Additional network settings items
These additional items will display on the Quickstart page
if the Network Mode has been modified in the Advanced
Networking configuration. Normally they will not be visible
on the Quickstart page.
Network Mode: This allows you to choose between bridged and
routed networking. Bridged networking is the simplest to configure
and will be the correct choice in almost all networks.
•
Bridge: The 215U-2 acts as a network bridge between the radio
and Ethernet ports. Ethernet packets are transparently passed
between the radio and Ethernet ports using rules learned from
traffic that has already passed.
•
Router: The 215U-2 acts as an IP Router between the radio and
Ethernet ports. Only IP packets are passed between the radio
and Ethernet, which are on separate sub-networks. You configure
the rules for which packets are transferred on the routing
configuration page.
Wireless IP Address/Netmask: When the network mode is set to
Router, the Ethernet and Wireless interfaces on the device each
have separate IP addresses. This sets the IP address for the
wireless interface.
I/O Back to Back configuration
This provides a simple method to configure I/O mappings between
two sites in a system. When the networking mode is ProMesh, you
can select this check box to configure the device to automatically
send the I/O data to another device connected to the same network.
You can also connect 115S-12 and 115S-13 modules to provide
additional I/O points.
When you select this option, input data from a remote site is sent to
the system Base. Input data at the base is sent to the remote site
that first sends the data to the Base. You should only set this option
at the base and at one remote site in the system. For more detail
on how this feature operates, refer to section "Default Back-To-Back
gather scatter mapping" on page 20.
Save Changes: Clicking this button saves changes to non-volatile
storage. Changes don’t take effect until the device has been
restarted. If you plan to make changes to multiple pages, use this
button before navigating to another page.
Save Change and Reset: Clicking this button immediately applies
the changes on you have made by saving the new configuration to
non-volatile storage, then forcing the device to reset immediately.
Once the device has booted, the new changes will be in effect.
Connecting to Other 802.11 devices
The 215U-2 uses standard 802.11 networking protocols and it is
possible to use it in conjunction with other 802.11 devices, either
joining an existing network, or allowing other devices to join the
215U-2 network.
Connecting a 215U-2 to existing 802.11 network
To connect to an existing 802.11 Access Point, you need to set
encryption mode and passphrase to match the existing network.
•
For a Manual Mode Client – Set the “System Address (ESSID)”
field to match the SSID of the Access Point
•
For a ProMesh Mesh Node, set the “System Name” field to
match the SSID of the Access Point.
•
For a Fixed Mesh Repeater and Fixed Mesh Remote, set the
“Upstream Device” field to match the SSID of the Access Point.
Connecting your device to an existing 215U-2 network
To connect an 802.11 capable device as a client to an existing
network of 215U-2 devices, you need to set the device’s encryption
mode and passphrase to match the settings in the existing network.
You also need to find the correct network name (SSID) to connect
to. This depends on the type of network you have configured as
shown below:
•
Manual: To connect to an “Access Point” unit in “Manual” mode,
connect to the network which matches the unit’s configured
“System Address (ESSID)” parameter.
ote:N You cannot connect to a “Station (Client)” unit.
•
Fixed Links: To connect to a “Base” unit or a “Repeater” unit in
“Fixed Links” mode, connect to the network that matches the
unit’s configured “Device Name”. Each Base and Repeater should
have a unique device name in the network.
ote:N You cannot connect to a “Field Station” unit.
•
ProMesh: Connecting to device configured for “ProMesh” mode
takes some care. In a ProMesh network all the devices share the
same SSID. This is the configured “System Name”, so your device
may see multiple networks with the same name.
You will always be able to connect to the “Base” unit by selecting
the correct network. For “Mesh Node” units, you must check
the “Enable Hotspot” check box on the unit’s configuration page
to ensure that it remains available for connection. Normally you
can connect to the unit with the best signal strength, and use
the 215U-2 ProMesh network to automatically reach the unit you
need to access.
Your device might also need to be configured with the correct IP
Address. You can do this through manually configuring your device,
or using automatic IP address assignment (DHCP). If you need
your device to be assigned an IP Address through DHCP, you can
configure the DHCP server on the central unit in the 215U-2 network
(This is the Base unit or the Access Point unit). You can access the
DHCP Configuration by selecting “Full Configuration >> DHCP
Server” on the right side menu. Refer to section “DHCP Server” on
page 27 for information on configuring the DHCP server.
Accessing Ethernet devices connected to 215U-2
You can connect devices such as PLCs or HMIs to the Ethernet port
on the remote 215U-2 devices. With the default configuration, you
will be able to access these devices directly from a PC or HMI at the
central site.
The 215U-2 default configuration bridges the wireless and Ethernet
connections. This means that all of the devices, including devices
connected to the remote Ethernet ports, are connected to a single
bridged network.
The 215U-2 can also be configured to route between the Wireless
and Ethernet ports. If you configure your 215U-2 network as a
routed network, then you will need to set up routing rules in your
devices to allow the data packets to reach the correct destination.