Danfoss Termix One Solar Operating instructions

Type
Operating instructions

Danfoss Termix One Solar is an instantaneous water heater designed for wall-mounting and applicable for heating systems with buffer accumulators, solar systems, or other heat sources where a very low return temperature is preferred. It features a heat exchanger for efficient heat extraction, a thermostatic control valve for precise temperature regulation, and a sensor accelerator for protection against overheating and lime scale formation.

Danfoss Termix One Solar is an instantaneous water heater designed for wall-mounting and applicable for heating systems with buffer accumulators, solar systems, or other heat sources where a very low return temperature is preferred. It features a heat exchanger for efficient heat extraction, a thermostatic control valve for precise temperature regulation, and a sensor accelerator for protection against overheating and lime scale formation.

InstallationGuide
TermixOneSolar
1.0TableofContents
1.0TableofContents.............................................1
........................................................................2
2.0Functionaldescription......................................3
3.0Safetynotes.....................................................4
3.1SafetyNotesgeneral............................................4
4.0Mounting........................................................5
4.1Mounting...........................................................5
4.2Electricalconnections.............................................7
5.0Design.............................................................8
5.1Design...............................................................8
5.2Schematicdiagram................................................9
5.3Design...............................................................10
5.4Schematicdiagram................................................11
6.0Controls..........................................................12
6.1DHWtemperaturecontrol........................................12
6.2Maintenance........................................................13
7.0Troubleshooting..............................................14
7.1Troubleshootingingeneral......................................14
7.2TroubleshootingDHW............................................14
7.3Disposal.............................................................15
8.0Declaration......................................................19
8.1Declarationofconformity........................................19
DanfossDistrictEnergy
VI.CW.K3.02/LUK38004
DEN-GT
1
InstallationGuideTermixOneSolar
2
DEN-GT
VI.CW.K3.02/LUK38004
DanfossDistrictEnergy
InstallationGuideTermixOneSolar
2.0Functionaldescription
Domestichotwatermodulewithheatexchangerand
thermostaticcontrol.Designedforwall-mounting.
Application
TheTermixOneSolarisaninstantaneouswaterheater,featuring
superbheatextractionandhighperformance.TheTermixOne
Solarisapplicableforheatingsystemswithbufferaccumulators,
solarsystemsorforotherheatsources,whereaverylowreturn
temperatureispreferred.Thewaterheaterisavailableinthree
sizes,eitherfor1apartment,for1-4apartmentsorfor5upto10
apartments.Thelargeheatexchangercoolsoutthewaterinthe
primaryreturnlineveryefciently,therebycreatingaverygood
operationeconomy.Aowswitchincoldwatermainsiscontrolling
theprimaryheatingpump.Anoptionalcirculationpumptogether
withathermostatcanmaintainthecirculatingtemperatureata
desiredtemperature.
Domestichotwater(DHW)
Thedomestichotwaterispreparedintheheatexchangerand
thetemperatureisregulatedwithathermostaticcontrolvalve.
Thepatentedsensoracceleratoracceleratestheclosingofthe
thermostaticcontrolvalveandprotectstheheatexchangeragainst
overheatingandlimescaleformation.Thesensoracceleratorand
thethermostaticcontrolvalvealsoworksasabypasskeepingthe
heatexchangerandsupplylinewarm.Thisshortensthewaiting
periods.Thesensoracceleratorhelpstoensureastablehotwater
temperaturebyvaryingloads,owtemperaturesanddifferential
pressurewithouttheneedforreadjustingthevalve.Thereisno
additionalpressurelossonthesecondarysideoftheDHWheat
exchangerwithathermostaticcontrol.Thereforethistypeof
regulationcanbeusedbylowpressureinthecoldwatermains.
DanfossDistrictEnergy
VI.CW.K3.02/LUK38004
DEN-GT
3
InstallationGuideTermixOneSolar
3.0Safetynotes
3.1SafetyNotesgeneral
Thefollowinginstructionsrefertothestandarddesignof
substation.Specialversionsofsubstationsareavailableon
request.
Thisoperatingmanualshouldbereadcarefullybeforeinstallation
andstart-upofthesubstation.Themanufactureracceptsno
liabilityfordamageorfaultsthatresultfromnon-compliancewith
theoperatingmanual.Pleasereadandfollowalltheinstructions
carefullytopreventaccidents,injuryanddamagetoproperty.
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
Pleasecomplywiththeinstructionsissuedbythesystem
manufacturerorsystemoperator.
