
Restart the secondary heat pumps.
5.4.3 Defining the operating mode
For each heat pump, you need to define which heat pump is ena-
bled for which heat demand. The heat pumps can be enabled for
heating mode, DHW heating, swimming pool heating and cooling.
Activate the function in the corresponding menu.
Example: Enable heating mode
Press the button on the start screen to open the main
menu.
Press the button.
Select the “Heating” menu.
Activate the function.
either
Press the button to return to the higher ranking
menu.
or
Press the button to return to the main menu.
ON
COMMISSIONING
Controller menu
8 | WPM G www.stiebel-eltron.com
5.5 Manual test
Note
Observe the chapter “Commissioning / Manual test
of connected components” in the operating and in-
stallation instructions for the heat pump.
Note
A hand is displayed when the manual test is activated.
All settings carried out now do not lead to any parameter
changes at the heat pump.
5.5.1 Activate manual test
Press the button on the start screen to open the main
menu.
Press the button.
Tap the button to access the “Manual test” menu.
Press the “Manual test” menu.
Activate the function.
Select the required test in the submenu.
5.5.2 End manual test
Press the button on the start screen to open the main
menu.
Press the button.
Tap the button to access the “Manual test” menu.
Press the “Manual test” menu.
Deactivate the function.
6. Controller menu
Note
Some setting options are only available in safe mode.
Once you have entered the access code, it does not need
to be re-entered for eight hours. The remaining time is
displayed top left of the screen.
Note
Certain menu items are protected by a code. The facto-
ry-set code is 607080.
Notification list
Settings
Language
System settings
SMART GRID
Heat pump
Heating
DHW
Dynamic allocation setting
Booster heater
Hot gas
DHW draw-off control
Water charging system
Pool
Mixing valves
Cooling
Cascade control
Building management system (BMS)
Buffer cylinder
Alarm control/central alarm
Circulation pumps
Stage speed setting
Energy management
Modbus
Manual test
Communication analysis
Process data
Operating data
Operating time
Version information
Graphs
Reason for stop
Operating mode
Notification list
In this view, you can see the last 100 active and acknowledged
error messages. The list is updated every minute and every time
the appliance is started.
ON
OFF
COMMISSIONING
Controller menu
www.stiebel-eltron.com WPM G | 9
Settings
Language
Set the required system language.
System settings
 Network settings
 Date/time
 Display settings
 Brightness
 Logging
 Network settings
The internet connection can be established via DHCP or a static
IP address.
Adjust the necessary settings. Observe the description in the
chapter “Commissioning/ Network connection/ Network
settings”).
 Date/time
Set the current date and current time.
 Display settings
 Brightness
Set the required brightness of the display backlighting.
 Logging
Note
Do not adjust the time during logging.
The controller allows you to export log files that can be read on
a computer. When a report is being logged, the data is recorded
directly onto the USB stick and not on the internal memory. Older
data is not displaced.
Insert a USB stick into the USB port.
Activate the “Logging” function. Report logging starts.
If the menu cannot be activated, remove the USB stick. Re-
turn to the menu. Insert the USB stick into the USB port.
If the menu still cannot be activated, replace the USB stick.
If you want to terminate the report logging, deactivate the
Logging” function.
A message appears when the report logging has finished.
Remove the USB stick.
SMART GRID
 Room temperature increase – accelerated mode
 Room temperature increase – maximum mode
 DHW start temperature – accelerated mode
 DHW stop temperature – accelerated mode
 DHW start temperature – maximum mode
 DHW stop temperature – maximum mode
Note
When the SG Ready function is being used, no other
power supply utility (PSU) function (power-OFF) is avail-
able.
The two digital inputs allow four different operating modes.
Smart
grid 1
Smart
grid 2
Operating
mode
Description
0 0 Standard Standard operation
0
1
Comfort buff-
er cylinder
Increased start and stop tem-
perature for DHW heating.
The room temperature is
increased.
1
0
EVU
The function blocks compres-
sor operation and the internal
flanged immersion heater.
Other components continue
to be controlled.
1
1
Boost
Increased start and stop
temperature for DHW heat-
ing. The room temperature
is increased. When the DHW
temperature in the DHW
cylinder is 2°C below the
stop temperature for the
anti-legionella program, the
program will start.
