SVI-450i cvcc POWER SOURCE FOR 575-VOLT SERVICE
Part No. 31955
SUPPLEMENT to Form 15-071
F-15-072
July, 1995
I. General
This supplement covers the SVI-450i Power Source
specifically designed for 575 Volt — 60 Hertz service. It
is identical to the standard SVI-450i, P/N 31950 unit cov-
ered in Form 15-071 except for the following:
IMPORTANT
As shipped from the factory, all 575-volt units are
hooked-up to operate “only” from a 575-volt input.
This unit “does not” contain a Voltage Changeover
Input Terminal Board assembly.
A. Replacement Parts:
Main Transformer Assy. (MTR) - P/N 31685 replaces
P/N 31133.
Control Transformer Assy. (CTR) - 31686 replaces
P/N 31134.
Power P.C. Board Assy. (PB1 and PB2) - P/N 31423
replaces P/N 674991.
Capacitors (C5 and C6) - P/N 672348 replaces
P/N 950516.
II. Form 15-071 is applicable to this unit except
as follows:
A. See Revised Specification Table following.
B. See Revised Table for Recommended Input Con-
ductors and Line Fuses.
Note that the customer can either use the factory sup-
plied input power cable (No. 6 AWG, 4/c, type SO,
90° C, 12-ft. 19.), or provide his own leads per the
Input Table.
SPECIFICATIONS
Rated Output @ 60% Duty ................. 450 amps @ 38 vdc
Open Circuit Voltage ................................................. 72 vdc
Input Voltage ...................................... 575 vac, 3 ph, 60 Hz
Input Current Rated Load .................. 29 amps @ 575 vac
Dimensions:
14.25" (362 mm) w x 23.0" (584 mm) d x 15.5" (394 mm) h
Weight .......................................................... 115 Ibs (52 kg)
C. Changes To Troubleshooting Section Vl, as fol-
lows:
All resistance and (low) voltage check readings de-
scribed in 15-071 are applicable to this unit, except
those designated with the symbol H.V. . This symbol
indicates “high” voltage checks which are not appli-
cable and cannot be safely made in this unit because
it does not contain an input terminal board-reference
the Capacitor Warning in the booklet (15-071).
D. Revised Wiring Diagram Contained Herein.
E. Revised Schematic Diagram Contained Herein.
Be sure this information reaches the operator.
You can get extra copies through your supplier.
Rated Input Input & Gnd. Time-Delay
Conductor Fuse Size
Volts Amps CU/AWG Amps
575 29 8 50
* Sized per National Electrical Code for 90° C rated copper con-
ductors @ 30° C ambient. Not more than three conductors in
raceway or cable. Local codes should be followed if they specify
sizes other than those listed above.