Be sure this information reaches the operator.
You can get extra copies through your supplier.
INSTRUCTIONS for
F-15-297
March, 1996
Installing
POWER LINE FILTER/CONDITIONER
P/N 35910 - 600 vac, 3-phase, 16 amp/phase
P/N 35911 - 600 vac, 3-phase, 25 amp/phase
F-15-297
To install Filter/Conditioner, refer to installation instruc-
tions and Figures 1 and 2 on the back of this form.
Power Line Filter/Conditioner is recommended for use
with inverter type power sources where 460 or 575 volt
input power surges and spikes are common. It will also
reduce input current draw by at least 25% as well as
improve power factor and efficency.
The 10" X 8" X 7" Filter/Conditioner is wall mountable.
It should be located no more than 2 feet from the power
source. The Filter/Conditioner is equipped with a 12-
foot long, 4-conductor, #10AWG input power cable for
connecting to your 460 or 575 vac power.
P/N 35910 Filter/Conditioner can be used with any 460
or 575 vac, 3-phase power source having an input cur-
rent draw up to 16 amps/phase such as PCM-750i (460
575 vac) and PCM-1000i (575 vac). P/N 35911 is de-
signed for power sources with higher input current draw
up to 25 amps/phase such as PCM-1000i (460 vac),
SVI 300i, and SVI 450i.
INPUT
POWER
OUTPUT
TO
INVERTER
POWER LINE FILTER
600VAC, 3 PHASE 16 AMP/PHASE
P/N 35910
Before installing this accessory, make sure all in-
put power is disconnected and/or lock out proce-
dures are in place.