STIEBEL ELTRON WPM G COMMISSIONING Operation Instruction

Type
Operation Instruction
COMMISSIONING
Programming unit
» WPM G
2 | WPM G www.stiebel-eltron.com
CONTENTS
COMMISSIONING
1. General information �����������������������������������������3
1.1 Relevant documents_____________________________________________ 3
1.2 Safety instructions _______________________________________________ 3
1.3 Other symbols in this documentation _______________________ 3
1.4 Units of measurement __________________________________________ 3
2. Safety ���������������������������������������������������������� 3
2.1 Instructions, standards and regulations ____________________ 3
2.2 General safety instructions ____________________________________ 3
2.3 Notes _______________________________________________________________ 3
2.4 Test symbols ______________________________________________________ 3
3. Appliance description ���������������������������������������4
3.1 Accessories ________________________________________________________ 4
4. Operation �����������������������������������������������������4
4.1 Symbols ____________________________________________________________ 4
5. Commissioning �����������������������������������������������4
5.1 Setting the language ____________________________________________ 4
5.2 Setting date and time ___________________________________________ 5
5.3 Network connection _____________________________________________ 5
5.4 Commissioning cascades _______________________________________ 6
5.5 Manual test _______________________________________________________ 8
6. Controller menu ����������������������������������������������8
Alarms _____________________________________________________________ 8
Settings ____________________________________________________________ 9
Language __________________________________________________________ 9
System settings __________________________________________________ 9
Installation ________________________________________________________ 9
Heating ___________________________________________________________ 10
Room temperature sensor ____________________________________ 11
DHW _______________________________________________________________ 11
Pool ________________________________________________________________ 12
Cooling ____________________________________________________________ 12
DHW draw-off control _________________________________________ 14
Water charging system ________________________________________ 14
Booster heater __________________________________________________ 15
Hot gas ____________________________________________________________ 15
Mixing valves ____________________________________________________ 16
Buffer cylinder __________________________________________________ 17
Alarm control/central alarm __________________________________ 18
Current limiter ___________________________________________________ 18
Flow switch ______________________________________________________ 19
Brine monitoring _______________________________________________ 19
SMART GRID _____________________________________________________ 19
Cascade control _________________________________________________ 20
Building management system (BMS) _______________________ 21
Modbus ___________________________________________________________ 21
Compressor settings ___________________________________________ 22
Circulation pumps ______________________________________________ 22
Temp. calibration _______________________________________________ 23
Manual test ______________________________________________________ 23
Process data _____________________________________________________ 25
Operating mode _________________________________________________ 27
7. Appendix ���������������������������������������������������� 28
7.1 Hydraulic connection diagram _______________________________ 28
COMMISSIONING
General information
www.stiebel-eltron.com WPM G | 3
1. General information
These instructions are intended for qualified contractors.
1.1 Relevant documents
Operating instructions for the programming unit
Heat pump operating and installation instructions
Operating and installation instructions for system
components
Note
Please see appliance operating instructions for informa-
tion on the "Guarantee" and "Environment and recycling".
1.2 Safety instructions
1.2.1 Structure of safety instructions
!
KEYWORD Type of risk
Here, possible consequences are listed that may result
from failure to observe the safety instructions.
Steps to prevent the risk are listed.
1.2.2 Symbols, type of risk
Symbol Type of risk
Injury
Electrocution
1.2.3 Keywords
KEYWORD Meaning
DANGER Failure to observe this information will result in serious
injury or death.
WARNING Failure to observe this information may result in serious
injury or death.
CAUTION Failure to observe this information may result in non-seri-
ous or minor injury.
1.3 Other symbols in this documentation
Note
General information is identified by the adjacent symbol.
Read these texts carefully.
Symbol Meaning
Material losses
(appliance damage, consequential losses and environmen-
tal pollution)
Appliance disposal
This symbol indicates that you have to do something. The ac-
tion you need to take is described step by step.
 These symbols show you the software menu level (in
this example level3).
1.4 Units of measurement
Note
All measurements are given in mm unless stated oth-
erwise.
2. Safety
Only a qualified contractor should carry out installation, commis-
sioning, maintenance and repair of the appliance.
2.1 Instructions, standards and regulations
Note
Observe all applicable national and regional regulations
and instructions.
2.2 General safety instructions
We guarantee trouble-free function and operational reliability only
if original accessories and spare parts intended for the appliance
are used.
2.3 Notes
- The appliance should only be operated once it is fully in-
stalled and all safety equipment has been fitted.
2.4 Test symbols
See type plate on the appliance.
!
!
COMMISSIONING
COMMISSIONING
Appliance description
4 | WPM G www.stiebel-eltron.com
3. Appliance description
The device is responsible for the processes that control and regu-
late the heat pump. The appliance allows remote monitoring and
heating system control via the internet.
If several heat demands are present at the same time, the appli-
ance switches back and forth between them. If a booster heater
is activated, DHW heating can run at the same time as the heating
mode and swimming pool heating.
3.1 Accessories
The following accessories can be installed for additional control
of the heat pump.
- Extension module
4. Operation
4.1 Symbols
Additional symbols are explained in the corresponding chapter.
Symbol Meaning
Call up main menu
Call up start screen
Authorisation code required
Confirm settings
Unconfirmed settings are reset to the previous
value.
Cancel settings
Scroll back one page
Scroll forward one page
Back
Reset to factory settings
The values on the current menu page are reset
to the factory settings.
Activate or deactivate functions
The symbol shows the activated function.
Activate or deactivate functions
The symbol shows the deactivated function.
Select one of two options
Symbol Meaning
Select one of two options
Receive further information
5. Commissioning
Note
If the heat pump needs to be restarted, the symbol is
shown on the device.
Note
Some setting options are only available in safe mode.
Once you have entered the access code, it does not need
to be re-entered for eight hours. The remaining time is
displayed top left of the screen.
Press the button on the start screen to open the main
menu.
Press the button to access safe mode.
Enter the following access code: 607080
Confirm the selection.
5.1 Setting the language
Press the button on the start screen to open the main
menu.
Press the button.
Press the "Language" menu.
Press the button to access the required language.
Select the required language.
Press the button to return to the higher ranking
menu.
Alter-
native
Press the button to return to the main menu.
ON
OFF
0
1
COMMISSIONING
Commissioning
www.stiebel-eltron.com WPM G | 5
5.2 Setting date and time
Note
The primary heat pump transfers the date and time set-
tings to the secondary heat pumps.
Press the button on the start screen to open the main
menu.
Press the button.
Press the "System settings" menu.
Press the "Date/time" menu.
Make the required changes.
Confirm the selection.
Press the button to return to the higher ranking
menu.
Alter-
native
Press the button to return to the main menu.
5.3 Network connection
Note
Please note that, for example, firewalls and faulty
connections may cause problems that prevent full
functionality.
If problems occur, contact your internet provider or
network administrator.
The device can be used to monitor the heating system via the
internet. For monitoring, you will need an internet connection,
a router and the Internet Service Gateway (ISG). Observe the ISG
operating and installation instructions. When using the ISG, use
the static IP address.
5.3.1 Connecting to the internet
Connect a patch cable to the RJ45 connector (see chapter
"Commissioning / Connecting to the internet" in the operat-
ing and installation instructions for the heat pump).
5.3.2 Network settings
Note
If multiple heat pumps are installed, the network
settings must be entered separately for each heat
pump.
Note
If settings are required on a router or other network
component, contact the network administrator.
The connection can be established via DHCP or a static IP address.
Ensure that you select the same connection for all heat pumps.
Press the button on the start screen to open the main
menu.
Press the button.
Select the "System settings" menu.
Select the "Network settings" menu.
Connection via DHCP
Note
Use dynamic assignment of the network address if
the heat pump is integrated in a network.
Select the required connection type.
Enter the required information in the corresponding
fields.
Press the button to return to the higher ranking
menu.
Alter-
native
Press the button to return to the main menu.
COMMISSIONING
Commissioning
6 | WPM G www.stiebel-eltron.com
Connection via a static IP address
Note
Use static assignment of the network address if the
heat pump is not integrated in a network.
Note
The router is only needed for setup via an external net-
work connection and for multiple secondary heat pumps.
Note
Do not change the setting in the network mask
(255.255.255.0).
Select the required connection type.
Enter the required information in the corresponding
fields.
Confirm the selection.
Press the button to return to the higher ranking
menu.
Alter-
native
Press the button to return to the main menu.
5.4 Commissioning cascades
Note
Only one heat pump can be defined as the primary heat
pump in the heating system.
Note
If you install a cascade without a switch or hub,
set the same network mask on the secondary heat
pumps as on the primary heat pump.
Restart the primary heat pump.
Restart the secondary heat pumps.
5.4.1 Setting up the primary and secondary heat pump
Note
When connecting heat pumps of a different series, ob-
serve the instructions regarding the "Settings"/ "Cascade
control" menu.
Press the button on the start screen to open the main
menu.
Press the button.
Select the "Installation" menu.
Activate cascade control.
Press the button to return to the higher ranking
menu.
Tap the button to access the "Cascade control" menu.
Select the "Cascade control" menu on the primary
heat pump.
Set the slide toggle to "Master=1".
Make the required settings.
Confirm the selection.
Select the "Cascade control" menu on the secondary
heat pump.
Set the slide toggle to "Slave=0".
Assign a heat pump ID ≥1 to the secondary heat
pump. Assign IDs in chronological order for further
secondary heat pumps.
Make the required settings.
Confirm the selection.
Follow the same sequence for additional secondary
heat pumps.
Press the button to return to the main menu.
Press the button.
Restart the primary heat pump.
Restart the secondary heat pumps.
If there is communication between the primary and secondary
heat pump, the heat pump ID is displayed on the secondary heat
pump screen.
Example: Without external network connection (for cascades
with only one secondary heat pump)
Note
Monitoring via the internet is not possible.
If you want to set up monitoring via the internet,
observe the example "With external network con-
nection (for cascades with one or more secondary
heat pumps)".
Use an Ethernet cable (Standard Cat 5 network cable, RJ45
connector).
Connect the heat pumps via the connection on the program-
ming unit. Observe chapter "Installation/ Removing the cas-
ing parts" in the operating and installation instructions for
the heat pump.
COMMISSIONING
Commissioning
www.stiebel-eltron.com WPM G | 7
D0000084758
1 2
1 Primary heat pump (e.g. IPaddress: 192.168.0.100)
2 Secondary heat pump (e.g. IPaddress: 192.168.0.101)
Example: With external network connection (for cascades with
one or more secondary heat pumps)
D0000084757
1
2
6 7 8 9 x
4
3
5
1 Router/ switch
2 Internet access via router
3 Online web browser
4 Online webserver and database
5 Internet Service Gateway (ISG)
6 Primary heat pump (e.g. IPaddress: 192.168.0.100)
7 Secondary heat pump (e.g. IPaddress: 192.168.0.101)
8 Secondary heat pump (e.g. IPaddress: 192.168.0.102)
9 Secondary heat pump (e.g. IPaddress: 192.168.0.103)
x Secondary heat pump (e.g. IPaddress: 192.168.0.xxx)
5.4.2 Messages
If one of the following messages appears, the primary heat pump
will no longer control the corresponding secondary heat pump for
the duration of the message.
Message Cause Remedy
Version error
The software version
of the secondary heat
pump is not identical
to the software ver-
sion of the primary
heat pump.
Have our customer
support install the
correct software ver-
sion.
Message Cause Remedy
Heat pump al-
ready registered
The secondary heat
pump is registered
under a different ID.
In the settings,
change the ID to the
first assigned ID or re-
start the primary heat
pump.
ID already regis-
tered
The ID has been as-
signed to another sec-
ondary heat pump.
Change the ID.
Multiple errors Several of the above
messages are active.