Corrosionprotection
Allpipesandcomponentsaremadeofstainlesssteelandbrass.
Themaximumchloridecompoundsoftheowmediumshouldnot
behigherthan150mg/l.
Theriskofequipmentcorrosionincreasesconsiderablyifthe
recommendedlevelofpermissiblechloridecompoundsis
exceeded.
Energysource
Thesubstationisdesignedfordistrictheatingastheprimary
sourceofenergy.However,alsootherenergysourcescanbeused
wheretheoperatingconditionsallowitandalwaysarecomparable
todistrictheating.
Application
Thesubstationisdesignedtobeconnectedtothehouse
installationinafrost-freeroom,wherethetemperaturedoesnot
exceed50°Candthehumiditydoesnotexceed60%.Donotcover
orwallupthesubstationorinanyotherwayblocktheentrance
tothestation.
Choiceofmaterial
Choiceofmaterialsalwaysincompliancewithlocallegislation.
Safetyvalve(s)
Werecommendmountingofsafetyvalve(s),however,alwaysin
compliancewithlocalregulations.
Connection
Thesubstationmustbeequippedwithfeaturesthatensurethat
thesubstationcanbeseparatedfromallenergysources(also
powersupply).
Emergency
Incaseofdangeroraccidents-re,leaksorotherdangerous
circumstances-interruptallenergysourcestothestationif
possible,andseekexperthelp.
Incaseofdiscolouredorbad-smellingdomestichotwater,closeall
shut-offvalvesonthesubstation,informtheoperatingpersonnel
andcallforexperthelpimmediately.
Storage
Anystorageofthesubstationwhichmaybenecessarypriorto
installationshouldbeinconditionswhicharedryandheated.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
Pleaseobserveinstructionscarefully
Toavoidinjurytopersonsanddamagetothedevice,itisabsolutely
necessarytoreadandobservetheseinstructionscarefully.
Warningofhighpressureandtemperature
Beawareoftheinstallationspermissiblesystempressureand
temperature.
Themaximumtemperatureoftheowmediuminthesubstationis
120°C.
Themaximumoperatingpressureofthesubstationis10bar.PN16
versionsareavailableonenquiry.
Theriskofpersonsbeinginjuredandequipmentdamagedincreases
considerablyiftherecommendedpermissibleoperatingparameters
areexceeded.
Thesubstationinstallationmustbeequippedwithsafetyvalves,
however,alwaysinaccordancewithlocalregulations.
Warningofhotsurface
Thesubstationhasgothotsurfaces,whichcancauseskinburns.
Pleasebeextremelycautiousincloseproximitytothesubstation.
Powerfailurecanresultinthemotorvalvesbeingstuckinopen
position.Thesurfacesofthesubstationcangethot,whichcancause
skinburns.Theballvalvesondistrictheatingsupplyandreturnshould
beclosed.
Warningoftransportdamage
Beforesubstationinstallation,pleasemakesurethatthesubstation
hasnotbeendamagedduringtransport.
IMPORTANT-Tighteningofconnections
Duetovibrationsduringtransportallangeconnections,screwjoints
andelectricalclampandscrewconnectionsmustbecheckedand
tightenedbeforewaterisaddedtothesystem.Afterwaterhasbeen
addedtothesystemandthesystemhasbeenputintooperation,
re-tightenALLconnections.
4
DEN-GT
VI.CW.K3.02/LUK38004
DanfossDistrictEnergy
InstallationGuideTermixOneSolar
4.0Mounting
4.1Mounting
Installationmustbeincompliancewithlocalstandardsand
regulations.
Districtheating(DH)-Inthefollowingsections,DHreferstothe
heatsourcewhichsuppliesthesubstations.Avarietyofenergy
sources,suchasoil,gasorsolarpower,couldbeusedasthe
primarysupplytoDanfosssubstations.Forthesakeofsimplicity,
DHcanbetakentomeantheprimarysupply.
Connections:
1.Domesticcoldwater(DCW)
2.Domestichotwater(DHW)
3.BufferTank(BT)supply
4.BufferTank(BT)return
5.Hotwatercirculation(HWC)-(Optional)
Connectionsizes:
BT:
G¾”(int.thread)
DCW+DHW+HWC:
G¾”(int.thread)
Dimensions(mm):
Withoutcirculationandcover:
H760xW312xD155
Withoutcirculationandwithcover:
H760xW315xD165
Withcirculationandwithoutcover:
H935xW410xD190
Weight(approx.):20kg
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
Thepipeplacementcandeviatefromtheshowndrawing.Pleasenote
themarkingsonthestation.
