nvent Raychem NGC-UIT-OUT Conversion Instructions

Type
Conversion Instructions

This manual is also suitable for

DESCRIPTION
These instructions will guide the installer on how to convert
from nVent RAYCHEM NGC-UIT-OUT to
nVent RAYCHEM NGC-UIT2-HAZ and are intended only for
personnel experienced in panel construction.
TOOLS REQUIRED
Masking tape #7 (.201) drill bit
11/32 in. Nut Driver 3/8 in. drill bit
Metal file
In-line torque wrench with 3/8 socket
Zipcut Disc for cutting Stainless Steel panels
(5.0 in x 0.45 in x 7/8 in)
Note: the Zipcut disc is used to cut the opening in the door for the
NGC-UIT2-HAZ display. Other cutting type tools can be used.
The NGC-UIT2-HAZ is an electronic unit.
During installation, take the following
precautions to avoid damage to its
electronic components.
Handle with care to avoid mechanical
damage.
Keep electronics dry.
Avoid exposure to static electricity.
Avoid contamination with metal filings,
liquids, or other foreign matter.
Take care to protect the user interface
board on the enclosure door.
Use agency-approved conduit bushings,
adapters, and cable glands to keep the
enclosure protected from dust and fluids.
WARNING:
General
Area of Use Nonhazardous or hazardous locations,
indoors or outdoors (Type 4X, IP66)
Supply Voltage 90–240 Vac
Operating Temperature 32°F to 140°F (0°C to 60°C) without
space heater
–22°F to 140°F (–30°C to 60°C) with
space heater
Min. Storage Temperature –40°F to 149°F (–40°C to 65°C)
Dimensions 13.43 in W X 10.87 in H X 3.63 in D
(341 mm W X 276 mm H X 92 mm D)
Alarm Outputs
Via External Alarm Module Three relay outputs, Form C contacts,
switching module up to 250 Vac/5 A
User to Drive External
Relays
Relays may be assigned for alarm
outputs
LCD Display
Display LCD is a 10.4 in SVGA, color TFT
transflective device with integral LED
backlight
Network Connection
Local/Remote Port RS-232/RS-485 (via external converter)
ports may be used to communicate
with host computer (RAYCHEM
Supervisor software) or DCS
Local RS-232 A non-isolated, 9 pin D sub male
Remote RS-232 to RS-485
using external converter #2
2 wire isolated,, Using a standard 9 pin
D sub female to 9 pin D sub male cable.
Data Rate 9600 to 57600 baud
Maximum cable length For RS-485 not to exceed 4000 ft
(1200 m). Cable to be shielded
twisted pair.
Field Port RS-232/RS-485 (via external converter)
port used to communicate with external
devices, such as NGC-30-CRM, CRMs
and RMM2.
Field RS-232 to RS-485
using external converter #1
2 wire isolated,, Using a standard 9 pin
D sub female to 9 pin D sub male cable.
Data Rate 9600
Maximum Cable Length For RS-485 not to exceed 4000 ft
(1200 m). Cable to be shielded
twisted pair.
LAN 10/100 Base-T Ethernet port with Link
and Activity Status LEDs
NGC-UIT-OUT to NGC-UIT2-HAZ
CONVERSION INSTRUCTIONS
Inside of
panel door
NGC-UIT
display
Cable ties
1
3
11/32 Nut Driver
2
Disconnect the cables from the NGC-UIT-OUT by
loosening the retaining screws that secure the Phoenix
connectors to the mating terminals on the NGC-UIT-OUT.
This includes the serial communications (RS-485), Relay
outputs and AC Input.
Disconnect the wires from the Phoenix connectors. Undo
all the cable ties for the wiring bundle to the NGC-UIT-OUT.
These wires will be used for the NGC-UIT2-HAZ once it is
installed.
Loosen and remove all 10 nuts and remove the
NGC-UIT-OUT from the panel door.
Qty Description Manufacturer Part Number
1 NGC-UIT2-HAZ TTC 10332-022
1 Din 35 Rail 15 inches any
2 Ilinx RS-232 to RS-485
converters
TTC 10332-023
1
ADAM 4069 relay
module
TTC 10332-024
Qty Description Manufacturer Part Number
2 Grounding terminal Phoenix 3044128
4 Terminal blocks Phoenix 3044102
2 Serial comm cables M-F L-Com CSMN9MF-2.5
1 UIT2-HAZ SS window kit TTC T1200033
2 Two position jumpers Phoenix 3030336
Removing the Existing NGC-UIT-OUT
Removing the Existing NGC-UIT-OUT
Removing the Existing NGC-UIT-OUT
WARNING: Power to the Electrical panel that is
housing the NGC-UIT-OUT must be turned OFF
before proceeding.
KIT CONTENTS
2 | nVent.com
Original Panel
Cutout Area
UIT2 Panel
Cutout Area
Drawing
Not to Scale
M1 M12 M11 M10
M4 M5 M6 M7
Upper left
hand corner
M2
M3
M9
M8
9.25 in.
11.75 in.
H1 H2
H3
4
Use the foldout template as a guide for enlarging the cutout.
Template is actual size (see attached at back of booklet)
Instructions
Line up the upper edge of the template with the existing
cutout. Use masking tape to secure the template to the
panel door. The dashed lines indicate the areas that must
be removed. To minimize the amount of cutting, it may be
desired to align the area to be removed with the upper left
corner of the existing cutout (as pictured)
Using a center punch, mark the 12 mounting holes.
M1 – M12
Remove the template after making the center punch marks.
Using a straight edge and marking pen draw a line starting
from the upper left hand corner of the existing cutout to the
center of H1 to H2 and H3.
Use a #7 (.201) drill bit, drill all 12 mounting holes. M1 – M12
Using the Zipcut disc or equivalent, start the cut from the
bottom left corner of the existing cutout and follow the
marked line to the center of H1. Continue the cut to H2
and H3. End the cut at the upper right hand corner of
the existing cutout.
Deburr all cut edges before installing the new NGC-UIT2-HAZ.
Do not install NGC-UIT2-HAZ until the holes for the
UIT2-HAZ Window Kit have been drilled.
HAZ cutout pattern
Inside of
panel door
Masking tape
Enlarging the NGC-UIT Opening
nVent.com | 3
5.06 in.
1.225 in.
Reference point
Cutout
1.225 in.
4.21 in.
8.41 in.
12.62 in.
15.18 in.
10.11 in.
1
2
3
4
5
6
7
8
9
10
11
12
Not to Scale
5
6
Refer to the drawing shown below for the hole pattern for
the UIT2-HAZ Window Kit.
Start by referencing the first hole of the window kit as
shown in the drawing below. (X=1.225 in. and Y=1.225 in.).
Use the Reference point shown in the drawing below as
your starting point.
Use masking tape to outline the mounting holes for the
window kit.
Measure each hole location from the first hole in the upper
left hand corner and continue around the perimeter until all
twelve holes are marked.
Using a center punch mark all 12 holes.
Drill all 12 holes using a #7 (.201) drill bit.
Remove the masking tape.
Insert the NGC-UIT2-HAZ into the panel door opening.
Verify that the gasket that came with the NGC-UIT2-HAZ
is properly installed. Secure the NGC-UIT2-HAZ using the
twelve 10-32 nuts and hardware.
After the display is properly positioned, tighten the nuts to
0.9 newton-meters (8 inch-pounds) of torque using a
3/8 inch wrench. Tighten Kep nuts in the sequence shown
for proper sealing.
Masking tape
NGC-UIT2-HAZ cutout
Installing the NGC-UIT2-HAZ
Drilling the Hole Pattern for the UIT2-HAZ Window Kit
4 | nVent.com
Neoprene
gasket
UIT2-HAZ Window Kit
Panel door
1/4-20 x 1/2 in. studs
A
RD
TD
Power
B
C
D
E
A
RD
TD
Power
B
C
D
E
RL4NO
RL4COM
RL3NO
RL3COM
RL2NC
RL2COM
RL2N0
RL1NC
RL1COM
RL1NO
RL0NC
RL0COM
RL0NO
RL5NO
RL5COM
RL6NO
RL6COM
RL7NO
RL7COM
RL7NC
NC
INT+
(Y ) DATA +
(G) DATA –
(R) +Vs
(B) GND 10
ADAM 4069
Relay Output
Module
8 Outputs
Two position jumpers
7
8
Insert the UIT2-HAZ Window Kit onto the panel door. Verify
that the gasket that came with the UIT2-HAZ Window Kit is
properly installed. Secure the UIT2-HAZ Window Kit using the
twelve 10-32 nuts and hardware.
After the UIT2-HAZ Window Kit is properly positioned, tighten
the nuts to 0.9 newton-meters (8 inch-pounds) of torque
using a 3/8 inch wrench. Tighten Kep nuts in the sequence
shown for the NGC-UIT2-HAZ.
If there is DIN rail space available,
mount the components shown on
the available space.
If there is no DIN rail space
available, use the DIN rail that
comes with the kit to mount the
components shown.
Installing the DIN Rail Components
Installing the UIT2-HAZ Window Kit
nVent.com | 5
1 2 3 4 8
RELAY 1 RELAY 2 RELAY 3
FAIL SAFE RELAY OUTPUTS AC INPUT
5 6 7 9 10 111 2 3 4 5 6
FIELD REMOTE
RS-485 PORTS
SIG–
SIG+
SHLD
SIG–
SIG+
SHLD
WH
BK
S
WH
BK
S
1 2 3
Line/L1
N/L2
Back of NGC-UIT-OUT
NGC-UIT2-HAZ mounted on panel door
A
RD
TD
Power
B
C
D
E
A
RD
TD
Power
Field
Port
Power
Supply
Connections
Connect to + 12 Vdc
power supply used to
power the CRM(S) boards
Remote
Port
120 – 240 Vac
B
C
D
E
RL4NO
RL4COM
RL3NO
RL3COM
RL2NC
RL2COM
RL2N0
RL1NC
RL1COM
RL1NO
RL0NC
RL0COM
RL0NO
RL5NO
RL5COM
RL6NO
RL6COM
RL7NO
RL7COM
RL7NC
NC
INT+
(Y) DATA +
(G) DATA –
(R) +Vs
(B) GND 10
+
+
ADAM 4069
Relay Output
Module
8 Outputs
9
Connect an AC power cord (120–240 V) to the NGC-UIT2-
HAZ AC input.
The Adam 4069 Relay module and the two RS-232 – RS-485
converters require +12 Vdc to operate. These devices can
be powered by the same power supply used to power the
CRM(s) boards.
Connect Power
6 | nVent.com
1 2 3 4 8
RELAY 1 RELAY 2 RELAY 3
FAIL SAFE RELAY OUTPUTS AC INPUT
5 6 7 9 10 111 2 3 4 5 6
FIELD REMOTE
RS-485 PORTS
SIG–
SIG+
SHLD
SIG–
SIG+
SHLD
WH
BK
S
WH
BK
S
1 2 3
Line/L1
N/L2
Back of NGC-UIT-OUT
NGC-UIT2-HAZ mounted on panel door
A
RD
TD
Power
B
C
D
E
A
RD
TD
Power
Field
Port
Refer to panel drawings
for location of Terminal
Block (TB) for landing relay
wires from ADAM Module
To Alarm Lamp/Switch
Mounted on Panel Door
N
TB-X
TB-X
TB-X
TB-X
TB-X
TB-X
Line
Fuse
A = Gnd
B = Data +
C = Data –
Remote
Port
B
C
D
E
RL4NO
RL4COM
RL3NO
RL3COM
RL2NC
RL2COM
RL2N0
RL1NC
RL1COM
RL1NO
RL0NC
RL0COM
RL0NO
RL5NO
RL5COM
RL6NO
RL6COM
RL7NO
RL7COM
RL7NC
NC
INT+
(Y) DATA +
(G) DATA –
(R) +Vs
(B) GND 10
AR
ADAM 4069
Relay Output
Module
8 Outputs
10
The illustration below shows the wiring for the alarm
relays from NGC-UIT-HAZ (dashed lines) to NGC-UIT2-
HAZ. TB-X’s are the field terminals. Refer to the panel
wiring for location of the field terminals.
Connecting the Alarm Relays
nVent.com | 7
1 2 3 4 8
RELAY 1 RELAY 2 RELAY 3
FAIL SAFE RELAY OUTPUTS AC INPUT
5 6 7 9 10 111 2 3 4 5 6
FIELD REMOTE
RS-485 PORTS
SIG–
SIG+
SHLD
SIG–
SIG+
SHLD
WH
BK
S
WH
BK
S
1 2 3
Line/L1
N/L2
Back of NGC-UIT-OUT
NGC-UIT2-HAZ mounted on panel door
A
RD
TD
Power
B
C
D
E
A
RD
TD
Power
Field
Port
3 2 1
Wh Bk G Wh Bk G
3 2 1
Remote
CRM(S)
To other
CRM(S)
RMM2
PLI
A = Gnd
B = Data +
C = Data –
Remote
Port
B
C
D
E
RL4NO
RL4COM
RL3NO
RL3COM
RL2NC
RL2COM
RL2N0
RL1NC
RL1COM
RL1NO
RL0NC
RL0COM
RL0NO
RL5NO
RL5COM
RL6NO
RL6COM
RL7NO
RL7COM
RL7NC
NC
INT+
(Y ) DATA +
(G) DATA –
(R) +Vs
(B) GND 10
3 2 1
ADAM 4069
Relay Output
Module
8 Outputs
11
The illustration below shows the wiring for RS-485 ports
from NGC-UIT-HAZ (dashed lines) to NGC-UIT2-HAZ. Refer to
the panel wiring for location of the field terminals.
Connect the RS-232 serial cables to the appropriate comm
port on the NGC-UIT2-HAZ as shown in the illustration.
Communications
8 | nVent.com
232.92 mm
(9.17 in)
Ø 5.08 mm
(0.2 in) X12
107.7 mm
(4.24 in)
215.65 mm
(8.49)
310.64 mm
(12.73 in)
243.54 mm
(11.73 in)
77.98 mm
(3.07 in)
12.7 mm
(0.5 in)
12.7 mm
(0.5 in)
179.58 mm
(7.07)
mm
(10.17 in)
Panel Cut Out Area
Top of Display
Drawing
Not to Scale
NGC-UIT2-HAZ Cut Out Dimensions
nVent.com | 9
nVent.com
©2018 nVent. All nVent marks and logos are owned or licensed by nVent Services GmbH or its aliates. All other trademarks are the property of their respective owners.
nVent reserves the right to change specications without notice.
Raychem-IM-H58812-NGCUIT1OUTtoUIT2HAZ-EN-1805
North America
Tel +1.800.545.6258
Fax +1.800.527.5703
Europe, Middle East, Africa
Tel +32.16.213.511
Fax +32.16.213.604
Asia Pacific
Tel +86.21.2412.1688
Fax +86.21.5426.3167
Latin America
Tel +1.713.868.4800
Fax +1.713.868.2333
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10

nvent Raychem NGC-UIT-OUT Conversion Instructions