Correct the faults one
after the other.
The corresponding secondary heat pump must be reconnected
manually to the primary heat pump. The connection can be es-
tablished in two ways.
Press the button.
Alter-
native
Check the settings.
Make any necessary changes.
Press the button to return to the main menu.
Press the button.
Restart the primary heat pump.
Restart the secondary heat pumps.
5.4.3 Defining the operating mode
For each heat pump, you need to define which heat pump is ena-
bled for which heat demand. The heat pumps can be enabled for
heating mode, DHW heating, swimming pool heating and cooling.
Activate the required functions in the "Installation" menu.
The functions can be managed in the "Settings" menu.
Example: Enable heating mode
Press the button on the start screen to open the main
menu.
Press the button.
Select the "Installation" menu.
Activate heating mode.
Press the button to return to the higher ranking
menu.
Alter-
native
Press the button to return to the main menu.
ON
COMMISSIONING
Controller menu
8 | WPM G www.stiebel-eltron.com
5.5 Manual test
Note
Observe the chapter "Commissioning/ Manual test
of connected components" in the operating and in-
stallation instructions for the heat pump.
Note
A hand is displayed when the manual test is activated.
5.5.1 Activate manual test
Press the button on the start screen to open the main
menu.
Press the button.
Tap the button to access the "Manual test" menu.
Press the "Manual test" menu.
Activate the function.
Select the required test in the submenu.
5.5.2 End manual test
Press the button on the start screen to open the main
menu.
Press the button.
Tap the button to access the "Manual test" menu.
Press the "Manual test" menu.
Deactivate the function.
6. Controller menu
Note
Some setting options are only available in safe mode.
Once you have entered the access code, it does not need
to be re-entered for eight hours. The remaining time is
displayed top left of the screen.
Note
Certain menu items are protected by a code. The code set
at the factory is 607080.
Alarms
Settings
Language
System settings
Installation
Heating
Room temperature sensor
DHW
Pool
Cooling
DHW draw-off control
Water charging system
Booster heater
Hot gas
Mixing valves
Buffer cylinder
Alarm control/central alarm
Current limiter
Flow switch
Brine monitoring
SMART GRID
Cascade control
Building management system (BMS)
Modbus
Compressor settings
Circulation pumps
Temp. calibration
Manual test
Process data
Operating data
Operating time
Version information
Graphs
Energy measurement
Heat pump status
Change log
Operating mode
Alarms
In this view, you can see the last 100 active and acknowledged
fault messages. The list is updated every minute and every time
the appliance is started.
ON
OFF
COMMISSIONING
Controller menu
www.stiebel-eltron.com WPM G | 9
Controller menu: Settings
Settings
Language
Set the required system language.
System settings
 Network settings
 Date/time
 Display settings
 Activate screen cleaning function
 Brightness
 Enable locked operation
 Activate locked operation
 Logging
 Network settings
The internet connection can be established via DHCP or a static
IP address.
Make the required settings. Observe the description in the
chapter "Commissioning/ Network connection/ Network
settings").
 Date/time
Set the current date and current time.
 Display settings
 Activate screen cleaning function
The display is locked for 15seconds. During this time you can
clean the display without making any unintentional adjustments.
 Brightness
Set the required brightness of the display backlighting.
 Enable locked operation
Activate or deactivate the function.
 Activate locked operation
Can only be activated if "Enable locked operation" is activated.
 Logging
Note
Do not adjust the time during logging.
The controller allows you to export log files that can be read on a
computer. When logging is running, the data is recorded directly
onto the USB stick and not on the internal memory. Older data is
not displaced.
Insert a USB stick into the USB port.
Activate the "Logging" function. Logging starts.
If the menu cannot be activated, remove the USB stick. Re-
turn to the menu. Insert the USB stick into the USB port.
If the menu still cannot be activated, replace the USB stick.
If you want to terminate logging, deactivate the "Logging"
function.
A message appears when logging has finished.
Remove the USB stick.
Installation
 Heating
 Room temperature sensor
 DHW
 Pool
 Cooling
 DHW draw-off control
 Water charging system
 Cascade control
 Building management system (BMS)
 Heating circuit 1
 Heating circuit 2
 Heating circuit 3
 Heating circuit 4
 Heating circuit 5
 Booster heater
 Hot gas
 Current limiter
 Brine monitoring
 External brine pump
 Brine pump external start
 Buffer cylinder
 Flow switch
 Central fault
 External alarm
 SMART GRID
 Heating
Activate or deactivate the function.
When the function is activated, the corresponding symbol appears
in the main menu. The symbol allows you quick access to another
menu.
 Room temperature sensor
Activate or deactivate the function.
When the function is activated, the sensor measures the current
room temperature.
 DHW
Activate or deactivate the function.
 Pool
Choose the module via which the function is connected.
 Cooling
Choose the module via which the function is connected.
 DHW draw-off control
Activate or deactivate the function.
COMMISSIONING
Controller menu
10 | WPM G www.stiebel-eltron.com
Controller menu: Settings
 Water charging system
Activate or deactivate the function.
 Cascade control
Activate or deactivate the function.
When the function is activated, multiple heat pumps can be in-
stalled in the heating system.
 Building management system (BMS)
Activate or deactivate the function.
If the function is activated, communication with the ISG can take
place.
Adjust the parameter.
Parameter Setting
Modbus mode (Building management system (BMS)) TCP
 Heating circuit
Activate or deactivate the function.
When the function is activated, the settings made apply to the cor-
responding heating circuit. The corresponding symbol appears in
the main menu. The symbol allows you quick access to this menu.
When the function is deactivated, the higher ranking settings are
used to control the heating circuit.
 Booster heater
Choose the module via which the function is connected.
 Hot gas
Activate or deactivate the function.
When the function is activated, hot gas can be used for DHW
heating.
 Current limiter
Activate or deactivate the function.
 Brine monitoring
Activate or deactivate the function.
When the function is activated, the device controls the brine tem-
perature.
 External brine pump
Choose the module via which the function is connected.
 Brine pump external start
Activate or deactivate the function.
 Buffer cylinder
Activate or deactivate the function.
When the function is activated, there is a buffer cylinder in the
heating system.
If the buffer cylinder is to be charged with a certain tempera-
ture, install a buffer sensor.
 Flow switch
Note
If no flow switch is connected, but the function is activat-
ed, the heat pump will not start.
Note
Several flow switches can be used in cascades.
Activate or deactivate the function.
 Central fault
Activate or deactivate the function.
 External alarm
Activate or deactivate the function.
When this function is activated, an external fault is registered.
 SMART GRID
Activate or deactivate the function.
"SG Ready" is a trademark of the Bundesverband
Wärmepumpe e.V. (German Heat Pump Association)
and denotes a property of heat pumps whose control
technology enables them to be integrated into a smart
power grid (SG = Smart Grid).
Heating
 Heating mode
 Heating type
 Heating curve
 Min. flow
 Max. flow
 Summer mode
 Heating time
 Comfort factor
 Switching delay
 Calculated start/stop threshold
 Fixed value operation
 Set flow temp.
 System return temperature sensor
 Heating mode
Activate or deactivate the function.
When the function is activated, the corresponding symbol ap-
pears in the main menu. The symbol allows you quick access to
another menu. Observe the information regarding the menu in
chapter "Further menus/ Heating settings" in these instructions
and "Settings/ Adjusting the temperature (central heating)/ In the
"Heating" menu" in the operating instructions for the appliance.
COMMISSIONING
Controller menu
www.stiebel-eltron.com WPM G | 11
Controller menu: Settings
 Heating type
Choose whether the rooms are heated by radiators or under-
floor heating.
 Heating curve
Adjust the heating curve.
 Min. flow
Set the minimum flow temperature.
 Max. flow
Set the maximum flow temperature.
 Summer mode
Set the outside temperature above which the heat pump is
no longer available to heat the building.
When the temperature falls below this setting, the heat pump will
start to heat the building again.
 Heating time
Set how long the heat pump is responsible for heating when
there is a heating demand.
 Comfort factor
The heating curve setting is multiplied by the set factor. This re-
sults in the new value for the heating curve.
 Switching delay
A delay prevents the different output stages switching on or off
too quickly.
Set the time that must pass until the next output stage
switches on or off.
 Calculated start/stop threshold
If the flow or return temperature deviates from the set tempera-
tures by this threshold value, the heat pump is switched on or off.
Set the value for the temperature deviation from the set flow
and return temperature at which the heat pump is switched
on or off.
 Fixed value operation
Activate or deactivate the function.
When this function is activated, the heat pump heats to a fixed
temperature, independently of the heating curve.
 Set flow temp.
Set the temperature to which the flow is heated in Fixed
value operation.
 System return temperature sensor
Activate or deactivate the function.
Room temperature sensor
 Activate room sensor
 Passive = 0, active = 1
 Room temperature sensor influence
 Activate room sensor
Activate or deactivate the function.
When the function is activated, the sensor measures the current
room temperature.
 Passive = 0, active = 1
Set whether the temperature is measured actively or passive-
ly.
If the temperature is measured actively, the room sensor influ-
ences the heating mode.
 Room temperature sensor influence
Set whether the room sensor only measures the temperature
or also helps to control the room temperature. The higher the
value, the more influence the room sensor has.
DHW
 System DHW mode
 DHW mode
 Separate sensor (autonomous DHW)
 System DHW mode
Activate or deactivate the function.
 DHW mode
Activate or deactivate the function.
 Primary heat pump DHW mode
Can only be set when the "System DHW mode" function is acti-
vated.
Activate or deactivate the function.
When this function is activated, DHW heating is carried out by the
primary heat pump.
 DHW mode start temp.
Set the DHW temperature at which DHW heating starts.
 DHW mode stop temp.
Set the DHW temperature at which DHW heating stops.
 Sensor influence
Set how the influence is shared between the top and bottom
sensor.
If you set a mid-range value, the top and bottom sensors have the
same amount of influence.
COMMISSIONING
Controller menu
12 | WPM G www.stiebel-eltron.com
Controller menu: Settings
 DHW mode max. runtime
Set how long the heat pump is to be responsible for DHW
heating when there is a DHW demand.
After this time has elapsed, the device checks whether there is a
heat demand. If there is a heat demand, this demand is processed
by the heat pump.
 Pasteurisation mode
Activate or deactivate the function.
When the function is activated, the DHW in the DHW cylinder is
heated according to the settings.
 Max. heating phase
Set the number of days that should pass before the pasteuri-
sation program next starts-up.
 Pasteurisation mode max. runtime
Set the duration for which the pasteurisation program should
run.
 Pasteurisation mode stop temp.
Set the temperature which must be reached before the pas-
teurisation program is terminated.
Pool
 Pool
 Set pool temperature
 Pool hysteresis
 Required heating temperature
 Switching delay
 Pool runtime
 Pool heating with booster heater
 Activate booster heater for pool
Parameter Unit
Pool return temperature °C
Current return temperature from the pool
Pool flow temperature °C
Current flow temperature to the pool
 Pool
Can only be activated when a module is selected.
Activate or deactivate the function.
When the function is activated, the heat pump can be used for
pool water heating. The corresponding symbol appears in the
main menu. The symbol allows you quick access to this menu.
 Set pool temperature
Set the water temperature to which the pool should be heat-
ed.
 Pool hysteresis
Set the temperature deviation from the set temperature at
which heating of the swimming pool water starts.
Example
Pool hysteresis 1 K
Set pool temperature 20 °C
Start swimming pool heating 18.5 °C
End swimming pool heating 21.5 °C
 Required heating temperature
Set the flow temperature at which the pool should be heated.
 Switching delay
Set the time after which the heat pump starts to run when
there is a swimming pool demand.
 Pool runtime
Set how long the heat pump is responsible for swimming
pool heating when there is a swimming pool demand.