DanfossDistrictEnergy
VI.CW.K3.02/LUK38004
DEN-GT
5
InstallationGuideTermixOneSolar
4.1.1Installation
Mounting:
Adequatespace
Pleaseallowadequatespacearoundthesubstationformounting
andmaintenancepurposes.
Orientation
Thestationmustbemountedsothatcomponents,keyholes
andlabelsareplacedcorrectly.Ifyouwishtomountthestation
differentlypleasecontactyoursupplier.
Drillings
Wheresubstationsaretobewall-mounted,drillingsareprovided
inthebackmountingplate.Floormountedunitshavesupport.
Labelling
Eachconnectiononthesubstationislabelled.
Beforeinstallation:
Cleanandrinse
Priortoinstallation,allsubstationpipesandconnectionsshouldbe
cleanedandrinsed.
Thightening
Duetovibrationduringtransport,allsubstationconnectionsmust
becheckedandtightenedbeforeinstallation.
Unusedconnections
Unusedconnectionsandshut-offvalvesmustbesealedwitha
plug.Shouldtheplugsrequireremoval,thismustonlybedoneby
anauthorizedservicetechnician.
Installation:
Strainer
Ifastrainerissuppliedwiththestationitmustbettedaccording
toschematicdiagram.Pleasenotethatthestrainermaybe
suppliedloose.
Connections
Internalinstallationanddistrictheatingpipesconnectionsmustbe
madeusingthreaded,angedorweldedconnections.
Keyholeformounting.
6
DEN-GT
VI.CW.K3.02/LUK38004
DanfossDistrictEnergy
InstallationGuideTermixOneSolar
4.2Electricalconnections
Beforemakingelectricalconnections,pleasenotethe
following:
Safetynotes
Pleasereadtherelevantpartsofthesafetynotes.
230V
Thesubstationmustbeconnectedto230VACandearth.
Disconnection
Thesubstationmustbeelectricallyconnectedsothatitcanbe
disconnectedforrepairs.
Outdoortemperaturesensor
Outdoorsensorsshouldbemountedsoastoavoidexposureto
directsunlight.Theyshouldnotbeplacedclosetodoors,windows
orventilationoutlets.
Theoutdoorsensormustbeconnectedtothestationonthe
terminalblockundertheelectroniccontrol.
Authorizedelectrician
Electricalconnectionsmustbemadebyanauthorizedelectricianonly.
Localstandards
Electricalconnectionsmustbemadeinaccordancewithcurrent
regulationsandlocalstandards.
DanfossDistrictEnergy
VI.CW.K3.02/LUK38004
DEN-GT
7
InstallationGuideTermixOneSolar
5.0Design
5.1Design
5.1.1DesignTermixOneSolar
Yoursubstationmightlookdifferentthanthesubstationshown.
Designdescription
B
Heatexchanger,DHW
35
Ballvalve/non-returnvalve
O
Termixsensoraccelerator
45
Flowswitch
7
Thermostaticcontroller,DHW
48
Airvent,manual
13
Chargingpump
63
Sieve
8
DEN-GT
VI.CW.K3.02/LUK38004
DanfossDistrictEnergy
InstallationGuideTermixOneSolar
5.2Schematicdiagram
5.2.1SchematicdiagramTermixOneSolar
BT
Supply
DHW
BT
Return
DCW
Yoursubstationmightlookdifferentthantheschematicdiagramshown.
Schematicdescriptionwithoutcirculation
B
Heatexchanger,DHW
7
Thermostaticvalve
45
Flowswitch
O
Termixsensoraccelerator
13
Chargingpump
48
Airvent,manual
1
Ballvalve
35
Ballvalve/non-returnvalve
63
Sieve
2
Singlecheckvalve
39
Connectionclosed
DHW:DomesticHotWater
DCW:
DomesticColdWater
BTSupply:
Buffertanksupply
BTReturn:
Buffertankreturn
DanfossDistrictEnergy
VI.CW.K3.02/LUK38004
DEN-GT
9
InstallationGuideTermixOneSolar
5.3Design
5.3.1DesignTermixOneSolarwithcirculation
Yoursubstationmightlookdifferentthanthesubstationshown.
Designdescription
B
Heatexchanger,DHW
13
Chargingpump
O
Termixsensoraccelerator
35
Ballvalve/non-returnvalve
4
Safetyvalve
45
Flowswitch
7
Thermostaticcontroller,DHW
48
Airvent,manual
11A
DHWpump,withbuildincheckvalve
63
Sieve
10
DEN-GT
VI.CW.K3.02/LUK38004
DanfossDistrictEnergy
InstallationGuideTermixOneSolar
5.4Schematicdiagram
5.4.1SchematicdiagramTermixOneSolarwithcirculation
BT
Supply
DHW
HWC
BT
ReturnDCW
Yoursubstationmightlookdifferentthantheschematicdiagramshown.
Schematicdescriptionwithcirculation
B
Heatexchanger,DHW
7
Thermostaticvalve
39
Connectionclosed
O
Termixsensoraccelerator
11A
DHWpump,withbuiltincheckvalve
45
Flowswitch
1
Ballvalve
13
Chargingpump
48
Airvent,manual
2
Singlecheckvalve
21
Tobeorderedseparately
63
Sieve
4
Safetyvalve
35
Ballvalve/non-returnvalve
DHW:DomesticHotWater
DCW:
DomesticColdWater
HWC:
HotWaterCirculation
BTSupply:
Buffertanksupply
BTReturn:
Buffertankreturn
5.4.2Technicalparameters
Technicalparameters
Nominalpressure:
PN16
Max.DHsupplytemperature:
120°C
Min.DCWstaticpressure:
0.5bar
Brazingmaterial(HEX):
Copper
Heatexchangerstestpressure:30bar
Soundlevel:55dB
DanfossDistrictEnergy
VI.CW.K3.02/LUK38004
DEN-GT
11
InstallationGuideTermixOneSolar
6.0Controls
6.1DHWtemperaturecontrol
DHWtemperaturecontrol
TherearevarioustypesofDHWtemperaturecontrolusedin
Danfosssubstations.
DHWtemperatureshouldbeadjustedto45-50°C,asthisprovides
optimalutilisationofDHwater.AtDHWtemperaturesabove55°C,
thepossibilityoflimescaledepositsincreasessignicantly.
6.1.1AVTBcontroller(20–60°)
Thetemperaturesettingisasfollows:
1=20°C
2=35°C
3=50°C
4=60°C
5=70°C
Thevaluesareintendedasaguide.
TheAVTBoperatesatitsbestatDHsupplytemperaturesofupto
90°C.
Thermostaticcontrol
DHWtemperatureisadjustedasfollows:
Toincreasetemperature,turnthehandleonthethermostatic
controllertoselectahighernumber.
Todecreasetemperature,turnthehandleonthethermostatic
controllertoselectalowernumber.
6.1.2Domestichotwaterpump
Thedomestichotwaterpumpcanbeprogrammedwiththe
desiredtimeprogramme.
12
DEN-GT
VI.CW.K3.02/LUK38004
DanfossDistrictEnergy
InstallationGuideTermixOneSolar
6.2Maintenance
Thesubstationrequireslittlemonitoring,apartfromroutine
checks.Itisrecommendedtoreadtheenergymeteratregular
intervals,andtowritedownthemeterreadings.
RegularinspectionsofthesubstationaccordingtothisInstruction
arerecommended,whichshouldinclude:
Strainers
Cleaningofstrainers.
Meters
Checkingofalloperatingparameterssuchasmeterreadings.
Temperatures
Checkingofalltemperatures,suchasDHsupplytemperatureand
DHWtemperature.
Connections
Checkingallconnectionsforleakages.
Safetyvalves
Theoperationofthesafetyvalvesshouldbecheckedbyturning
thevalveheadintheindicateddirection.
Venting
Checkingthatthesystemisthoroughlyvented.
Inspectionsshouldbecarriedoutminimumeverytwoyears.
SparepartscanbeorderedfromDanfoss.Pleaseensurethatany
enquiryincludesthesubstationserialnumber.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
DanfossDistrictEnergy
VI.CW.K3.02/LUK38004
DEN-GT
13
InstallationGuideTermixOneSolar
7.0Troubleshooting
7.1Troubleshootingingeneral
Intheeventofoperatingdisturbances,thefollowingbasicfeatures
shouldbecheckedbeforecarryingoutactualtroubleshooting:
thesubstationisconnectedtoelectricity,
thestrainerontheDHsupplypipeisclean,
thesupplytemperatureoftheDHisatthenormallevel
(summer,atleast60°C-winter,atleast70°C),
thedifferentialpressureisequaltoorhigherthanthenormal
(local)differentialpressureintheDHnetworkifindoubt,ask
theDHplantsupervisor,
pressureonthesystem-checktheHEpressuregauge.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
7.2TroubleshootingDHW
ProblemPossiblecauseSolution
Strainerinsupplyorreturnlineclogged.Cleanstrainer(s).
