GENERAL INFORMATION
Please read these instructions and keep them in a safe place.
These instructions must be followed carefully to ensure proper
operation.
The nVent RAYCHEM TraceTek TTSIM-1A has been designed for
use with TraceTek sensing cables, point sensors and normally
open, dry contact devices (float switch, pressure or vacuum
switch, optical probe with adapter, limit switch, etc.). Up to 150
m (500 ft) of sensor cable can be monitored by the TTSIM-1A.
Contact factory for information regarding longer monitoring
distance.
The TTSIM-1A is designed for installation in ordinary (non-
hazardous) areas. The TTSIM-1A has five small LED’s to indicate
power, status and communications activity, as well as a relay with
SPDT contacts. The TTSIM-1A can be used as a stand-alone leak
detection alarm, or connected to a host system (TraceTek TTDM-
128, computer, or control automation system) via simple, twisted
pair RS-485 serial communication wiring.
TOOLS REQUIRED
• Small flat blade screwdriver
• Small needle nose pliers
• Tools to mount DIN rail or enclosure
INSTALLATION ITEMS (NOT SUPPLIED)
• 35 mm DIN rail mounting strip (for wall mounts or interior of
large control cabinets) and attachment hardware.
• TT-RS485 power and telemetry jumper cable.
• Optional TTSIM-ENC-4X-OUTDOORS environmental enclosure
for outdoor or corrosive environments, or TTSIM-ENC-4X-
INDOORS enclosure with clear cover for indoor, non-corrosive
environments.
STORAGE
Keep the TTSIM-1A modules in a dry place prior to installation.
Avoid damage to components.
ADDITIONAL ITEMS
An agency-approved zener barrier must be used where sensing
cable connected to the TTSIM-1A will be located in Class1 Div 1
(Zone 0 or 1 in Europe) Hazardous Locations.
APPROVALS AND CERTIFICATIONS
General Signaling Equipment
76LJ
Only AC versions are UL listed and VDE Certified.
For DC models use a Listed Class 2 Power Supply.
TYPE NM
PRODUCT INFORMATION
TTSIM-1A
TTSIM-1A-120
TTSIM-1A-230
TTSIM-1A-12VDC
TTSIM-1A-24VDC
22 to 26 Vac, 50/60 Hz, 3 W (SELV level for Europe)
92 to 132 Vac, 50/60 Hz, 3 W
216 to 253 Vac, 50/60 Hz, 3 W
12 Vdc +/- 10% 2W
24 Vdc +/- 10% 2W
Relay contacts Form C (SPDT), 250 Vac/30 Vdc at 2 Amps maxi-
mum
(30 V SELV level for Europe)
Installation categories Overvoltage Category II
Pollution Degree 2
Storage temperature –18°C to 60°C (0°F to 140°F)
Operating temperature 0°C to 50°C (32°F to 122°F)
Enclosure NEMA 1; IP20 (NEMA 4X / IP 56 with optional
enclosure)
TTSIM-1A
TraceTek Sensor Interface Module with Relay Installation/Operation Instructions