After this time has elapsed, the device checks whether there is a
heat demand. If there is a heat demand, this demand is processed
by the heat pump.
 Pool heating with booster heater
Activate or deactivate the function.
When the function is activated, the booster heater can be used to
support the heat pump for a swimming pool demand.
 Activate booster heater for pool
Can only be activated when the "Pool heating with booster heater"
function is enabled.
Activate or deactivate the function.
When the function is activated, the booster heater can support the
heat pump when there is a swimming pool demand.
Cooling
 Passive cooling
 Active cooling
 Surplus heat: Brine = 1, cooler = 2
 Summer mode cooling temperature
 Start temp. Cooling
 Shutdown temp. Cooling
 Switching delay
 Delay, directional control valve, source
 Cooling - mixing valve
 Set cooling temperature
 Activate dew point sensor
 Alarm limit deviation
 Alarm delay
 Cooling - cylinder
 Alarm high limit
 Alarm delay
 Cooling - surplus heat
COMMISSIONING
Controller menu
www.stiebel-eltron.com WPM G | 13
Controller menu: Settings
 Activate surplus heat dissipation
 Set return temperature
 Alarm limit deviation
 Alarm delay
To be able to cool with the primary and secondary heat pumps, the
heat pumps must be connected to the same heat source.
Passive cooling
For passive cooling, the brine is routed through the bore hole
where it is cooled.
Set passive cooling on the primary heat pump.
Set passive cooling on the required secondary heat pumps.
Active cooling
For active cooling, the brine is routed through the evaporator
and actively cooled via the refrigerant circuit. The waste heat can
be used for the heating mode, DHW heating or swimming pool
heating. When the waste heat is not needed, it is routed through
the bore hole or to the air cooler.
Set active cooling on the primary heat pump. The secondary
heat pumps are activated automatically.
Parameter Unit
Buffer cylinder temperature °C
Current temperature in the cooling buffer cylinder
Cooling flow temperature °C
 Passive cooling
Can only be activated if an extension module (EM) is selected.
Activate or deactivate the function.
When the function is activated, the building is cooled passively.
The corresponding symbol appears in the main menu. The symbol
allows you quick access to this menu.
 Active cooling
Can only be activated if an extension module (EM) is selected.
Activate or deactivate the function.
When the function is activated, the building is cooled actively. The
corresponding symbol appears in the main menu. The symbol
allows you quick access to this menu.
 Surplus heat: Brine = 1, cooler = 2
Can only be adjusted if the "Active cooling" function is activated.
Set whether the excess heat should be discharged into the
borehole or via the air cooler.
 Summer mode cooling temperature
Set the outside temperature from which the rooms will be
cooled.
 Start temp. Cooling
Set the cooling buffer cylinder temperature, at which cooling
mode should start.
 Shutdown temp. Cooling
Set the cooling buffer cylinder temperature, at which cooling
mode should stop.
 Switching delay
A delay prevents the different output stages switching on or off
too quickly.
Set the time that must pass until the next output stage
switches on or off.
 Reconnect delay, directional control valve, borehole
Set a time after which cooling can take place again.
 Cooling - mixing valve
Parameter Unit
Cooling flow sensor °C
Current temperature captured by the flow sensor
Required cooling flow temperature °C
Feedback, opening level %
 Set cooling temperature
Set the flow temperature for cooling mode.
 Activate dew point sensor
Activate or deactivate the function.
When the function is activated, the dew point is monitored.
 Alarm limit deviation
Set a temperature which will trigger the display of a fault
message on the device when reached.
 Alarm delay
Set a time after which a fault message is displayed on the
device.
 Cooling - cylinder
Parameter Unit
Buffer cylinder temperature °C
Current temperature in buffer cylinder
 Alarm high limit
Set a temperature which will trigger the display of a fault
message on the device when reached.
COMMISSIONING
Controller menu
14 | WPM G www.stiebel-eltron.com
Controller menu: Settings
 Alarm delay
Set a time after which a fault message is displayed on the
device.
 Cooling - surplus heat
Parameter Unit
Heat surplus, flow °C
Heat surplus, return °C
 Activate surplus heat dissipation
Activate or deactivate the function.
 Set return temperature
Select the set temperature at which heat dissipation should
start.
 Alarm limit deviation
Set a temperature which will trigger the display of a fault
message on the device when reached.
 Alarm delay
Set a time after which a fault message is displayed on the
device.
DHW draw-off control
 DHW draw-off control
 Set DHW draw-off temp.
 Alarm limit DHW
 Alarm delay DHW
 Alarm limit DHW return
 Alarm delay DHW return
 DHW draw-off control booster heater
 DHW booster heater start temp.
 Booster heater start delay
 DHW booster heater stop temp.
Parameter Unit
DHW draw-off temp. °C
Current temperature at the draw-off points
DHW draw-off control return temp. °C
Current DHW return temperature
Hot gas temp. DHW °C
Current DHW temperature in the DHW cylinder
 DHW draw-off control
Can only be activated when a module is selected.
Activate or deactivate the function.
When the function is activated, DHW is delivered at the required
temperature at the draw-off points.
 Set DHW draw-off temp.
Set the temperature to be supplied at the draw-off points.
 Alarm limit DHW
Set a temperature which will trigger the display of a fault
message on the device when reached. This function prevents
too high DHW temperatures at the draw-off points.
 Alarm delay DHW
Set a time after which a fault message is displayed on the
device. This function delays the appearance of a fault mes-
sage on the appliance when the DHW temperature at the
draw-off points reaches the limit value.
 Alarm limit DHW return
Set a temperature which will trigger the display of a fault
message on the device when reached.
 Alarm delay DHW return
Set a time after which a fault message is displayed on the
device.
 DHW draw-off control booster heater
Activate or deactivate the function.
When this function is activated, the DHW between DHW cylinder
and draw-off points is further heated-up with the booster heater.
 DHW booster heater start temp.
Set the DHW temperature at which the booster heater will
support the heat pump.
 Booster heater start delay
Set the time after which the booster heater will support the
heat pump.
 DHW booster heater stop temp.
Set the DHW temperature at which the booster heater will
stop supporting the heat pump.
Water charging system
 Activate water charging system
 Set temperature
 Water charging system - activate hot gas function
 Set hot gas temperature
 Alarm delay
 Alarm limit
Parameter Unit
Temperature °C
Current return temperature from heat exchanger to
heat pump
COMMISSIONING
Controller menu
www.stiebel-eltron.com WPM G | 15
Controller menu: Settings
 Activate water charging system
Can only be activated when a module is selected.
Activate or deactivate the function.
 Set temperature
Select the set temperature.
 Water charging system - activate hot gas function
Activate or deactivate the function.
 Set hot gas temperature
 Alarm delay
Set a time after which a fault message is displayed on the
device.
 Alarm limit
Set a temperature which will trigger the display of a fault
message on the device when reached.
Booster heater
 Activate booster heater
 Temporarily deactivate external booster heater
 Outside temperature-dependent
 Outside temperature limit
 Start delay
 Start limit calculated demand
 Stop limit calculated demand
 Heat-up time
 Cooldown time
 Deactivate cooldown delay
 System flow offset
 Accounting period
 P
 I
 Minimum opening level
 Maximum opening level
Parameter Unit
Feedback, opening level %
 Activate booster heater
Activate or deactivate the function.
When the function is activated, the booster heater switches on as
the last output stage when there is a heat demand.
 Temporarily deactivate external booster heater
Activate or deactivate the function.
 Outside temperature-dependent
Activate or deactivate the function.
When this function is activated, the booster heater is activated at
the set outside temperature.
 Outside temperature limit
Can only be adjusted if the "Outside temperature-dependent"
function is activated.
Set the outside temperature from which the booster heater
will support the heat pump.
 Start delay
A delay prevents the booster heater switching on too quickly when
there is a heat demand.
Set the time after which the booster heater will support the
heat pump.
 Start limit calculated demand
 Stop limit calculated demand
 Heat-up time
Set how long the booster heater will support the heat pump.
 Cooldown time
 Deactivate cooldown delay
 System flow offset
 Accounting period
 P
 I
 Minimum opening level
Set the mixing valve opening level.
 Maximum opening level
Set the mixing valve opening level.
Hot gas
 Hot gas mode
 Start temp. Hot gas
 Stop temp. lower limit Hot gas
 Stop temp. upper limit Hot gas
 Activate hot gas diverter valve
 Connection temperature for cylinder charging with hot gas
 Changeover temp. for cylinder charging with hot gas
 Hot gas mode
Activate or deactivate the function.
When the function is activated, hot gas can be used for DHW
heating.
COMMISSIONING
Controller menu
16 | WPM G www.stiebel-eltron.com
Controller menu: Settings
 Start temp. Hot gas
Set the temperature at which hot gas is used for DHW heat-
ing.
 Stop temp. lower limit Hot gas
Set the minimum temperature at which the hot gas pump
switches off.
 Stop temp. upper limit Hot gas
Set the maximum temperature at which the hot gas pump
switches off.
 Activate hot gas diverter valve
Activate or deactivate the function.
 Connection temperature for cylinder charging with hot
gas
 Changeover temp. for cylinder charging with hot gas
Can only be adjusted if the "Activate hot gas diverter valve" func-
tion is activated.
Mixing valves
 Heating circuit 1
 Activate heating circuit 1
 Type
 Heating type
 Heating curve
 Min. flow
 Max. flow
 Set cooling temperature
 Cooling subject to season
 Summer mode cooling temperature
 Internal brine pump increase
 Set/actual deviation
 Alarm delay
 Heating circuit 2 / 3 / 4 / 5
 Activate heating circuit x
 Heating type
 Heating curve
 Min. flow
 Max. flow
 Activate room sensor
 Passive = 0, active = 1
 Set temperature
 Room temperature sensor influence
 Subject to heating season
 Seasonal heating temperature
Parameter Unit
Room temperature °C
Temperature captured by room sensor
 Heating circuit 1
 Activate heating circuit 1
Activate or deactivate the function.
When the function is activated, the settings made here apply for
the corresponding heating circuit. The corresponding symbol ap-
pears in the main menu. The symbol allows you quick access to
this menu.
When the function is deactivated, the higher ranking settings are
used to control the heating circuit.
 Type
Choose whether the heating circuit is used for heating or
cooling.
 Heating type
Choose whether the rooms are heated by radiators or under-
floor heating.
 Heating curve
Adjust the heating curve.
 Min. flow
Set the minimum temperature for the system flow.
 Max. flow
Set the maximum temperature for the system flow.
 Set cooling temperature
Can only be activated if the heating circuit is used for cooling.
Set the flow temperature for cooling mode.
 Cooling subject to season
Can only be activated if the heating circuit is used for cooling.
Activate or deactivate the function.
 Summer mode cooling temperature
Can only be activated if the heating circuit is used for cooling.
Set the outside temperature from which the rooms will be
cooled.
 Internal brine pump increase
Can only be activated if the heating circuit is used for cooling.
Activate or deactivate the function.
 Set/actual deviation
Set the maximum temperature deviation; if it is reached, a
fault message is displayed on the device.
COMMISSIONING
Controller menu
www.stiebel-eltron.com WPM G | 17
Controller menu: Settings
 Alarm delay
Set a time after which a fault message is displayed on the
device.
 Heating circuit 2 / 3 / 4 / 5
Note
You need one extension module for mixer control of heat-
ing circuits 2 and 3, and one for heating circuits 4 and 5.
 Activate heating circuit x
Can only be activated when a module is selected.
Activate or deactivate the function.
When the function is activated, the settings made here apply for
the corresponding heating circuit. The corresponding symbol ap-
pears in the main menu. The symbol allows you quick access to
this menu.
When the function is deactivated, the higher ranking settings are
used to control the heating circuit.