Buffer cylin-
der
The required DHW temper-
ature is set to 55°C. If the
Allow booster heater during
maximum mode” function is
activated in the programming
unit, the internal flanged im-
mersion heater is used.
 Room temperature increase – accelerated mode
Set by how much more the room will be heated in °C.
 Room temperature increase – maximum mode
Set by how much more the room will be heated in °C.
 DHW start temperature – accelerated mode
Set the temperature at which DHW heating starts.
 DHW stop temperature – accelerated mode
Set the temperature at which DHW heating ends.
COMMISSIONING
Controller menu
10 | WPM G www.stiebel-eltron.com
 DHW start temperature – maximum mode
Set the temperature at which DHW heating starts.
 DHW stop temperature – maximum mode
Set the temperature at which DHW heating ends.
Heat pump
 Brine pressure switch
 Compressor start-up delay
 Attempt restart if pressure drops/ Activate start attempts if pressure/
flow problems occur
 Only during compressor operation
 Brine outlet monitoring
 Brine alarm
 Min. brine outlet
 Alarm limit, brine temperature spread
 Brine inlet monitoring
 Min. brine inlet
 Switching delay, ramp up
 Switching delay, ramp down
 Maximum flow temperature
 Maximum return temperature
 Brine pressure switch
Activate or deactivate the function.
When the function is activated, the brine pressure is controlled.
 Compressor start-up delay
Only available if the “Brine pressure switch” function is switched
on.
Set the time period, during which only the brine pump oper-
ates before the compressor starts.
 Attempt restart if pressure drops/ Activate start
attempts if pressure/flow problems occur
Can only be activated if the “Brine pressure switch” function is
switched on.
Activate or deactivate the function.
 Only during compressor operation
Can only be activated if the “Brine pressure switch” function is
switched on.
Activate or deactivate the function.
When the function is activated, monitoring takes place while the
compressor is running.
 Brine outlet monitoring
Activate or deactivate the function.
When the function is activated, the appliance controls the outlet
temperature of the brine out of the heat pump. If the temperature
falls below the set value, the brine pump and the compressor are
switched off.
 Brine alarm
Activate or deactivate the function.
When the function is activated, an error message appears on the
appliance when the value falls below the set temperature.
 Min. brine outlet
Can only be adjusted if the “Brine outlet monitoring” function is
activated.
Set the minimum brine outlet temperature.
 Alarm limit, brine temperature spread
Set a temperature differential between the brine inlet and
brine outlet temperatures.
If there is a deviation from the set temperature differential, an
error message is displayed on the appliance. The heat pump is
switched off.
 Brine inlet monitoring
Activate or deactivate the function.
When the function is activated, the appliance controls the inlet
temperature of the brine into the heat pump. If the temperature
falls below the set value, the brine pump and the compressor are
switched off.
 Min. brine inlet
Set the minimum brine inlet temperature.
 Switching delay, ramp up
Can only be adjusted if the “Brine inlet monitoring” function is
activated.
Set the time after which the brine pump output is increased,
if the brine temperature is above the minimum temperature.
 Switching delay, ramp down
Can only be adjusted if the “Brine inlet monitoring” function is
activated.
Set the time after which brine pump output is reduced, so
the brine temperature does not fall too quickly.
 Maximum flow temperature
Set the maximum flow temperature.
 Maximum return temperature
Set the maximum return temperature.
COMMISSIONING
Controller menu
www.stiebel-eltron.com WPM G | 11
Heating
 Heating mode
 Heating time
 Minimum compressor stage
 Maximum compressor stage
 Compressor switching delay
 Activate room sensor
 Room temperature sensor
 Passive = 0, active = 1
 Influence of room temperature sensor
 Calculated start/stop threshold
 Heating mode
Activate or deactivate the function.
When the function is activated, the corresponding symbol ap-
pears in the main menu. The symbol allows you quick access to
another menu. Observe the information regarding the menu in
chapter “Further menus/ Heating settings” in these instructions
and “Settings/ Adjusting the temperature (central heating)/ In the
“Heating” menu” in the operating instructions for the appliance.
 Heating time
Set how long the heat pump is responsible for heating when
there is a heating demand.
 Minimum compressor stage
Set the minimum stage at which the heat pump should run to
meet the heating demand.
 Maximum compressor stage
Set the maximum stage at which the heat pump should run
to meet the heating demand.
 Compressor switching delay
A delay prevents the different output stages switching on or off
too quickly.
Set the time that must pass until the next output stage
switches on or off.
 Activate room sensor
Can only be activated if a module for the room sensor has been
selected.
Activate or deactivate the function.
When the function is activated, the sensor measures the current
room temperature.
 Room temperature sensor
Set the module to which the sensor is connected.
 Passive = 0, active = 1
Can only be activated if a module for the room sensor has been
selected.
Set whether the temperature is measured actively or passive-
ly.
If the temperature is measured actively, the room sensor influ-
ences the heating mode.
 Influence of room temperature sensor
Set whether the room sensor only measures the temperature
or also helps to control the room temperature. The higher the
value, the more influence the room sensor has.
 Calculated start/stop threshold
DHW
 System DHW mode
 System DHW mode
 Primary heat pump DHW mode
 DHW mode start temp.
 DHW mode stop temp.
 Sensor influence
 DHW mode max. runtime
 Circulation pump min. speed
 Circulation pump max. speed
 Minimum compressor stage
 Maximum compressor stage
 Pasteurisation mode
 Max. heating phase
 Pasteurisation mode max. runtime
 Pasteurisation mode stop temp.
Parameter Unit
DHW temp. (top) °C
The DHW temperature captured by the top sensor
DHW temp. (weighted) °C
Calculated DHW temperature between the top and
bottom DHW temperature, including the “Sensor in-
fluence” effect.
DHW temp. (bottom) °C
The DHW temperature captured by the bottom sensor
 System DHW mode
Activate or deactivate the function.
When the function is activated, the corresponding symbol appears
in the main menu. The symbol allows you quick access to another
menu. Observe the menu description in the chapter “Additional
menus / DHW settings”.
 DHW mode
Activate or deactivate the function.
When the function is activated, the corresponding symbol appears
in the main menu. The symbol allows you quick access to another
menu. Observe the menu description in the chapter “Additional
menus / DHW settings”.
COMMISSIONING
Controller menu
12 | WPM G www.stiebel-eltron.com
 Primary heat pump DHW mode
Can only be set when the “System DHW mode” function is acti-
vated.
Activate or deactivate the function.
When this function is activated, DHW heating is carried out by the
primary heat pump.
 DHW mode start temp.
Set the DHW temperature at which DHW heating starts.
 DHW mode stop temp.
Set the DHW temperature at which DHW heating stops.
 Sensor influence
Set how the influence is shared between the top and bottom
sensor.
If you set a mid-range value, the top and bottom sensors have the
same amount of influence.
 DHW mode max. runtime
Set how long the heat pump is to be responsible for DHW
heating when there is a DHW demand.
When this time has expired, the appliance checks if there is a heat
demand. If there is a heat demand, this demand is processed by
the heat pump.
 Circulation pump min. speed
Set the minimum output at which the circulation pump
should run to meet the DHW demand.
 Circulation pump max. speed
Set the maximum output at which the circulation pump
should run to meet the DHW demand.
 Minimum compressor stage
Set the minimum stage at which the heat pump should run to
meet the DHW demand.
 Maximum compressor stage
Set the maximum stage at which the heat pump should run
to meet the DHW demand.
 Pasteurisation mode
Activate or deactivate the function.
When the function is activated, the DHW in the DHW cylinder is
heated according to the settings.
 Max. heating phase
Set the number of days until the pasteurisation program next
starts up.
 Pasteurisation mode max. runtime
Set the duration for which the pasteurisation program is to
run.
 Pasteurisation mode stop temp.
Set the temperature which must be reached before the pas-
teurisation program is terminated.
Dynamic allocation setting
Some connections on the heat pump controller can have other
functions assigned to them. Observe the details in the operating
and installation instructions for the heat pump (chapter “Electrical
connection/ Dynamic allocation”).
Set which functions you would like to use on which module.
If an assignment isn’t possible, the selection is shown in red.
