COMMISSIONING
Controller menu
www.stiebel-eltron.com WPM G | 17
Controller menu: Settings
Alarm delay
Set a time after which a fault message is displayed on the
device.
Heating circuit 2 / 3 / 4 / 5
Note
You need one extension module for mixer control of heat-
ing circuits 2 and 3, and one for heating circuits 4 and 5.
Activate heating circuit x
Can only be activated when a module is selected.
Activate or deactivate the function.
When the function is activated, the settings made here apply for
the corresponding heating circuit. The corresponding symbol ap-
pears in the main menu. The symbol allows you quick access to
this menu.
When the function is deactivated, the higher ranking settings are
used to control the heating circuit.
Heating type
Choose whether the rooms are heated by radiators or under-
floor heating.
Heating curve
Adjust the heating curve.
Min. flow
Set the minimum temperature for the system flow.
Max. flow
Set the maximum temperature for the system flow.
Activate room sensor
Activate or deactivate the function.
When the function is activated, the sensor measures the current
room temperature.
Passive = 0, active = 1
Set whether the temperature is measured actively or passive-
ly.
If the temperature is measured actively, the room sensor influ-
ences the heating mode.
Set temperature
Set the temperature to which the assigned rooms should be
heated.
Room temperature sensor influence
Set whether the room sensor only measures the temperature
or also helps to control the room temperature. The higher the
value, the more influence the room sensor has.
Subject to heating season
Activate or deactivate the function.
Seasonal heating temperature
Set the outside temperature below which the rooms are
heated.
Buffer cylinder
Buffer cylinder type
Buffer cylinder temperature, automatic mode
Buffer cylinder overcharge
Required buffer temperature
Booster heater increase
Booster heater max. application limit
Buffer cylinder configuration
Heat pump start offset
Booster heater start offset
Summer mode permissible
Parameter Unit
Buffer cylinder temperature °C
Current temperature in buffer cylinder
System flow °C
Current temperature in system flow
Buffer cylinder type
Set the hydraulic connection of the buffer cylinder.
The hydraulic connection diagrams can be found in the appendix.
Option
None
A buffer cylinder may be installed in the heating sys-
tem. The buffer cylinder is not overcharged. The sen-
sor for the system return is not installed.
1
The heat pump charges the buffer cylinder. The buffer
cylinder supplies the heating system via the mixing
valve. Overcharging the buffer cylinder is allowed. An
internal booster heater is allowed.
2
The heat pump charges the buffer cylinder. An unreg-
ulated external heat source (e.g. high capacity incin-
erator) charges the buffer cylinder. When the set tem-
perature according to the heating curve is reached,
the heat pump is switched off. The buffer cylinder
supplies the heating system via the mixing valve.
3
The heat pump charges the buffer cylinder. An ex-
ternally regulated second heat generator (e.g. high
capacity incinerator) charges the buffer cylinder via
a mixing valve managed by the internal control unit.
The buffer cylinder supplies the heating system via
the mixing valve. Overcharging the buffer cylinder is
allowed.
4
The heat pump charges the buffer cylinder. A regulat-
ed external second heat generator (e.g. high capacity
incinerator) provides heat directly to the heating
system via a mixing valve. The second heat generator
is controlled by the internal control unit of the heat
pump. The buffer cylinder is not charged by the sec-
ond heat generator. Overcharging the buffer cylinder
is allowed.