 Heating type
Choose whether the rooms are heated by radiators or under-
floor heating.
 Heating curve
Adjust the heating curve.
 Min. flow
Set the minimum temperature for the system flow.
 Max. flow
Set the maximum temperature for the system flow.
 Activate room sensor
Activate or deactivate the function.
When the function is activated, the sensor measures the current
room temperature.
 Passive = 0, active = 1
Set whether the temperature is measured actively or passive-
ly.
If the temperature is measured actively, the room sensor influ-
ences the heating mode.
 Set temperature
Set the temperature to which the assigned rooms should be
heated.
 Room temperature sensor influence
Set whether the room sensor only measures the temperature
or also helps to control the room temperature. The higher the
value, the more influence the room sensor has.
 Subject to heating season
Activate or deactivate the function.
 Seasonal heating temperature
Set the outside temperature below which the rooms are
heated.
Buffer cylinder
 Buffer cylinder type
 Buffer cylinder temperature, automatic mode
 Buffer cylinder overcharge
 Required buffer temperature
 Booster heater increase
 Booster heater max. application limit
 Buffer cylinder configuration
 Heat pump start offset
 Booster heater start offset
 Summer mode permissible
Parameter Unit
Buffer cylinder temperature °C
Current temperature in buffer cylinder
System flow °C
Current temperature in system flow
 Buffer cylinder type
Set the hydraulic connection of the buffer cylinder.
The hydraulic connection diagrams can be found in the appendix.
Option
None
A buffer cylinder may be installed in the heating sys-
tem. The buffer cylinder is not overcharged. The sen-
sor for the system return is not installed.
1
The heat pump charges the buffer cylinder. The buffer
cylinder supplies the heating system via the mixing
valve. Overcharging the buffer cylinder is allowed. An
internal booster heater is allowed.
2
The heat pump charges the buffer cylinder. An unreg-
ulated external heat source (e.g. high capacity incin-
erator) charges the buffer cylinder. When the set tem-
perature according to the heating curve is reached,
the heat pump is switched off. The buffer cylinder
supplies the heating system via the mixing valve.
3
The heat pump charges the buffer cylinder. An ex-
ternally regulated second heat generator (e.g. high
capacity incinerator) charges the buffer cylinder via
a mixing valve managed by the internal control unit.
The buffer cylinder supplies the heating system via
the mixing valve. Overcharging the buffer cylinder is
allowed.
4
The heat pump charges the buffer cylinder. A regulat-
ed external second heat generator (e.g. high capacity
incinerator) provides heat directly to the heating
system via a mixing valve. The second heat generator
is controlled by the internal control unit of the heat
pump. The buffer cylinder is not charged by the sec-
ond heat generator. Overcharging the buffer cylinder
is allowed.
COMMISSIONING
Controller menu
18 | WPM G www.stiebel-eltron.com
Controller menu: Settings
 Buffer cylinder temperature, automatic mode
Can only be activated if the "Activate buffer cylinder mixer circuit
control" function is switched on.
Activate or deactivate the function.
When this function is activated, the appliance automatically regu-
lates the set mixer circuit temperature under consideration of the
"Buffer cylinder overcharge".
 Buffer cylinder overcharge
Can only be adjusted if the "Buffer cylinder temperature, auto-
matic mode" function is activated.
Set the temperature deviation to which the buffer cylinder
should be heated.
The overcharge is an increase of the set mixer circuit temperature
and is therefore an offset value for the mixer circuit.
 Required buffer temperature
Set the temperature to which the water in the buffer cylinder
is heated.
 Booster heater increase
Can only be activated if the "Activate booster heater" function in
the "Booster heater" menu is switched on.
Activate or deactivate the function.
When this function is activated, the booster heater can be used.
 Booster heater max. application limit
Can only be adjusted if the "Booster heater increase" function is
activated.
Set the temperature up to which the booster heater will sup-
port the heat pump.
 Buffer cylinder configuration
Start at heating curve demand
Activate or deactivate the function.
When the function is activated, the contents of the buffer cylinder
are heated based on the heating curve.
Start at fixed temperature offset
Activate or deactivate the function.
When the function is activated, the contents of the buffer cylinder
are heated when the set temperature deviation is reached.
 Heat pump start offset
Can only be adjusted if the "Start at fixed temperature offset"
function is activated.
Set the temperature deviation at which the heat pump should
cover the heat demand.
 Booster heater start offset
Can only be adjusted if the "Start at fixed temperature offset"
function is activated.
Set the temperature deviation at which the booster heater
will support the heat pump with the heat demand.
 Summer mode permissible
Can only be adjusted if the "Start at fixed temperature offset"
function is activated.
Activate or deactivate the function.
If this function is activated, the heat pump is switched off when the
outside temperature falls in line with the set outside temperature
(see chapter "Further menus/ Heating settings").
Alarm control/central alarm
 Class
 External alarm input
 Class
Choose which fault categories are displayed and which trig-
ger the differential relay.
 External alarm input
Activate or deactivate the function.
When this function is activated, an external fault is registered.
Current limiter
 Activate current limiter
 Limit booster heater
 Limiting secondary appliances
 Maximum power consumption (per phase)
 Booster heater hysteresis
 Compressor hysteresis
Parameter Unit
L1 current A
L2 current A
L3 current A
Maximum current at present A
 Activate current limiter
Can only be activated when a module is selected.
 Limit booster heater
Can only be activated if "Activate current limiter" is activated.
Activate or deactivate the function.
 Limiting secondary appliances
Can only be activated if "Activate current limiter" is activated.
Activate or deactivate the function.
COMMISSIONING
Controller menu
www.stiebel-eltron.com WPM G | 19
Controller menu: Settings
 Maximum power consumption (per phase)
Can only be adjusted if the "Activate current limiter" function is
activated.
 Booster heater hysteresis
 Compressor hysteresis
Can only be adjusted if the "Activate current limiter" function is
activated.
Flow switch
 Brine pressure switch
 Local flow switch
 Attempt restart if pressure drops/ Activate start attempts if pressure/
flow problems occur
 Only during compressor operation
 Brine pressure switch
Activate or deactivate the function.
When the function is activated, the brine pressure is controlled.
 Local flow switch
Activate or deactivate the function.
 Attempt restart if pressure drops/ Activate start
attempts if pressure/flow problems occur
Can only be activated if the "Brine pressure switch" function is
switched on.
Activate or deactivate the function.
 Only during compressor operation
Can only be activated if the "Brine pressure switch" function is
switched on.
Activate or deactivate the function.
When the function is activated, monitoring takes place while the
compressor is running.
Brine monitoring
 Brine outlet monitoring
 Brine alarm
 Evaporator frost protection active
 Min. brine outlet
 Alarm limit, brine temperature spread
 Brine inlet monitoring
 Min. brine inlet
 Switching delay, ramp up
 Switching delay, ramp down
 Brine outlet monitoring
Activate or deactivate the function.
When this function is activated, the device monitors the outlet
temperature of the brine coming from the heat pump. If the tem-
perature falls below the set value, the brine pump and the com-
pressor are switched off.
 Brine alarm
Activate or deactivate the function.
When this function is activated, a fault message is displayed on
the device if the set temperature is undershot.
 Evaporator frost protection active
Activate or deactivate the function.
 Min. brine outlet
Can only be adjusted if the "Brine outlet monitoring" function is
activated.
Set the minimum brine outlet temperature.
 Alarm limit, brine temperature spread
Set a temperature differential between the brine inlet and
brine outlet temperatures.
A fault message is displayed on the device if there is a deviation
from the set temperature differential. The heat pump is switched
off.
 Brine inlet monitoring
Activate or deactivate the function.
When this function is activated, the device monitors the inlet tem-
perature of the brine entering the heat pump. If the temperature
falls below the set value, the brine pump and the compressor are
switched off.
 Min. brine inlet
Set the minimum brine inlet temperature.
 Switching delay, ramp up
Can only be adjusted if the "Brine inlet monitoring" function is
activated.
Set the time after which the brine pump output is increased,
if the brine temperature is above the minimum temperature.
 Switching delay, ramp down
Can only be adjusted if the "Brine inlet monitoring" function is
activated.
Set the time after which brine pump output is reduced, so
the brine temperature does not fall too quickly.
SMART GRID
 Room temperature increase - accelerated mode
 Room temperature increase - maximum mode
 DHW start temperature - forced mode
 DHW stop temperature - forced mode
 DHW start temperature - maximum mode
COMMISSIONING
Controller menu
20 | WPM G www.stiebel-eltron.com
Controller menu: Settings
 DHW stop temperature - maximum mode
Parameter
Current operating mode
"SG Ready" is a trademark of the Bundesverband
Wärmepumpe e.V. (German Heat Pump Association)
and denotes a property of heat pumps whose control
technology enables them to be integrated into a smart
power grid (SG = Smart Grid).
Note
When the SG Ready function is being used, no other
power supply utility function (power-OFF) is available.
The two digital inputs allow four different operating modes.
Smart
grid 1
Smart
grid 2
Operating
mode
Description
0 0 Standard Standard operation
0
1
Comfort buff-
er cylinder
Increased start and stop tem-
perature for DHW heating.
The room temperature is
increased.
1
0
EVU
The function blocks compres-
sor operation and the internal
flanged immersion heater.
Other components continue
to be controlled.
1
1
Boost
Increased start and stop
temperature for DHW heat-
ing. The room temperature
is increased. When the DHW
temperature in the DHW
cylinder is 2°C below the
stop temperature for the
anti-legionella program, the
program will start.
Buffer cylin-
der
The required cylinder tem-
perature is set to 55°C. If the
"Allow booster heater during
maximum mode" function is
activated in the programming
unit, the internal flanged im-
mersion heater is used.
 Room temperature increase - accelerated mode
Set by how much more the room will be heated in °C.
 Room temperature increase - maximum mode
Set by how much more the room will be heated in °C.
 DHW start temperature - forced mode
Set the temperature at which DHW heating starts.
 DHW stop temperature - forced mode
Set the temperature at which DHW heating ends.
 DHW start temperature - maximum mode
Set the temperature at which DHW heating starts.
 DHW stop temperature - maximum mode
Set the temperature at which DHW heating ends.
Cascade control
 Cascade control
 Slave = 0, Master = 1
 WPE-IHPremium heat pumps
 Number of secondary WPE-I H Premium
 Ext. controllable heat pumps
 Heat pump ID
 Port number
Parameter
Number of ext. controllable heat pumps
Number of heat pumps of a different series
Communication mode
Broadcast address
In this menu, specify which heat pumps are the primary heat pump
and the secondary heat pumps. The primary heat pump controls
the complete cascade. Some settings can be made on the second-
ary heat pumps. If there is communication between the primary
and secondary heat pumps, the heat pump ID is displayed on the
secondary heat pump screen.
If you make changes in this menu, all the heat pumps must
be restarted.
If the primary heat pump is not communicating with the
secondary heat pump, reinitialise the secondary heat pump.
Restart the secondary heat pump. Observe the chapter "Com-
missioning/ Commissioning cascades".
Possible causes for faulty communication can be found in chapter
"Commissioning/ Commissioning cascades/ Messages".
 Cascade control
Activate or deactivate the function.
When the function is activated, multiple heat pumps can be in-
stalled in the heating system.
 Slave = 0, Master = 1
Can only be adjusted if the "Cascade control" function is activated.
Input whether the heat pump is being set up as a primary
(master) or secondary (slave) heat pump.
 WPE-IHPremium heat pumps
Note
Use this menu item if further heat pumps of the same
series are installed in your heating system.
Can only be activated if the "Cascade control" function is switched
on and the heat pump is set up as a primary heat pump.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36

STIEBEL ELTRON WPM G COMMISSIONING Operation Instruction

Type
Operation Instruction

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI