  • Hello! I am an AI chatbot trained to assist you with the Danfoss Termix AT BTD Operating instructions. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
Operatingguide
TermixATBTD
1.0TableofContents
1.0TableofContents.............................................1
2.0Functionaldescription......................................2
3.0Safetynotes.....................................................3
3.1SafetyNotesgeneral............................................3
4.0Mounting........................................................4
4.1Mounting...........................................................4
4.2Start-up..............................................................5
5.0Design.............................................................6
5.1DesignTermixATBTD5pipes...................................6
5.2SchematicdiagramTermixATBTD5Pipes....................7
5.3DesignTermixATBTD4pipes...................................8
5.4SchematicdiagramTermixATBTD4Pipes....................9
6.0Controls..........................................................10
6.1DHWtemperaturecontrol........................................10
6.2Other.................................................................11
6.3Maintenance........................................................12
7.0Troubleshooting..............................................13
7.1Troubleshootingingeneral......................................13
7.2TroubleshootingDHW............................................13
7.3Disposal.............................................................14
8.0Declaration......................................................15
8.1Declarationofconformity........................................15
DanfossDistrictEnergy
VI.JV.Y1.02/LUK40692
DEN-GT
1
OperatingguideTermixATBTD
2.0Functionaldescription
Districtheatingsubstationwithtankfordomestichotwater
preparationandwiththermostaticcontrol.Designedfor
wall-mounting.
Application
TheTermixATBTDsubstationisacompletesolutionforhot
water.TheTermixATBTDisapplicableforsingle-familyhouses
orapartments.
Domestichotwater(DHW)
Thedomestichotwatercircuitconsistsofahotwatertankwithcoil
andself-actingthermostaticcontrolvalve.Thehotwatertankand
coilareenamelledandthetankcontainsamagnesiumanode.The
substationisdeliveredwithabuiltinsafetyvalve.
2
DEN-GT
VI.JV.Y1.02/LUK40692
DanfossDistrictEnergy
OperatingguideTermixATBTD
3.0Safetynotes
3.1SafetyNotesgeneral
Thefollowinginstructionsrefertothestandarddesignof
substation.Specialversionsofsubstationsareavailableon
request.
Thisoperatingmanualshouldbereadcarefullybeforeinstallation
andstart-upofthesubstation.Themanufactureracceptsno
liabilityfordamageorfaultsthatresultfromnon-compliancewith
theoperatingmanual.Pleasereadandfollowalltheinstructions
carefullytopreventaccidents,injuryanddamagetoproperty.
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
Pleasecomplywiththeinstructionsissuedbythesystem
manufacturerorsystemoperator.
Corrosionprotection
Allpipesandcomponentsaremadeofstainlesssteelandbrass.
Themaximumchloridecompoundsoftheowmediumshouldnot
behigherthan150mg/l.
Theriskofequipmentcorrosionincreasesconsiderablyifthe
recommendedlevelofpermissiblechloridecompoundsis
exceeded.
Energysource
Thesubstationisdesignedfordistrictheatingastheprimary
sourceofenergy.However,alsootherenergysourcescanbeused
wheretheoperatingconditionsallowitandalwaysarecomparable
todistrictheating.
Application
Thesubstationisdesignedtobeconnectedtothehouse
installationinafrost-freeroom,wherethetemperaturedoesnot
exceed50°Candthehumiditydoesnotexceed60%.Donotcover
orwallupthesubstationorinanyotherwayblocktheentrance
tothestation.
Choiceofmaterial
Choiceofmaterialsalwaysincompliancewithlocallegislation.
Safetyvalve(s)
Werecommendmountingofsafetyvalve(s),however,alwaysin
compliancewithlocalregulations.
Connection
Thesubstationmustbeequippedwithfeaturesthatensurethat
thesubstationcanbeseparatedfromallenergysources(also
powersupply).
Emergency
Incaseofdangeroraccidents-re,leaksorotherdangerous
circumstances-interruptallenergysourcestothestationif
possible,andseekexperthelp.
Incaseofdiscolouredorbad-smellingdomestichotwater,closeall
shut-offvalvesonthesubstation,informtheoperatingpersonnel
andcallforexperthelpimmediately.
Storage
Anystorageofthesubstationwhichmaybenecessarypriorto
installationshouldbeinconditionswhicharedryandheated.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
Pleaseobserveinstructionscarefully
Toavoidinjurytopersonsanddamagetothedevice,itisabsolutely
necessarytoreadandobservetheseinstructionscarefully.
Warningofhighpressureandtemperature
Beawareoftheinstallationspermissiblesystempressureand
temperature.
Themaximumtemperatureoftheowmediuminthesubstationis
120°C.
Themaximumoperatingpressureofthesubstationis10bar.PN16
versionsareavailableonenquiry.
Theriskofpersonsbeinginjuredandequipmentdamagedincreases
considerablyiftherecommendedpermissibleoperatingparameters
areexceeded.
Thesubstationinstallationmustbeequippedwithsafetyvalves,
however,alwaysinaccordancewithlocalregulations.
Warningofhotsurface
Thesubstationhasgothotsurfaces,whichcancauseskinburns.
Pleasebeextremelycautiousincloseproximitytothesubstation.
Powerfailurecanresultinthemotorvalvesbeingstuckinopen
position.Thesurfacesofthesubstationcangethot,whichcancause
skinburns.Theballvalvesondistrictheatingsupplyandreturnshould
beclosed.
Warningoftransportdamage
Beforesubstationinstallation,pleasemakesurethatthesubstation
hasnotbeendamagedduringtransport.
IMPORTANT-Tighteningofconnections
Duetovibrationsduringtransportallangeconnections,screwjoints
andelectricalclampandscrewconnectionsmustbecheckedand
tightenedbeforewaterisaddedtothesystem.Afterwaterhasbeen
addedtothesystemandthesystemhasbeenputintooperation,
re-tightenALLconnections.
DanfossDistrictEnergy
VI.JV.Y1.02/LUK40692
DEN-GT
3
OperatingguideTermixATBTD
4.0Mounting
4.1Mounting
Installationmustbeincompliancewithlocalstandardsand
regulations.
Districtheating(DH)-Inthefollowingsections,DHreferstothe
heatsourcewhichsuppliesthesubstations.Avarietyofenergy
sources,suchasoil,gasorsolarpower,couldbeusedasthe
primarysupplytoDanfosssubstations.Forthesakeofsimplicity,
DHcanbetakentomeantheprimarysupply.
Connectionsizes:
Allconnections:
G¾”(int.thread)
Dimensions(mm):
Withcover:
100L:H1180xW540xD520
150L:H1510xW540xD520
Weight(approx.):85100kg
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
TermixATBTD5pipes
Thepipeplacementcandeviatefromtheshowndrawing.Pleasenote
themarkingsonthestation.
TermixATBTD4pipes
Thepipeplacementcandeviatefromtheshowndrawing.Pleasenote
themarkingsonthestation.
Preinstalled
4
DEN-GT
VI.JV.Y1.02/LUK40692
DanfossDistrictEnergy
OperatingguideTermixATBTD
4.1.1Installation
Mounting:
Adequatespace
Pleaseallowadequatespacearoundthesubstationformounting
andmaintenancepurposes.
Orientation
Thestationmustbemountedsothatcomponents,keyholes
andlabelsareplacedcorrectly.Ifyouwishtomountthestation
differentlypleasecontactyoursupplier.
Drillings
Wheresubstationsaretobewall-mounted,drillingsareprovided
inthebackmountingplate.Floormountedunitshavesupport.
Labelling
Eachconnectiononthesubstationislabelled.
Beforeinstallation:
Cleanandrinse
Priortoinstallation,allsubstationpipesandconnectionsshouldbe
cleanedandrinsed.
Tightening
Duetovibrationduringtransport,allsubstationconnectionsmust
becheckedandtightenedbeforeinstallation.
Unusedconnections
Unusedconnectionsandshut-offvalvesmustbesealedwitha
plug.Shouldtheplugsrequireremoval,thismustonlybedoneby
anauthorizedservicetechnician.
Installation:
Strainer
Ifastrainerissuppliedwiththestationitmustbettedaccording
toschematicdiagram.Pleasenotethatthestrainermaybe
suppliedloose.
Connections
Internalinstallationanddistrictheatingpipesconnectionsmustbe
madeusingthreaded,angedorweldedconnections.
4.2Start-up
Start-up,Directheating
Theshut-offvalvesshouldbeopenedandtheunitobservedas
itentersservice.Visualcheckingshouldconrmtemperatures,
pressures,acceptablethermalexpansionandabsenceofleakage.
Iftheheatexchangeroperatesinaccordancewithdesign,itcanbe
puttoregularuse.
Afterwaterhasbeenaddedtothesystemandthesystemhasbeen
putintooperation,re-tightenALLconnections.
Re-thightenconnections
Afterwaterhasbeenaddedtothesystemandthesystemhasbeen
putintooperation,re-tightenALLconnections.
DanfossDistrictEnergy
VI.JV.Y1.02/LUK40692
DEN-GT
5
OperatingguideTermixATBTD
5.0Design
5.1DesignTermixATBTD5pipes
Yoursubstationmightlookdifferentthanthesubstationshown.
Designdescription
E
Hotwatertankwithcoil
41A
Fittingpiece,coldwatermains
1A
Ballvalve,DVGW
59
Differentialpressure/temperatureregulatorwithowlimiting
4
Safetyvalve
6
DEN-GT
VI.JV.Y1.02/LUK40692
DanfossDistrictEnergy
OperatingguideTermixATBTD
5.2SchematicdiagramTermixATBTD5Pipes
DHW
DCW
CWM
DH
Supply
DH
Return
Yoursubstationmightlookdifferentthantheschematicdiagramshown.
Schematicdescription
E
Hotwatertankwithcoil
41A
Fittingpiece,coldwatermains
1
Ballvalve
59
Differentialpressure/temperatureregulatorwithowlimiting
1A
Ballvalve,DVGW
4
Safetyvalve
DHW:DomesticHotWater
DCW:
DomesticColdWater
CWM:
Coldwatermains
DHSupply:DistrictHeatingSupply
DHReturn:DistrictHeatingReturn
DanfossDistrictEnergy
VI.JV.Y1.02/LUK40692
DEN-GT
7
OperatingguideTermixATBTD
5.3DesignTermixATBTD4pipes
Yoursubstationmightlookdifferentthanthesubstationshown.
Designdescription
E
Hotwatertankwithcoil
4
Safetyvalve
59
Differentialpressure/temperatureregulatorwithowlimiting
8
DEN-GT
VI.JV.Y1.02/LUK40692
DanfossDistrictEnergy
OperatingguideTermixATBTD
5.4SchematicdiagramTermixATBTD4Pipes
DHW
DCW
DH
Supply
DH
Return
Yoursubstationmightlookdifferentthantheschematicdiagramshown.
Schematicdescription
E
Hotwatertankwithcoil
1
Ballvalve
4
Safetyvalve
59
Differentialpressure/temperatureregulatorwithowlimiting
DHW:DomesticHotWater
DCW:
DomesticColdWater
DHSupply:DistrictHeatingSupply
DHReturn:DistrictHeatingReturn
5.4.1Technicalparameters
Technicalparameters
Nominalpressure:
PN10
Max.DHsupplytemperature:
T–max=95°C
DanfossDistrictEnergy
VI.JV.Y1.02/LUK40692
DEN-GT
9
OperatingguideTermixATBTD
6.0Controls
6.1DHWtemperaturecontrol
DHWtemperaturecontrol
TherearevarioustypesofDHWtemperaturecontrolusedin
Danfosssubstations.
DHWtemperatureshouldbeadjustedto45-50°C,asthisprovides
optimalutilisationofDHwater.AtDHWtemperaturesabove55°C,
thepossibilityoflimescaledepositsincreasessignicantly.
6.1.1AB-QMcontroller(45–60°)
QTisaself-actingthermostaticactuatordesignedtobeused
asreturntemperaturecontrolthermostatinone-pipeheating
systems.
QTisdedicatedtobeusedwithAB-QMautomaticbalancing&
controlvalve.
AB-QMDN10-20(45-60°C)
QTSensorsetting(turns)
Temperaturesetting
01
2
34
5
6
20%
48,050,553,0
55,5
58,060,563,0
30%
47,049,552,0
54,5
57,059,562,0
40%
46,048,551,053,556,058,561,0
50%
45,0
47,5
50,052,555,0
57,5
60,0
60%
44,046,549,0
51,5
54,056,559,0
70%
43,0
45,5
48,050,553,0
55,5
58,0
80%
42,0
44,5
47,049,552,0
54,5
57,0
90%
41,043,546,048,551,053,556,0
AB-QM(ow
setting)
100%
40,042,545,0
47,5
50,052,555,0
Thevaluesareintendedasaguide.
10
DEN-GT
VI.JV.Y1.02/LUK40692
DanfossDistrictEnergy
OperatingguideTermixATBTD
6.2Other
6.2.1Coldwatermeterttingpiece
Thesubstationisequippedwithattingpieceforcoldwatermeter.
Assemblyofcoldwatermeter:
1:Closeballvalves
Closetheballvalvesoncoldwater,ifthereiswateronthesystem.
2:Loosennuts
Loosenthenutsonthettingpiece.
3:Removettingpiece
Removethettingpieceandreplaceitwiththecoldwatermeter.
Donotforgetthegaskets.
4:Tightenconnections
Aftermountingofthecoldwatermeterremembertocheckand
tightenallthreadedconnections.
DanfossDistrictEnergy
VI.JV.Y1.02/LUK40692
DEN-GT
11
OperatingguideTermixATBTD
6.3Maintenance
Thesubstationrequireslittlemonitoring,apartfromroutine
checks.Itisrecommendedtoreadtheenergymeteratregular
intervals,andtowritedownthemeterreadings.
RegularinspectionsofthesubstationaccordingtothisInstruction
arerecommended,whichshouldinclude:
Strainers
Cleaningofstrainers.
Meters
Checkingofalloperatingparameterssuchasmeterreadings.
Temperatures
Checkingofalltemperatures,suchasDHsupplytemperatureand
DHWtemperature.
Connections
Checkingallconnectionsforleakages.
Safetyvalves
Theoperationofthesafetyvalvesshouldbecheckedbyturning
thevalveheadintheindicateddirection.
Venting
Checkingthatthesystemisthoroughlyvented.
Inspectionsshouldbecarriedoutminimumeverytwoyears.
SparepartscanbeorderedfromDanfoss.Pleaseensurethatany
enquiryincludesthesubstationserialnumber.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
12
DEN-GT
VI.JV.Y1.02/LUK40692
DanfossDistrictEnergy
OperatingguideTermixATBTD
7.0Troubleshooting
7.1Troubleshootingingeneral
Intheeventofoperatingdisturbances,thefollowingbasicfeatures
shouldbecheckedbeforecarryingoutactualtroubleshooting:
thesubstationisconnectedtoelectricity,
thestrainerontheDHsupplypipeisclean,
thesupplytemperatureoftheDHisatthenormallevel
(summer,atleast60°C-winter,atleast70°C),
thedifferentialpressureisequaltoorhigherthanthenormal
(local)differentialpressureintheDHnetworkifindoubt,ask
theDHplantsupervisor,
pressureonthesystem-checktheHEpressuregauge.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
7.2TroubleshootingDHW
ProblemPossiblecauseSolution
Strainerinsupplyorreturnlineclogged.Cleanstrainer(s).
DHWcirculationpumpoutoforderorwith
toolowsetting.
Checkcirculationpump.
Defectiveorcloggednon-returnvalve.
Replaceclean.
Noelectricity.Check.
Wrongsettingofautomaticcontrols,ifany.Toadjustanelectroniccontrollerfor
DHW,pls.noteenclosedinstructionsfor
electroniccontroller.
Scalingoftheplateheatexchanger.
Replacerinseout.
Defectivemotorizedvalve.Check(usemanualfunction)replace.
Defectivetemperaturesensors.
Checkreplace.
ToolittleornoDHW.
Defectivecontroller.
Checkreplace.
DCWisbeingmixedwiththeDHW,e.g.in
adefectivethermostaticmixingvalve.
Checkreplace. Hotwaterinsometapsbutnotinall.
Defectiveorcloggednon-returnvalveon
circulationvalve.
Replaceclean.
Taptemperaturetoohigh;DHWtapload
toohigh.
Thermostaticvalveadjustedtoatoohigh
level.
Checkset.
Scalingoftheplateheatexchanger.
Replacerinseout. Temperaturedropduringtapping.
LargerDHWowthanthesubstationhas
beendesignedfor.
ReduceDHWow.
Thermostaticcontrolvalvedoesnotclose
TemperaturedifferencebetweenDH
supplyandDHWsetpointtoolow.
Lowerthesetpointtemperatureor
increasetheDHsupplytemperature.
DanfossDistrictEnergy
VI.JV.Y1.02/LUK40692
DEN-GT
13
OperatingguideTermixATBTD
7.3Disposal
Disposal
Thisproductshouldbedismantledanditscomponents
sorted,ifpossible,invariousgroupsbeforerecycling
ordisposal.
Alwaysfollowthelocaldisposalregulations.
14
DEN-GT
VI.JV.Y1.02/LUK40692
DanfossDistrictEnergy
OperatingguideTermixATBTD
8.0Declaration
8.1Declarationofconformity
8.1.1Category0withoutelectricalequipment
EUDeclarationofConformity
GeminaTermixA/S
MemberoftheDanfossGroup
Navervej15-17
DK-7451Sunds
Declaresunderoursoleresponsibilitythattheproduct
SubstationCategory0withoutelectricalequipment,
coveredbythisdeclaration,isinconformitywiththefollowingdirective(s),standard(s)orothernormative
document(s),providedtheproductisusedinaccordancewithourinstructions.
MachineryDirective2006/42/EC
DS/EN60204-1/A1:2009.Safetyofmachinery
Part1GeneralRequirements.
DS/EN12100:2011.SafetyofmachineryRisk
assessment.
Sunds2016.03.29
PlaceanddateofissueClausGjøderumMortensen
Quality&EnvironmentManager
DanfossDistrictEnergy
VI.JV.Y1.02/LUK40692
DEN-GT
15
OperatingguideTermixATBTD
ProducedbyDanfossA/S©04/2016
/