JS1_CANplus_18Pin Reusable Panel External Inputs screen description (continued)
Name Unit Description
PDO1 - Timed Out --
Indicates if the function block receives a CAN Rx_PDO1 (Process Data Object 1)
within a defined timeout limit.
This message reports the status of buttons and digital inputs.
When this signal is T, the function block sets all Out signals associated with the
Rx_PDO1 message to either 0 or F. It sets all Fault signals associated with the
Rx_PDO1 message to T.
When this signal becomes F again, the function block enables all Out signals
associated with the Rx_PDO1 message. It resets all Fault signals associated with the
Rx_PDO1 message to F.
T = Message not received within a PDO1_Timeout limit
F = Message received within a PDO1_Timeout limit
PDO1 - NoMsgRcvd --
No PDO1 message received from the device.
Flt = No message received since power on.
OK = At least one message has been received.
PDO4 - Timed Out --
Indicates if the function block receives a CAN Rx_PDO4 (Process Data Object 4)
within a 2500 ms timeout limit.
This message reports the sensor power of the joystick.
When this signal is T, the function block sets all Out signals associated with the
Rx_PDO4 message to either 0 or F. It sets all Fault signals associated with the
Rx_PDO4 message to T.
When this signal becomes F again, the function block enables all Out signals
associated with the Rx_PDO4 message. It resets all Fault signals associated with the
Rx_PDO4 message to F.
T = Message not received within PDO4_Timeout limit
F = Message received within PDO4_Timeout limit
PDO4 - NoMsgRcvd --
No PDO4 message received from the device.
Flt = No message received since power on.
OK = At least one message has been received.
JS1_CANplus_18Pin Reusable Panel Joystick Signals screen description
Item Unit Description
Buttons - Btn (1 to 12) --
Indicates the states of grip-mounted push-button switches.
On = Closed
Off = Open
If the NA is active, then the signal is not available. The associated signal is set to
false.
If the Flt is active, then a fault condition currently exists for the signal. The
associated signal is set to false.
Node Address --
Specifies the factory-set node address of the joystick.
The Type code on the joystick label identifies the node address.
Positions – X Axis %
Indicates the position of the joystick’s X-axis.
If the NA is active, then the signal is not available. The associated signal is set to
false.
If the Flt is active, then a fault condition currently exists for the signal. The
associated signal is set to false.
Positions – Y Axis %
Indicates the position of the joystick’s Y-axis.
If the NA is active, then the signal is not available. The associated signal is set to
false.
If the Flt is active, then a fault condition currently exists for the signal. The
associated signal is set to false.
Positions – T Axis %
Indicates the position of the joystick’s T-axis.
If the NA is active, then the signal is not available. The associated signal is set to
false.
If the Flt is active, then a fault condition currently exists for the signal. The
associated signal is set to false.
User Manual
PLUS+1® Compliant JS1 CANopen CANplus Joystick Function Block
JS1 CANplus Service Screens
14 |
©
Danfoss | February 2020 AQ309185946321en-000101