Booster heater
 Activate booster heater
 Temporarily deactivate external booster heater
 Outside temperature-dependent
 Outside temperature limit
 Start delay
 Start limit calculated demand
 Stop limit calculated demand
 Heat-up time
 Cooldown time
 Deactivate cooldown time delay
 System flow offset
 Accounting period
 P
 I
 Minimum opening level
 Maximum opening level
Parameter Unit
Feedback, opening level %
 Activate booster heater
Activate or deactivate the function.
When the function is activated, the booster heater switches on as
the last output stage when there is a heat demand.
 Temporarily deactivate external booster heater
Activate or deactivate the function.
 Outside temperature-dependent
Activate or deactivate the function.
When this function is activated, the booster heater is activated at
the set outside temperature.
COMMISSIONING
Controller menu
www.stiebel-eltron.com WPM G | 13
 Outside temperature limit
Can only be adjusted if the “Outside temperature-dependent
function is activated.
Set the outside temperature from which the booster heater
will support the heat pump.
 Start delay
A delay prevents the booster heater switching on too quickly when
there is a heat demand.
Set the time after which the booster heater will support the
heat pump.
 Start limit calculated demand
 Stop limit calculated demand
 Heat-up time
Set how long the booster heater will support the heat pump.
 Cooldown time
 Deactivate cooldown time delay
 System flow offset
 Accounting period
 P
 I
 Minimum opening level
 Maximum opening level
Hot gas
 Hot gas mode
 Hot gas start temp.
 Hot gas stop temp., lower limit
 Hot gas stop temp., upper limit
 Activate hot gas diverter valve
 Changeover temp.for cylinder charging with hot gas
 Hot gas mode
Activate or deactivate the function.
When the function is activated, hot gas can be used for DHW
heating.
 Hot gas start temp. Hot gas
Set the temperature at which hot gas is used for DHW heat-
ing.
 Hot gas stop temp., lower limit Hot gas
Set the minimum temperature at which the hot gas pump
switches off.
 Hot gas stop temp., upper limit Hot gas
Set the maximum temperature at which the hot gas pump
switches off.
 Activate hot gas diverter valve
Activate or deactivate the function.
 Changeover temp. for cylinder charging with hot gas
Can only be adjusted if the “Activate hot gas diverter valve” func-
tion is activated.
DHW draw-off control
 DHW draw-off control
 Selected module
 Set DHW draw-off temp.
 DHW alarm limit
 DHW alarm delay
 Alarm limit DHW return
 Alarm delay DHW return
 DHW draw-off control – booster heater
 DHW booster heater start temp.
 Booster heater start delay
 DHW booster heater stop temp.
Parameter Unit
DHW draw-off temp. °C
Current temperature at the draw-off points
DHW draw-off control return temp. °C
Current DHW return temperature
Hot gas temperature DHW °C
Current DHW temperature in the DHW cylinder
 DHW draw-off control
Can only be activated when a module is selected.
Activate or deactivate the function.
When the function is activated, DHW is delivered at the required
temperature at the draw-off points.
 Selected module
Set the module to which the necessary components are con-
nected.
 Set DHW draw-off temp.
Set the temperature to be supplied at the draw-off points.
 DHW alarm limit
Set a temperature at which an error message is displayed on
the appliance. This function prevents too high DHW tempera-
tures at the draw-off points.
COMMISSIONING
Controller menu
14 | WPM G www.stiebel-eltron.com
 DHW alarm delay
Set a time after which an error message is displayed on the
appliance. This function delays the appearance of an error
message on the appliance when the DHW temperature at the
draw-off points reaches the limit value.
 Alarm limit DHW return
Set a temperature at which an error message is displayed on
the appliance.
 Alarm delay DHW return
Set a time after which an error message is displayed on the
appliance.
 DHW draw-off control – booster heater
Activate or deactivate the function.
When this function is activated, the DHW between DHW cylinder
and draw-off points is further heated-up with the booster heater.
 DHW booster heater start temp.
Set the DHW temperature at which the booster heater will
support the heat pump.
 Booster heater start delay
Set the time after which the booster heater will support the
heat pump.
 DHW booster heater stop temp.
Set the DHW temperature at which the booster heater will
stop supporting the heat pump.
Water charging system
 Activate water charging system
 Selected module
 Set temperature
 Water charging system – activate hot gas function
 Alarm delay
 Alarm limit
Parameter Unit
Temperature °C
Current return temperature from heat exchanger to
heat pump
 Activate water charging system
Can only be activated when a module is selected.
Activate or deactivate the function.
 Selected module
Set the module to which the necessary components are con-
nected.
 Set temperature
 Water charging system – activate hot gas function
Activate or deactivate the function.
 Alarm delay
Set a time after which an error message is displayed on the
appliance.
 Alarm limit
Set a temperature at which an error message is displayed on
the appliance.
Pool
 Pool
 Selected module
 Set pool temperature
 Pool hysteresis
 Required heating temperature
 Minimum compressor stage
 Maximum compressor stage
 Switching delay
 Pool runtime
 Pool heating with booster heater
 Activate booster heater for pool
Parameter Unit
Pool return temperature °C
Current return temperature from the pool
Pool flow temperature °C
Current flow temperature to the pool
 Pool
Can only be activated when a module is selected.
Activate or deactivate the function.
When the function is activated, the heat pump can be used for
pool water heating. The corresponding symbol appears in the
main menu. The symbol allows you quick access to this menu.
 Selected module
Set the module to which the necessary components are con-
nected.
 Set pool temperature
Set the water temperature to which the pool should be heat-
ed.
COMMISSIONING
Controller menu
www.stiebel-eltron.com WPM G | 15
 Pool hysteresis
Set the temperature deviation from the set temperature, at
which heating of the swimming pool water starts.
Example
Pool hysteresis 3 °C
Set pool temperature 20 °C
Start swimming pool heating 18.5 °C
End swimming pool heating 21.5 °C
 Required heating temperature
Set the flow temperature at which the pool should be heated.
 Minimum compressor stage
Set the minimum stage at which the heat pump should run to
meet the swimming pool demand.
 Maximum compressor stage
Set the maximum stage at which the heat pump should run
to meet the swimming pool demand.
 Switching delay
Set the time after which the heat pump starts to run when
there is a swimming pool demand.
 Pool runtime
Set how long the heat pump is responsible for swimming
pool heating when there is a swimming pool demand.
When this time has expired, the appliance checks if there is a heat
demand. If there is a heat demand, this demand is processed by
the heat pump.
 Pool heating with booster heater
Activate or deactivate the function.
When the function is activated, the booster heater can be used to
support the heat pump for a swimming pool demand.
 Activate booster heater for pool
Can only be activated when the “Pool heating with booster heater
function is enabled.
Activate or deactivate the function.
When the function is activated, the booster heater can support the
heat pump when there is a swimming pool demand.
Mixing valves
 Heating circuit 1
 Activate heating circuit 1
 Heating = 0, cooling = 1
 Min. flow
 Max. flow
 Set/actual deviation
 Alarm delay
 Heating circuit 2 / 3 / 4 / 5
 Activate heating circuit x
 Selected module
 Min. flow
 Max. flow
 Activate room sensor
 Passive = 0, active = 1
 Set temperature
 Influence of room temperature sensor
Parameter Unit
Temperature °C
Current temperature in the heating system
Set temperature °C
Required temperature in the heating system
Opening level %
Current opening level of mixing valve
Room temperature °C
Temperature captured by room sensor
 Heating circuit 1
 Activate heating circuit 1
Activate or deactivate the function.
When the function is activated, the settings made here apply for
the corresponding heating circuit. The corresponding symbol ap-
pears in the main menu. The symbol allows you quick access to
this menu.
When the function is deactivated, the higher ranking settings are
used to control the heating circuit.
 Heating = 0, cooling = 1
Set whether the heating circuit is responsible for heating or
cooling operation.
 Min. flow
Set the minimum temperature for the system flow.
 Max. flow
Set the maximum temperature for the system flow.
 Set/actual deviation
Set the maximum temperature deviation at which an error
message is displayed on the appliance.
COMMISSIONING
Controller menu
16 | WPM G www.stiebel-eltron.com
 Alarm delay
Set a time after which an error message is displayed on the
appliance.
 Heating circuit 2 / 3 / 4 / 5
Note
The extension module is required for heating circuits 2-5.
Each extension module supports two heating circuits.
 Activate heating circuit x
Can only be activated when a module is selected.
Activate or deactivate the function.
When the function is activated, the settings made here apply for
the corresponding heating circuit. The corresponding symbol ap-
pears in the main menu. The symbol allows you quick access to
this menu.
When the function is deactivated, the higher ranking settings are
used to control the heating circuit.
 Selected module
Set the module to which the necessary components are con-
nected.
 Min. flow
Set the minimum temperature for the system flow.
 Max. flow
Set the maximum temperature for the system flow.
 Activate room sensor
Activate or deactivate the function.
When the function is activated, the sensor measures the current
room temperature.
 Passive = 0, active = 1
Set whether the temperature is measured actively or passive-
ly.
If the temperature is measured actively, the room sensor influ-
ences the heating mode.
 Set temperature
Set the temperature to which the assigned rooms should be
heated.
 Influence of room temperature sensor
Set whether the room sensor only measures the temperature
or also helps to control the room temperature. The higher the
value, the more influence the room sensor has.
Cooling
 Passive cooling
 Active cooling
 Selected module
 Surplus heat: Brine = 1, cooler = 2
 Summer mode cooling temperature
 Hot gas start temp. Cooling
 Shutdown temp. Cooling
 Minimum compressor stage
 Maximum compressor stage
 Switching delay
 Delay, directional valve, source
 Cooling – mixing valve
 Set cooling temperature
 Activate dew point sensor
 Alarm limit deviation
 Alarm delay
 Cooling – cylinder
 Alarm high limit
 Alarm delay
 Cooling – surplus heat
 Set return temperature
 Alarm limit deviation
 Alarm delay
To be able to cool with the primary and secondary heat pumps, the
heat pumps must be connected to the same heat source.
Passive cooling
For passive cooling, the brine is routed through the bore hole
where it is cooled.
Set passive cooling on the primary heat pump.
Set passive cooling on the required secondary heat pumps.
Active cooling
For active cooling, the brine is routed through the condenser and
actively cooled via the refrigerant circuit. The waste heat can be
used for the heating mode, DHW heating or swimming pool heat-
ing. When the waste heat is not needed, it is routed through the
bore hole or to the air cooler.
Set active cooling on the primary heat pump. The secondary
heat pumps are activated automatically.
Parameter Unit
Buffer cylinder temperature °C
Current temperature in the cooling buffer cylinder
Flow temperature, cooling °C
 Passive cooling
Can only be activated when a module is selected.
Activate or deactivate the function.
When the function is activated, the building is cooled passively.
The corresponding symbol appears in the main menu. The symbol
allows you quick access to this menu.
COMMISSIONING
Controller menu
www.stiebel-eltron.com WPM G | 17
 Active cooling
Can only be activated when a module is selected.
Activate or deactivate the function.
When the function is activated, the building is cooled actively. The
corresponding symbol appears in the main menu. The symbol
allows you quick access to this menu.
 Selected module
Set the module to which the necessary components are con-
nected.
 Surplus heat: Brine = 1, cooler = 2
Can only be adjusted if the “Active cooling” function is activated.
Set whether the excess heat should be discharged into the
borehole or via the air cooler.
 Summer mode cooling temperature
Set the outside temperature from which the rooms will be
cooled.
 Hot gas start temp. Cooling
Set the cooling buffer cylinder temperature, at which cooling
mode should start.
 Shutdown temp. Cooling
Set the cooling buffer cylinder temperature, at which cooling
mode should stop.
 Minimum compressor stage
Set the minimum stage at which the heat pump should run to
meet the cooling demand.
 Maximum compressor stage
Set the maximum stage at which the heat pump should run
to meet the cooling demand.
 Switching delay
A delay prevents the different output stages switching on or off
too quickly.
Set the time that must pass until the next output stage
switches on or off.
 Delay, directional valve, source
 Cooling – mixing valve
Parameter Unit
Cooling flow sensor °C
Current temperature captured by the flow sensor
Required cooling flow temperature °C
Feedback, opening level %
 Set cooling temperature
Set the flow temperature for cooling mode.
 Activate dew point sensor
Activate or deactivate the function.
When the function is activated, the dew point is monitored.
 Alarm limit deviation
Set a temperature at which an error message is displayed on
the appliance.
 Alarm delay
Set a time after which an error message is displayed on the
appliance.
 Cooling – cylinder
Parameter Unit
Buffer cylinder temperature °C
Current temperature in buffer cylinder
 Alarm high limit
Set a temperature at which an error message is displayed on
the appliance.
 Alarm delay
Set a time after which an error message is displayed on the
appliance.
 Cooling – surplus heat
Parameter Unit
Heat surplus flow °C
Heat surplus return °C
 Set return temperature
COMMISSIONING
Controller menu
18 | WPM G www.stiebel-eltron.com
 Alarm limit deviation
Set a temperature at which an error message is displayed on
the appliance.
 Alarm delay
Set a time after which an error message is displayed on the
appliance.
Cascade control
 Cascade control
 Slave = 0, Master = 1
 WPE-I H Premium heat pumps
 Number of secondary WPE-I H Premium
 Ext. controllable heat pumps
 Heat pump ID
 Port number
Parameter
Number of ext. controllable heat pumps
Number of heat pumps of a different series
Communication mode
Broadcast address
In this menu, specify which heat pumps are the primary heat pump
and the secondary heat pumps. The primary heat pump controls
the complete cascade. Some settings can be made on the second-
ary heat pumps. If there is communication between the primary
and secondary heat pumps, the heat pump ID is displayed on the
secondary heat pump screen.
If you make changes in this menu, all the heat pumps must
be restarted.
If the primary heat pump is not communicating with the
secondary heat pump, reinitialise the secondary heat pump.
Restart the secondary heat pump. Observe the chapter “Com-
missioning/ Commissioning cascades”.
Possible causes for faulty communication can be found in chapter
“Commissioning/ Commissioning cascades/ Messages”.
 Cascade control
Activate or deactivate the function.
When the function is activated, multiple heat pumps can be in-
stalled in the heating system.
 Slave = 0, Master = 1
Can only be adjusted if the “Cascade control” function is activated.
Input whether the heat pump is being set up as a primary or
secondary heat pump.
 WPE-I H Premium heat pumps
Note
Use this menu item if further heat pumps of the same
series are installed in your heating system.
Can only be activated if the “Cascade control” function is switched
on and the heat pump is set up as a primary heat pump.
Activate or deactivate the function.
When this function is activated, further heat pumps of the same
series can be set up.
 Number of secondary WPE-I H Premium
Can only be activated if the “WPE-IHPremium heat pumps” func-
tion is switched on.
Set the number of secondary heat pumps that can be con-
trolled by the primary heat pump.
 Ext. controllable heat pumps
Note
Use this menu item if heat pumps of a different series are
installed in your heating system.
Can only be activated if the “Cascade control” function is switched
on and the heat pump is set up as a primary heat pump.
Activate or deactivate the function.
When this function is activated, heat pumps of a different series
can be connected to the primary heat pump.
In the menu, change to the last page.
Tap on the button to add a heat pump of a different series.
Ext. heat pumps
Assign a heat pump ID ≥1 to the secondary heat pump. As-
sign IDs in chronological order for further secondary heat
pumps.
EM3
kW
Set the secondary heat pump output.
 Heat pump ID
Can only be entered if the “Cascade control” function is switched
on and the heat pump is set up as a secondary heat pump.
Assign a heat pump ID ≥1 to the secondary heat pump. As-
sign IDs in chronological order for further secondary heat
pumps.
 Port number
COMMISSIONING
Controller menu
www.stiebel-eltron.com WPM G | 19
Building management system (BMS)
 Activate BMS
 Modbus mode
 Address
 Baud rate
 Parity
 Port number
Parameter
Number of stop bits
The heat pump can be monitored and controlled via a Modbus.
The heat pump sends data to the Modbus on request.
 Activate BMS
Activate or deactivate the function.
When the function is activated, there is a higher ranking control
unit.
 Modbus mode
Set how communication with the higher ranking control unit
takes place.
RTU
Communication takes place directly via an external Modbus.
TCP
Communication takes place via a router at the RJ45 connector for
the heat pump.
 Address
Can only be adjusted if the “RTU” Modbus mode is selected.
Set the correct address.
 Baud rate
Can only be adjusted if the “RTU” Modbus mode is selected.
Set the speed, at which the data should be transferred.
 Parity
Can only be adjusted if the “RTU” Modbus mode is selected.
Set the required parity.
 Port number
Can only be adjusted if the “TCP” Modbus mode is selected.
Buffer cylinder
 Activate buffer cylinder mixer circuit control
 Heat pump connected to cylinder
 Buffer cylinder temperature, automatic mode
 Required buffer temperature
 Buffer cylinder overcharge
 Booster heater increase
 Booster heater max. application limit
 Buffer cylinder configuration
 Heat pump start offset
 Booster heater start offset
 Summer mode permissible
Parameter Unit
Buffer cylinder temperature °C
Current temperature in buffer cylinder
System flow °C
Current temperature in system flow
 Activate buffer cylinder mixer circuit control
Activate or deactivate the function.
When the function is activated, there is a buffer cylinder with
mixer circuit control in the heating system.
The mixer circuit controller must be set lower than heating cir-
cuit1, otherwise it will be purely mixer circuit control.
 Heat pump connected to cylinder
 Buffer cylinder temperature, automatic mode
Can only be activated if the “Activate buffer cylinder mixer circuit
control” function is switched on.
Activate or deactivate the function.
When this function is activated, the appliance automatically regu-
lates the set mixer circuit temperature under consideration of the
“Buffer cylinder overcharge”.
 Required buffer temperature
Can only be adjusted if the “Buffer cylinder temperature, auto-
matic mode” function is deactivated.
Set the required DHW temperature for the cylinder capacity.
 Buffer cylinder overcharge
Can only be adjusted if the “Buffer cylinder temperature, auto-
matic mode” function is activated.
Set the temperature deviation to which the buffer cylinder
should be heated.
The overcharge is an increase of the set mixer circuit temperature
and is therefore an offset value for the mixer circuit.
COMMISSIONING
Controller menu
20 | WPM G www.stiebel-eltron.com
 Booster heater increase
Can only be activated if the “Activate booster heater” function in
the “Booster heater” menu is switched on.
Activate or deactivate the function.
When this function is activated, the booster heater can be used.
 Booster heater max. application limit
Can only be adjusted if the “Booster heater increase” function is
activated.
Set the temperature up to which the booster heater will sup-
port the heat pump.
 Buffer cylinder configuration
Start at heating curve demand
Activate or deactivate the function.
When the function is activated, the contents of the buffer cylinder
are heated based on the heating curve.
Start at fixed temperature offset
Activate or deactivate the function.
When the function is activated, the contents of the buffer cylinder
are heated when the set temperature deviation is reached.
 Heat pump start offset
Can only be adjusted if the “Start at fixed temperature offset
function is activated.
Set the temperature deviation at which the heat pump should
cover the heat demand.
 Booster heater start offset
Can only be adjusted if the “Start at fixed temperature offset
function is activated.
Set the temperature deviation at which the booster heater
will support the heat pump with the heat demand.
 Summer mode permissible
Can only be adjusted if the “Start at fixed temperature offset
function is activated.
Activate or deactivate the function.
If this function is activated, the heat pump is switched off when the
outside temperature falls in line with the set outside temperature
(see chapter “Further menus/ Heating settings”).
Alarm control/central alarm
 Class
 External alarm input
 Class
Choose which error categories are displayed and which trig-
ger the differential relay.
 External alarm input
Activate or deactivate the function.
When this function is activated, an external error is registered.
Circulation pumps
 Activate system circulation pump
 Circulation pump (HP) speed control
 Condenser pump continuous operation
 Min. speed
 Max. speed
 Brine circulation pump (HP) speed control
 Brine pump continuous operation
 Min. speed
 Max. speed
 Standby circulation pump (HP)
 Standby brine pump (HP)
Parameter Unit
Feedback %
 Activate system circulation pump
Activate or deactivate the function.
 Circulation pump (HP) speed control
Activate or deactivate the function.
When the function is activated, the pump runs within the defined
speed range.
 Condenser pump continuous operation
Activate or deactivate the function.
When the function is activated, the pump runs permanently. If
the compressor is not operating, the pump rate is dictated by the
settings under “Standby circulation pump (HP)”.
 Min. speed
Can only be adjusted if the function “Circulation pump (HP) speed
control” is activated.
Set the minimum output at which the pump should run.
 Max. speed
Set the maximum output at which the pump should run.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28

STIEBEL ELTRON WPM G_COMMISSIONING Operation Instruction

Type
Operation Instruction

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI