Danfoss Termix Solar A+/B+ Operating instructions

  • Hello! I am an AI chatbot trained to assist you with the Danfoss Termix Solar A+/B+ Operating instructions. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
OperatingGuide
TermixSolarA+/B+
1.0TableofContents
1.0TableofContents.............................................1
........................................................................2
2.0Functionaldescription......................................3
3.0Safetynotes.....................................................4
3.1SafetyNotesgeneral............................................4
4.0Mounting........................................................5
4.1Mounting...........................................................5
4.2Electricalconnections.............................................7
5.0Design.............................................................8
5.1Design...............................................................8
5.2Schematicdiagram................................................9
5.3Design...............................................................10
5.4Schematicdiagram................................................11
6.0Controls..........................................................12
6.1DHWtemperaturecontrol........................................12
6.2Maintenance........................................................14
7.0Troubleshooting..............................................15
7.1Troubleshootingingeneral......................................15
7.2TroubleshootingDHW............................................15
7.3Disposal.............................................................16
8.0Declaration......................................................19
8.1Declarationofconformity........................................19
DanfossDistrictEnergy
VI.JV.I2.02/LUK38016
DEN-GT
1
OperatingGuideTermixSolarA+/B+
2
DEN-GT
VI.JV.I2.02/LUK38016
DanfossDistrictEnergy
OperatingGuideTermixSolarA+/B+
2.0Functionaldescription
Domestichotwatermodulewithheatexchangerand
thermostaticcontrol.Designedforwall-mounting.
Application
TheTermixSolarA+/B+isaninstantaneouswaterheater,featuring
superbheatextractionandhighperformance.TheTermixSolar
A+/B+isapplicableforheatingsystemswithbufferaccumulators,
solarsystemsorforotherheatsources,whereaverylowreturn
temperatureispreferred.Thelargeheatexchangercoolsoutthe
waterintheprimaryreturnlineveryefciently,therebycreatinga
verygoodoperationeconomy.Aowswitchinthedomestichot
waterpipeiscontrollingtheprimaryheatingpump.Anoptional
circulationpumptogetherwithathermostatcanmaintainthe
circulatingtemperatureatadesiredtemperature.
Domestichotwater(DHW)
Thedomestichotwaterispreparedintheheatexchangerandthe
temperatureisregulatedwithathermostaticcontrolvalve.There
isnoadditionalpressurelossonthesecondarysideoftheDHW
heatexchangerwithathermostaticcontrol.Thereforethistypeof
regulationcanbeusedbylowpressureinthecoldwatermains.
DanfossDistrictEnergy
VI.JV.I2.02/LUK38016
DEN-GT
3
OperatingGuideTermixSolarA+/B+
3.0Safetynotes
3.1SafetyNotesgeneral
Thefollowinginstructionsrefertothestandarddesignof
substation.Specialversionsofsubstationsareavailableon
request.
Thisoperatingmanualshouldbereadcarefullybeforeinstallation
andstart-upofthesubstation.Themanufactureracceptsno
liabilityfordamageorfaultsthatresultfromnon-compliancewith
theoperatingmanual.Pleasereadandfollowalltheinstructions
carefullytopreventaccidents,injuryanddamagetoproperty.
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
Pleasecomplywiththeinstructionsissuedbythesystem
manufacturerorsystemoperator.
Corrosionprotection
Allpipesandcomponentsaremadeofstainlesssteelandbrass.
Themaximumchloridecompoundsoftheowmediumshouldnot
behigherthan150mg/l.
Theriskofequipmentcorrosionincreasesconsiderablyifthe
recommendedlevelofpermissiblechloridecompoundsis
exceeded.
Energysource
Thesubstationisdesignedfordistrictheatingastheprimary
sourceofenergy.However,alsootherenergysourcescanbeused
wheretheoperatingconditionsallowitandalwaysarecomparable
todistrictheating.
Application
Thesubstationisdesignedtobeconnectedtothehouse
installationinafrost-freeroom,wherethetemperaturedoesnot
exceed50°Candthehumiditydoesnotexceed60%.Donotcover
orwallupthesubstationorinanyotherwayblocktheentrance
tothestation.
Choiceofmaterial
Choiceofmaterialsalwaysincompliancewithlocallegislation.
Safetyvalve(s)
Werecommendmountingofsafetyvalve(s),however,alwaysin
compliancewithlocalregulations.
Connection
Thesubstationmustbeequippedwithfeaturesthatensurethat
thesubstationcanbeseparatedfromallenergysources(also
powersupply).
Emergency
Incaseofdangeroraccidents-re,leaksorotherdangerous
circumstances-interruptallenergysourcestothestationif
possible,andseekexperthelp.
Incaseofdiscolouredorbad-smellingdomestichotwater,closeall
shut-offvalvesonthesubstation,informtheoperatingpersonnel
andcallforexperthelpimmediately.
Storage
Anystorageofthesubstationwhichmaybenecessarypriorto
installationshouldbeinconditionswhicharedryandheated.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
Pleaseobserveinstructionscarefully
Toavoidinjurytopersonsanddamagetothedevice,itisabsolutely
necessarytoreadandobservetheseinstructionscarefully.
Warningofhighpressureandtemperature
Beawareoftheinstallationspermissiblesystempressureand
temperature.
Themaximumtemperatureoftheowmediuminthesubstationis
120°C.
Themaximumoperatingpressureofthesubstationis10bar.PN16
versionsareavailableonenquiry.
Theriskofpersonsbeinginjuredandequipmentdamagedincreases
considerablyiftherecommendedpermissibleoperatingparameters
areexceeded.
Thesubstationinstallationmustbeequippedwithsafetyvalves,
however,alwaysinaccordancewithlocalregulations.
Warningofhotsurface
Thesubstationhasgothotsurfaces,whichcancauseskinburns.
Pleasebeextremelycautiousincloseproximitytothesubstation.
Powerfailurecanresultinthemotorvalvesbeingstuckinopen
position.Thesurfacesofthesubstationcangethot,whichcancause
skinburns.Theballvalvesondistrictheatingsupplyandreturnshould
beclosed.
Warningoftransportdamage
Beforesubstationinstallation,pleasemakesurethatthesubstation
hasnotbeendamagedduringtransport.
IMPORTANT-Tighteningofconnections
Duetovibrationsduringtransportallangeconnections,screwjoints
andelectricalclampandscrewconnectionsmustbecheckedand
tightenedbeforewaterisaddedtothesystem.Afterwaterhasbeen
addedtothesystemandthesystemhasbeenputintooperation,
re-tightenALLconnections.
4
DEN-GT
VI.JV.I2.02/LUK38016
DanfossDistrictEnergy
OperatingGuideTermixSolarA+/B+
4.0Mounting
4.1Mounting
Installationmustbeincompliancewithlocalstandardsand
regulations.
Districtheating(DH)-Inthefollowingsections,DHreferstothe
heatsourcewhichsuppliesthesubstations.Avarietyofenergy
sources,suchasoil,gasorsolarpower,couldbeusedasthe
primarysupplytoDanfosssubstations.Forthesakeofsimplicity,
DHcanbetakentomeantheprimarysupply.
Connections:
1.BufferTank(BT)supply
2.Domestichotwater(DHW)
3.BufferTank(BT)return
4.Domesticcoldwater(DCW)
5.Hotwatercirculation(HWC)-(Optional)
Connectionsizes:
BT:
G¾”(int.thread)
DCW+DHW+HWC:
G¾”(int.thread)
Dimensions(mm):
Withoutcirculationandcover:
H655xW440xD138
Withoutcirculationandwithcover:
H715xW450xD150
Withcirculationandwithoutcover:
H940xW440xD138
Withcirculationandcover:
H940xW450xD150
Weight(approx.):
BrazedHEX(A+):
14kg
GasketedHEX(B+):
17kg
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
Thepipeplacementcandeviatefromtheshowndrawing.Pleasenote
themarkingsonthestation.
DanfossDistrictEnergy
VI.JV.I2.02/LUK38016
DEN-GT
5
OperatingGuideTermixSolarA+/B+
4.1.1Installation
Mounting:
Adequatespace
Pleaseallowadequatespacearoundthesubstationformounting
andmaintenancepurposes.
Orientation
Thestationmustbemountedsothatcomponents,keyholes
andlabelsareplacedcorrectly.Ifyouwishtomountthestation
differentlypleasecontactyoursupplier.
Drillings
Wheresubstationsaretobewall-mounted,drillingsareprovided
inthebackmountingplate.Floormountedunitshavesupport.
Labelling
Eachconnectiononthesubstationislabelled.
Beforeinstallation:
Cleanandrinse
Priortoinstallation,allsubstationpipesandconnectionsshouldbe
cleanedandrinsed.
Tightening
Duetovibrationduringtransport,allsubstationconnectionsmust
becheckedandtightenedbeforeinstallation.
Unusedconnections
Unusedconnectionsandshut-offvalvesmustbesealedwitha
plug.Shouldtheplugsrequireremoval,thismustonlybedoneby
anauthorizedservicetechnician.
Installation:
Strainer
Ifastrainerissuppliedwiththestationitmustbettedaccording
toschematicdiagram.Pleasenotethatthestrainermaybe
suppliedloose.
Connections
Internalinstallationanddistrictheatingpipesconnectionsmustbe
madeusingthreaded,angedorweldedconnections.
Keyholeformounting.
6
DEN-GT
VI.JV.I2.02/LUK38016
DanfossDistrictEnergy
OperatingGuideTermixSolarA+/B+
4.2Electricalconnections
Beforemakingelectricalconnections,pleasenotethe
following:
Safetynotes
Pleasereadtherelevantpartsofthesafetynotes.
230V
Thesubstationmustbeconnectedto230VACandearth.
Potentialbonding
Potentialbondingshouldbecarriedoutaccording
to60364-4-41:2007andIEC60364-5-54:2011.
Bondingpointonthemountingplatebelowrightcornermarked
withearthsymbol.
Disconnection
Thesubstationmustbeelectricallyconnectedsothatitcanbe
disconnectedforrepairs.
Outdoortemperaturesensor
Outdoorsensorsshouldbemountedsoastoavoidexposureto
directsunlight.Theyshouldnotbeplacedclosetodoors,windows
orventilationoutlets.
Theoutdoorsensormustbeconnectedtothestationonthe
terminalblockundertheelectroniccontrol.
Authorizedelectrician
Electricalconnectionsmustbemadebyanauthorizedelectricianonly.
Localstandards
Electricalconnectionsmustbemadeinaccordancewithcurrent
regulationsandlocalstandards.
DanfossDistrictEnergy
VI.JV.I2.02/LUK38016
DEN-GT
7
OperatingGuideTermixSolarA+/B+
5.0Design
5.1Design
5.1.1DesignTermixSolarA+/B+
Yoursubstationmightlookdifferentthanthesubstationshown.
Designdescription
B
Heatexchanger,DHW
13
Chargingpump
M
Electricalwiringbox
21
Tobeorderedseparately
7
Thermostaticcontroller,DHW
35
Ballvalve/non-returnvalve
45
Flowswitch
8
DEN-GT
VI.JV.I2.02/LUK38016
DanfossDistrictEnergy
OperatingGuideTermixSolarA+/B+
5.2Schematicdiagram
5.2.1SchematicdiagramTermixSolarA+/B+
BT
Supply
DHW
BT
Return
DCW
Yoursubstationmightlookdifferentthantheschematicdiagramshown.
Schematicdescriptionwithoutcirculation
B
Heatexchanger,DHW
1A
Ballvalve,DVGW
21
Tobeorderedseparately
M
Electricalwiringbox
7
Thermostaticvalve
35
Ballvalve/non-returnvalve
1
Ballvalve
13
Chargingpump
45
Flowswitch
DHW:DomesticHotWater
DCW:
DomesticColdWater
BTSupply:
Buffertanksupply
BTReturn:
Buffertankreturn
DanfossDistrictEnergy
VI.JV.I2.02/LUK38016
DEN-GT
9
OperatingGuideTermixSolarA+/B+
5.3Design
5.3.1DesignTermixSolarA+/B+withcirculation
Yoursubstationmightlookdifferentthanthesubstationshown.
Designdescription
B
Heatexchanger,DHW
7
Thermostaticcontroller,DHW
21
Tobeorderedseparately
M
Electricalwiringbox
11A
DHWpump,withbuiltincheckvalve
35
Ballvalve/non-returnvalve
2
Singlecheckvalve
13
Chargingpump
45
Flowswitch
4
Safetyvalve
10
DEN-GT
VI.JV.I2.02/LUK38016
DanfossDistrictEnergy
OperatingGuideTermixSolarA+/B+
5.4Schematicdiagram
5.4.1SchematicdiagramTermixSolarA+/B+withcirculation
DHW
BT
Supply
DCW
BT
Return
HWC
Yoursubstationmightlookdifferentthantheschematicdiagramshown.
Schematicdescriptionwithcirculation
B
Heatexchanger,DHW
2
Singlecheckvalve
13
Chargingpump
M
Electricalwiringbox
4
Safetyvalve
21
Tobeorderedseparately
1
Ballvalve
7
Thermostaticvalve
35
Ballvalve/non-returnvalve
1A
Ballvalve,DVGW
11A
DHWpump,withbuiltincheckvalve
45
Flowswitch
DHW:DomesticHotWater
DCW:
DomesticColdWater
HWC:
HotWaterCirculation
BTSupply:
Buffertanksupply
BTReturn:
Buffertankreturn
5.4.2Technicalparameters
Technicalparameters
Nominalpressure:
PN10
Max.DHsupplytemperature:
120°C
Min.DCWstaticpressure:
0.5bar
BrazedHEX(A+):
Brazingmaterial(HEX):
Copper
Heatexchangerstestpressure:30bar
GasketedHEX(B+):
Gasketmaterial(HEX):
EPDMper.
Heatexchangerstestpressure:13bar
Soundlevel:55dB
DanfossDistrictEnergy
VI.JV.I2.02/LUK38016
DEN-GT
11
OperatingGuideTermixSolarA+/B+
6.0Controls
6.1DHWtemperaturecontrol
DHWtemperaturecontrol
TherearevarioustypesofDHWtemperaturecontrolusedin
Danfosssubstations.
DHWtemperatureshouldbeadjustedto45-50°C,asthisprovides
optimalutilisationofDHwater.AtDHWtemperaturesabove55°C,
thepossibilityoflimescaledepositsincreasessignicantly.
6.1.1AVTBcontroller(20–60°)
Thetemperaturesettingisasfollows:
1=20°C
2=35°C
3=50°C
4=60°C
5=70°C
Thevaluesareintendedasaguide.
TheAVTBoperatesatitsbestatDHsupplytemperaturesofupto
90°C.
Thermostaticcontrol
DHWtemperatureisadjustedasfollows:
Toincreasetemperature,turnthehandleonthethermostatic
controllertoselectahighernumber.
Todecreasetemperature,turnthehandleonthethermostatic
controllertoselectalowernumber.
6.1.2CirculatorpumpUPM3
UPM3Pumpscanbecontrolledinconstantpressure,proportional
pressureorconstantspeedmodedenedbythemeansofasmart
userinterface.
Thevariablespeedmodulatingmodesallowthepumptomatchits
performancetothesystemrequirements,helpingtoreducenoise
whenthermostaticvalvesareclosingdown.
EnergylabellingclassA
12
DEN-GT
VI.JV.I2.02/LUK38016
DanfossDistrictEnergy
OperatingGuideTermixSolarA+/B+
6.1.3GrundfosUPM3AUTOLinstructions
Controlmode
Youcanswitchfromtheperformanceviewtothesettingsviewbypressingthepushbutton.Thesettingsviewshowswhichmode
controlsthecirculator.After2seconds,thedisplayswitchesbacktoperformanceview.
Ifyoupressthebuttonfor2to10seconds,theuserinterfaceswitchesto"settingselection"iftheuserinterfaceisunlocked.Youcan
changethesettingsastheyappear.Theselectionofthecontrolmodedependsonthesystemtypeandtheallocationofpressurelosses.
Ifyoupressthekeylockformorethan10seconds,youcantogglebetweenenabling/disablingthekeylockfunction.
Function
Recommendedfor
Green
YellowYellowYellowYellow
Proportionalpressure1
1-pipesystems
µµ
Proportionalpressure2
µµµ
Proportionalpressure3
2-pipesystems
µµµµ
Constantpressure1
Underoorheating
µµ
Constantpressure2
µµµ
Constantpressure3
µµµµ
ConstantCurve1
µµµ
ConstantCurve2
µµµµ
ConstantCurve3
µµµµµ
ConstantCurveMax.
µµµµ
Operationstatus
Function
Recommendedfor
Green
YellowYellowYellowYellow
Standby**OnlyPWMcontrolled
µ
0%P125%
µµ
25%P150%
µµµ
50%P175%
µµµµ
75%P1100%
µµµµµ
Alarmstatus
Function
Recommendedfor
RedYellowYellowYellowYellow
Blocked
µµ
Supplyvoltagelow
µµ
Electricalerror
µµ
DanfossDistrictEnergy
VI.JV.I2.02/LUK38016
DEN-GT
13
OperatingGuideTermixSolarA+/B+
6.1.4Domestichotwaterpump
Thedomestichotwaterpumpcanbeprogrammedwiththe
desiredtimeprogramme.
6.2Maintenance
Thesubstationrequireslittlemonitoring,apartfromroutine
checks.Itisrecommendedtoreadtheenergymeteratregular
intervals,andtowritedownthemeterreadings.
RegularinspectionsofthesubstationaccordingtothisInstruction
arerecommended,whichshouldinclude:
Strainers
Cleaningofstrainers.
Meters
Checkingofalloperatingparameterssuchasmeterreadings.
Temperatures
Checkingofalltemperatures,suchasDHsupplytemperatureand
DHWtemperature.
Connections
Checkingallconnectionsforleakages.
Safetyvalves
Theoperationofthesafetyvalvesshouldbecheckedbyturning
thevalveheadintheindicateddirection.
Venting
Checkingthatthesystemisthoroughlyvented.
Inspectionsshouldbecarriedoutminimumeverytwoyears.
SparepartscanbeorderedfromDanfoss.Pleaseensurethatany
enquiryincludesthesubstationserialnumber.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
14
DEN-GT
VI.JV.I2.02/LUK38016
DanfossDistrictEnergy
OperatingGuideTermixSolarA+/B+
7.0Troubleshooting
7.1Troubleshootingingeneral
Intheeventofoperatingdisturbances,thefollowingbasicfeatures
shouldbecheckedbeforecarryingoutactualtroubleshooting:
thesubstationisconnectedtoelectricity,
thestrainerontheDHsupplypipeisclean,
thesupplytemperatureoftheDHisatthenormallevel
(summer,atleast60°C-winter,atleast70°C),
thedifferentialpressureisequaltoorhigherthanthenormal
(local)differentialpressureintheDHnetworkifindoubt,ask
theDHplantsupervisor,
pressureonthesystem-checktheHEpressuregauge.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
7.2TroubleshootingDHW
ProblemPossiblecauseSolution
Strainerinsupplyorreturnlineclogged.Cleanstrainer(s).
DHWcirculationpumpoutoforderorwith
toolowsetting.
Checkcirculationpump.
Defectiveorcloggednon-returnvalve.
Replaceclean.
Noelectricity.Check.
Wrongsettingofautomaticcontrols,ifany.Toadjustanelectroniccontrollerfor
DHW,pls.noteenclosedinstructionsfor
electroniccontroller.
Scalingoftheplateheatexchanger.
Replacerinseout.
Defectivemotorizedvalve.Check(usemanualfunction)replace.
Defectivetemperaturesensors.
Checkreplace.
ToolittleornoDHW.
Defectivecontroller.
Checkreplace.
DCWisbeingmixedwiththeDHW,e.g.in
adefectivethermostaticmixingvalve.
Checkreplace. Hotwaterinsometapsbutnotinall.
Defectiveorcloggednon-returnvalveon
circulationvalve.
Replaceclean.
Taptemperaturetoohigh;DHWtapload
toohigh.
Thermostaticvalveadjustedtoatoohigh
level.
Checkset.
Scalingoftheplateheatexchanger.
Replacerinseout. Temperaturedropduringtapping.
LargerDHWowthanthesubstationhas
beendesignedfor.
ReduceDHWow.
Thermostaticcontrolvalvedoesnotclose
TemperaturedifferencebetweenDH
supplyandDHWsetpointtoolow.
Lowerthesetpointtemperatureor
increasetheDHsupplytemperature.
DanfossDistrictEnergy
VI.JV.I2.02/LUK38016
DEN-GT
15
OperatingGuideTermixSolarA+/B+
7.3Disposal
Disposal
Thisproductshouldbedismantledanditscomponents
sorted,ifpossible,invariousgroupsbeforerecycling
ordisposal.
Alwaysfollowthelocaldisposalregulations.
16
DEN-GT
VI.JV.I2.02/LUK38016
DanfossDistrictEnergy
OperatingGuideTermixSolarA+/B+
DanfossDistrictEnergy
VI.JV.I2.02/LUK38016
DEN-GT
17
OperatingGuideTermixSolarA+/B+
18
DEN-GT
VI.JV.I2.02/LUK38016
DanfossDistrictEnergy
OperatingGuideTermixSolarA+/B+
8.0Declaration
8.1Declarationofconformity
Category0withelectricalequipment
DanfossDistrictEnergy
VI.JV.I2.02/LUK38016
DEN-GT
19
OperatingGuideTermixSolarA+/B+
ProducedbyDanfossA/S©11/2016
/