DHWcirculationpumpoutoforderorwith
toolowsetting.
Checkcirculationpump.
Defectiveorcloggednon-returnvalve.
Replaceclean.
Noelectricity.Check.
Wrongsettingofautomaticcontrols,ifany.Toadjustanelectroniccontrollerfor
DHW,pls.noteenclosedinstructionsfor
electroniccontroller.
Scalingoftheplateheatexchanger.
Replacerinseout.
Defectivemotorizedvalve.Check(usemanualfunction)replace.
Defectivetemperaturesensors.
Checkreplace.
ToolittleornoDHW.
Defectivecontroller.
Checkreplace.
DCWisbeingmixedwiththeDHW,e.g.in
adefectivethermostaticmixingvalve.
Checkreplace. Hotwaterinsometapsbutnotinall.
Defectiveorcloggednon-returnvalveon
circulationvalve.
Replaceclean.
Taptemperaturetoohigh;DHWtapload
toohigh.
Thermostaticvalveadjustedtoatoohigh
level.
Checkset.
Scalingoftheplateheatexchanger.
Replacerinseout. Temperaturedropduringtapping.
LargerDHWowthanthesubstationhas
beendesignedfor.
ReduceDHWow.
Thermostaticcontrolvalvedoesnotclose
TemperaturedifferencebetweenDH
supplyandDHWsetpointtoolow.
Lowerthesetpointtemperatureor
increasetheDHsupplytemperature.
14
DEN-GT
VI.CW.K3.02/LUK38004
DanfossDistrictEnergy
InstallationGuideTermixOneSolar
7.3Disposal
Disposal
Thisproductshouldbedismantledanditscomponents
sorted,ifpossible,invariousgroupsbeforerecycling
ordisposal.
Alwaysfollowthelocaldisposalregulations.
DanfossDistrictEnergy
VI.CW.K3.02/LUK38004
DEN-GT
15
InstallationGuideTermixOneSolar
16
DEN-GT
VI.CW.K3.02/LUK38004
DanfossDistrictEnergy
InstallationGuideTermixOneSolar
DanfossDistrictEnergy
VI.CW.K3.02/LUK38004
DEN-GT
17
InstallationGuideTermixOneSolar
18
DEN-GT
VI.CW.K3.02/LUK38004
DanfossDistrictEnergy
InstallationGuideTermixOneSolar
8.0Declaration
8.1Declarationofconformity
8.1.1Category0withelectricalequipment
ECDeclarationofConformity
GeminaTermixA/S
MemberoftheDanfossGroup
Navervej15-17
DK-7451Sunds
Declaresonoursoleresponsibilitythatthebelowproducts:
SubstationsCategory0withelectricalequipment,
coveredbythisdeclarationareinconformitywiththefollowingdirectives,standardsandothernormative
documents,providedthattheyareusedaccordingtoourinstructions.
MachineryDirective2006/42/EC
DS/EN60204-1/A1:2009.Safetyofmachinery
Part1GeneralRequirements.
DS/EN12100:2011.SafetyofmachineryRisk
assessment.
LVDLowVoltageDirective2006/95/EC
DS/EN60204-1/A1:2009.Safetyofmachinery
Part1GeneralRequirements.
EMCDirective2004/108/EC
DS/EN61000-6-2/Corr.:2005.Electromagnetic
compatibilityGenericstandard:Immunity
industry.
DS/EN61000-6-3:2007.Electromagnetic
compatibilityGenericstandard:Emissionfor
residential,commercial&lightindustry.
Sunds2013.03.15
PlaceanddateofissueClausGjøderumMortensen
Quality&EnvironmentManager
DanfossDistrictEnergy
VI.CW.K3.02/LUK38004
DEN-GT
19
InstallationGuideTermixOneSolar
ProducedbyDanfossA/S©11/2013
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20

Danfoss Termix One Solar Operating instructions

Type
Operating instructions

Danfoss Termix One Solar is an instantaneous water heater designed for wall-mounting and applicable for heating systems with buffer accumulators, solar systems, or other heat sources where a very low return temperature is preferred. It features a heat exchanger for efficient heat extraction, a thermostatic control valve for precise temperature regulation, and a sensor accelerator for protection against overheating and lime scale formation.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI