8 VI.76.P4.02 Danfoss 8/98 BC-HM
g) Min. boiler temperatureg) Min. boiler temperature
g) Min. boiler temperatureg) Min. boiler temperature
g) Min. boiler temperature
The boiler temperature can be set within
a range of 10 - 70 °C. The factory
setting is 10 °C, however, the min.
allowable boiler temperature is to be set
according to the boiler manufactorer
instructions.
h) Boiler temperature differenceh) Boiler temperature difference
h) Boiler temperature differenceh) Boiler temperature difference
h) Boiler temperature difference
Fixed difference
Set the fixed difference between the
start and stop temperatures within the
range 2 - 20 K.
Automatic difference (AUTO)
Set potentiometer in position AUTO and
start and stop temperature will be
automatically adapted to the boiler type
and system load. This function is
suitable for low thermal capacity boilers
(reduces the start/stop frequency). The
factory setting is 12 K, however the
setting is to follow the boiler
manufactorer instructions.
i) Setting reduced temperature leveli) Setting reduced temperature level
i) Setting reduced temperature leveli) Setting reduced temperature level
i) Setting reduced temperature level
The reduced temperature level can be
set at a fixed value (1 - 8) or at an
outdoor-temperature-dependent value
(AUTO). The basic setting for reduced
temperature is 5. Each graduation on
the scale corresponds to about 1 degree
in the room.
Reduced temperature
The scale shows room temperature drop
during reduced temperature period.
Different settings are given (–2, –4, –6,
–8 and AUTO).
If no room sensor is used, the control
calculates the parallel displacement to
give the set room temperature drop.
j) Setting the hot water servicej) Setting the hot water service
j) Setting the hot water servicej) Setting the hot water service
j) Setting the hot water service
temperaturetemperature
temperaturetemperature
temperature
The hot-water-service temperature can
be set with potentiometer j) within 30 - 70
°C.
The basic setting is 50 °C.
Time control of hot water service circuit
A 2-channel digital time switch or a
control panel ECA 9020 - channel 3 can
time control the hot-water-service circuit.
The hot-water-service temperature is
reduced to 10 °C at reduced operation.
Special settingsSpecial settings
Special settingsSpecial settings
Special settings
ECL 9200 and ECL 9250 has eight mini-
switches placed behind a small cover
when tipping out the inside cover. The
switches are used for adapting the
controller to the heating system.
Factory setting