JS1 - H

Danfoss JS1 - H User guide

  • Hello! I am an AI chatbot trained to assist you with the Danfoss JS1 - H User guide. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
  • What is the Factory-set source address of the joystick?
    How to properly connect the CAN bus to the joystick?
    What is the Status block used for in this device?
    What is indicated by T_Det_NA in the Status block?
    What does the Fault block in this device do?
    What does the occurrence of 'TimeOut_BJM = True' indicate?
    What is the purpose of XGrp_Det_Flt in the Fault block?
    What information does the Out block provide?
    What does the Status U16 output in the Out block represent?
User Manual
PLUS+1® Compliant
JS1 J1939 CAN Joystick Function Block
powersolutions.danfoss.com
Revision history Table of revisions
Date Changed Rev
March 2018 Re-branding 0102
September 2015 0101
User Manual
PLUS+1® Compliant JS1 J1939 CAN Joystick Function Block
2 |
©
Danfoss | March 2018 AQ00000202en-US0102
JS1_J1939 Function Block
Function Block Inputs..................................................................................................................................................................... 4
Function Block Outputs..................................................................................................................................................................4
Status and Fault Logic.....................................................................................................................................................................8
Status Logic...................................................................................................................................................................................8
Boolean Output Signals............................................................................................................................................................8
Proportional Output Signals................................................................................................................................................... 8
Function Block Connections.........................................................................................................................................................9
Configuration of Input and Output Buses...............................................................................................................................9
User Manual
PLUS+1® Compliant JS1 J1939 CAN Joystick Function Block
Contents
©
Danfoss | March 2018 AQ00000202en-US0102 | 3
The JS1_J1939 function block configures the output of a JS1 Joystick with CAN.
This joystick has a CAN (Controller Area Network) 2.0B output that uses the J1939 communication
protocol.
The JS1 Joystick with CAN is a highly configurable joystick that has:
A joystick base with a single three-point Y-axis or with three-point X- and Y-axes.
Up to three grip-mounted proportional three-point rocker switches.
Up to 12 grip-mounted push-button switches.
Function Block Inputs
Inputs to the function block are described.
JS1_J1939 Function Block Inputs
Input Type Range Description
SA U8 0-253 Specifies the factory-set source address of the joystick.
All source addresses on the same CAN bus must be different. Do not use the same address twice.
The Type code on the joystick label identifies the source address. Typical addresses are C33 (right), C34 (left),
C35 (center), and C36 (auxiliary).
Enter the source address in hexadecimal format as shown in the following examples:
C33 (right) = 0x33
C34 (left) = 0x34
C35 (center) = 0x35
C36 (auxiliary) = 0x36
CAN —— —— Inputs CAN messages from the joystick. Route this bus to the CAN pin on this function block.
CAN messages sent from the joystick to the function block contain information about the availability of joystick
inputs, joystick input faults, and joystick commands.
Function Block Outputs
The outputs of the function block are described.
JS1_J1939 Function Block Outputs
Output Type Range Description
Status —— —— Outputs a bus that contains the following status signals.
Btn1_NA–Btn12_NA BOOL —— Indicates if an input is available from a grip-mounted push-button switch.
T = Not available.
F = Available.
User Manual
PLUS+1® Compliant JS1 J1939 CAN Joystick Function Block
JS1_J1939 Function Block
4 |
©
Danfoss | March 2018 AQ00000202en-US0102
JS1_J1939 Function Block Outputs (continued)
Output Type Range Description
T_Det_NA BOOL —— Indicates if an input from a detent switch on the joystick’s rotational (theta) axis is
available.
T = Not available.
F = Available.
T_NA BOOL —— Indicates if an input from a rotational (theta) axis is available.
T = Not available.
F = Available.
XGrp_Det_NA BOOL —— Indicates if an input from a grip-mounted, X-axis detent switch is available.
T = Not available.
F = Available.
XGrp_NA BOOL —— Indicates if an input from a grip-mounted, X-axis proportional switch is available.
T = Not available.
F = Available.
X_Det_NA BOOL —— Indicates if an input from an X-axis detent switch is available.
T = Not available.
F = Available.
X_NA BOOL —— Indicates if an input from the joystick’s X-axis is available.
T = Not available.
F = Available.
YGrp_Det_NA BOOL —— Indicates if an input from a grip-mounted, Y-axis detent switch is available.
T = Not available.
F = Available.
YGrp_NA BOOL —— Indicates if an input from a grip-mounted, Y-axis proportional switch is available.
T = Not available.
F = Available.
Y_Det_NA BOOL —— Indicates if an input from a Y-axis detent switch is available.
T = Not available.
F = Available.
Y_NA BOOL —— Indicates if an input from the joystick’s Y-axis is available.
T = Not available.
F = Available.
Fault —— —— Outputs a bus that contains the following fault signals.
Btn1_Flt–Btn12_Flt BOOL —— Indicates if the input from a grip-mounted push-button switch has a fault.
T = Fault.
F = No fault.
T_Det_Flt BOOL —— Indicates if the input from a detent switch on the joystick’s rotational (theta) axis has a
fault.
T = Fault.
F = No fault.
T_Flt BOOL —— Indicates if the input from the joystick’s rotational (theta) axis has a fault.
T = Fault.
F = No fault.
User Manual
PLUS+1® Compliant JS1 J1939 CAN Joystick Function Block
JS1_J1939 Function Block
©
Danfoss | March 2018 AQ00000202en-US0102 | 5
JS1_J1939 Function Block Outputs (continued)
Output Type Range Description
TimeOut_BJM BOOL —— Indicates if the function block receives a BJM (Basic Joystick Message) within a 100 ms
timeout limit.
This message reports joystick X-axis and Y-axis positions as well as the state of grip-
mounted button switches.
When a message has not been seen for 100 ms, this signal becomes True. The function
block then sets all Out signals associated with the message to either 0 or F. It sets all fault
signals associated with the message to True.
Once a message is seen again, this signal becomes False and the function block enables
all Out signals associated with the message. It resets all fault signals associated with the
message to False.
T = Timeout fault. Message not received within 100 ms limit.
F = Message received within 100 ms limit.
TimeOut_EJM BOOL —— Indicates if the function block receives an EJM (Extended Joystick Message) within a 100
ms timeout limit.
This message reports the position of grip-mounted proportional switches.
When a message has not been seen for 100 ms, this signal becomes True. The function
block then sets all Out signals associated with the message to either 0 or F. It sets all fault
signals associated with the message to True.
Once a message is seen again, this signal becomes False and the function block enables
all Out signals associated with the message. It resets all fault signals associated with the
message to False.
T = Timeout fault. Message not received within 100 ms limit.
F = Message received within 100 ms limit.
NoMsgReceived_BJM BOOL —— No BJM received from the device.
T = No message received since power on.
F = At least one message has been received.
NoMsgReceived_EJM BOOL —— No EJM received from the device.
T = No message received since power on.
F = At least one message has been received.
XGrp_Det_Flt BOOL —— Indicates if the input from a grip-mounted, X-axis detent switch has a fault.
T = Fault.
F = No fault.
XGrp_Flt BOOL —— Indicates if the input from a grip-mounted, X-axis proportional switch has a fault.
T = Fault.
F = No fault.
X_Det_Flt BOOL —— Indicates if the input from a detent switch on the joystick’s X-axis has a fault.
T = Fault.
F = No fault.
X_Flt BOOL —— Indicates if the input from the joystick’s X-axis has a fault.
T = Fault.
F = No fault.
YGrp_Det_Flt BOOL —— Indicates if the input from a detent switch on the joystick’s Y-axis has a fault.
T = Fault.
F = No fault.
YGrp_Flt BOOL —— Indicates if the input from a grip-mounted, Y-axis proportional switch has a fault.
T = Fault.
F = No fault.
Y_Det_Flt BOOL —— Indicates if the input from a detent switch on the joystick’s Y-axis has a fault.
T = Fault.
F = No fault.
Y_Flt BOOL —— Indicates if the input from the joystick’s Y-axis has a fault.
T = Fault.
F = No fault.
User Manual
PLUS+1® Compliant JS1 J1939 CAN Joystick Function Block
JS1_J1939 Function Block
6 |
©
Danfoss | March 2018 AQ00000202en-US0102
JS1_J1939 Function Block Outputs (continued)
Output Type Range Description
Out —— —— Outputs a bus that contains the following command signals. These signals indicate the
position of each joystick axis and the state of push-button and detent switches.
Btn1–Btn12 BOOL —— Indicates the states of grip-mounted push-button switches.
T = Closed.
F = Open.
Rx_BJM BOOL —— Indicates when the function block receives a BJM (Basic Joystick Message).
This message reports joystick X-axis and Y-axis positions as well as the state of grip-
mounted button switches.
T = Message received.
F = Message not received.
Rx_EJM BOOL —— Indicates when the function block receives an EJM (Extended Joystick Message).
This message reports the position of grip-mounted proportional switches.
T = Message received.
F = Message not received.
Status U16 —— Reports the status of the function block.
See Status Logic for more about this output.
T_Axis_Det BOOL —— Indicates the state of a detent switch on the joystick’s rotational (theta) axis.
T = Closed.
F = Open.
T_Axis_Psn S16 -10000 to +10000 Indicates the position of the joystick’s rotational (theta) axis.
-10000 = -100%
+10000 = +100%
XGrp_Det BOOL —— Indicates the state of a detent switch on a grip-mounted, X-axis proportional switch.
T = Closed.
F = Open.
XGrp_Psn S16 -10000 to +10000 Indicates the position of a grip-mounted, X-axis proportional switch.
-10000 = -100%
+10000 = +100%
X_Axis_Det BOOL —— Indicates the state of a detent switch on the joystick’s X-axis.
T = Closed.
F = Open.
X_Axis_Psn S16 -10000 to +10000 Indicates the position of the joystick’s X-axis.
-10000 = -100%
+10000 = +100%
YGrp_Det BOOL —— Indicates the state of a detent switch on a grip-mounted, Y-axis proportional switch.
T = Closed.
F = Open.
YGrp_Psn S16 -10000 to +10000 Indicates the position of a grip-mounted, Y-axis proportional switch.
-10000 = -100%
+10000 = +100%
Y_Axis_Det BOOL —— Indicates the state of a detent switch on the joystick’s Y-axis.
T = Closed.
F = Open.
Y_Axis_Psn S16 -10000 to +10000 Indicates the position of the joystick’s Y-axis.
-10000 = -100%
+10000 = +100%
User Manual
PLUS+1® Compliant JS1 J1939 CAN Joystick Function Block
JS1_J1939 Function Block
©
Danfoss | March 2018 AQ00000202en-US0102 | 7
Status and Fault Logic
Use status and fault codes to determine if the function block is operating properly.
Status Logic
This topic describes codes that can help you determine if the function block is operating properly.
Status Hex
*
Binary
Cause
Response Correction
Parameters are corrupt.
0x8008
1000 Msg value > 3 or < 1. Incorrect or no message may be
received. Data presented to the
application may be incorrect.
Verify correct Msg value for
connected hardware and set
value within its 1–3 range.
SA value > 253 or < 0. Incorrect or no message may be
received. Data presented to the
application may be incorrect.
Verify correct SA for connected
hardware and set value within its
0–253 range.
*
Bit 16 set to 1 identifies a standard Danfoss status or fault code.
Boolean Output Signals
The changing states of the Status and Fault signals affect the value of Boolean output signals.
Output Signal Status Signal State Fault Signal State Output Signal Value
Btn1–Btn12, Rx_BJM, Rx_EJM, T_Axis_Det, XGrp_Det, X_Axis_Det,
YGrp_Det, Y_Axis_Det
F F T or F
T T F
T F F
F T F
For example:
As long as the Status signal and the Fault signal for the Btn1 input are both F, the Btn1 output signal
can be either T or F.
As soon as either the Status signal or the Fault signal for the Btn1 input becomes T, the Btn1 output
signal goes to and stays F.
When the Status signal and the Fault signal for the Btn1 input are again both F, the Btn1 output
signal returns to its normal T or F operation.
Proportional Output Signals
The states of the Status and Fault signals can change and affect the value of proportional output signals.
Output Signal Status Signal State Fault Signal State Output Signal Value
T_Axis_Psn, XGrp_Psn, X_Axis_Psn, YGrp_Psn, Y_Axis_Psn F F ±10000
T T 0
T F 0
F T 0
For example:
As long as the Status signal and the Fault signal for the T_Axis_Psn input are both F, the
T_Axis_Psn output signal ranges ±10000.
As soon as either the Status signal or the Fault signal for the T_Axis_Psn input becomes T, the
T_Axis_Psn output signal goes to and stays at 0.
When the Status signal and the Fault signal for the T_Axis_Psn input are again both F, the
T_Axis_Psn output signal returns to its normal ±10000 operation.
User Manual
PLUS+1® Compliant JS1 J1939 CAN Joystick Function Block
JS1_J1939 Function Block
8 |
©
Danfoss | March 2018 AQ00000202en-US0102
Function Block Connections
Connections you can make with the function block are described.
Item Description
1
Determines the CAN port connected to the joystick.
2
Configures the function block to listen for CAN data from the joystick’s network address.
3
Output bus containing the joystick axis position, proportional grip inputs, and button states.
4
Reports faults for individual signals or communication timeout.
5
Reports Not Available state for each signal if connected joystick hardware does not support the function or for all signals if communication
has not yet been established.
Configuration of Input and Output Buses
You do not have to change the configuration of either input or output buses to use the function block.
User Manual
PLUS+1® Compliant JS1 J1939 CAN Joystick Function Block
JS1_J1939 Function Block
©
Danfoss | March 2018 AQ00000202en-US0102 | 9
User Manual
PLUS+1® Compliant JS1 J1939 CAN Joystick Function Block
10 |
©
Danfoss | March 2018 AQ00000202en-US0102
User Manual
PLUS+1® Compliant JS1 J1939 CAN Joystick Function Block
©
Danfoss | March 2018 AQ00000202en-US0102 | 11
Danfoss Power Solutions is a global manufacturer and supplier of high-quality hydraulic and
electronic components. We specialize in providing state-of-the-art technology and solutions
that excel in the harsh operating conditions of the mobile off-highway market. Building on
our extensive applications expertise, we work closely with our customers to ensure
exceptional performance for a broad range of off-highway vehicles.
We help OEMs around the world speed up system development, reduce costs and bring
vehicles to market faster.
Danfoss – Your Strongest Partner in Mobile Hydraulics.
Go to www.powersolutions.danfoss.com for further product information.
Wherever off-highway vehicles are at work, so is Danfoss. We offer expert worldwide support
for our customers, ensuring the best possible solutions for outstanding performance. And
with an extensive network of Global Service Partners, we also provide comprehensive global
service for all of our components.
Please contact the Danfoss Power Solution representative nearest you.
Local address:
Danfoss
Power Solutions GmbH & Co. OHG
Krokamp 35
D-24539 Neumünster, Germany
Phone: +49 4321 871 0
Danfoss
Power Solutions ApS
Nordborgvej 81
DK-6430 Nordborg, Denmark
Phone: +45 7488 2222
Danfoss
Power Solutions (US) Company
2800 East 13th Street
Ames, IA 50010, USA
Phone: +1 515 239 6000
Danfoss
Power Solutions Trading
(Shanghai) Co., Ltd.
Building #22, No. 1000 Jin Hai Rd
Jin Qiao, Pudong New District
Shanghai, China 201206
Phone: +86 21 3418 5200
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products
already on order provided that such alterations can be made without changes being necessary in specifications already agreed.
All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
©
Danfoss | March 2018 AQ00000202en-US0102
Products we offer:
Bent Axis Motors
Closed Circuit Axial Piston
Pumps and Motors
Displays
Electrohydraulic Power
Steering
Electrohydraulics
Hydraulic Power Steering
Integrated Systems
Joysticks and Control
Handles
Microcontrollers and
Software
Open Circuit Axial Piston
Pumps
Orbital Motors
PLUS+1
®
GUIDE
Proportional Valves
Sensors
Steering
Transit Mixer Drives
Comatrol
www.comatrol.com
Turolla
www.turollaocg.com
Hydro-Gear
www.hydro-gear.com
Daikin-Sauer-Danfoss
www.daikin-sauer-danfoss.com
/