Rosemount 5400 Quick start guide

Type
Quick start guide

Rosemount 5400 is a high-performance level transmitter designed for continuous level measurement in challenging applications. With its advanced technology, Rosemount 5400 offers accurate and reliable level measurement, helping you optimize your process efficiency and safety.

Key features of Rosemount 5400 include:

  • Non-contacting ultrasonic technology for accurate and reliable level measurement
  • Two-wire loop-powered design for easy installation and maintenance
  • HART® communication protocol for remote configuration and diagnostics
  • Advanced echo processing algorithms for reliable measurement in noisy environments

Rosemount 5400 is a high-performance level transmitter designed for continuous level measurement in challenging applications. With its advanced technology, Rosemount 5400 offers accurate and reliable level measurement, helping you optimize your process efficiency and safety.

Key features of Rosemount 5400 include:

  • Non-contacting ultrasonic technology for accurate and reliable level measurement
  • Two-wire loop-powered design for easy installation and maintenance
  • HART® communication protocol for remote configuration and diagnostics
  • Advanced echo processing algorithms for reliable measurement in noisy environments
Quick Start Guide
00825-0600-4026, Rev BA
December 2016
Rosemount
5400 Level Transmitter
Mounting Instructions for Parabolic Antenna
December 2016
2
Quick Start Guide
1.0 About this guide
This Quick Start Guide provides mechanical installation instructions for the
Rosemount 5402 Level Transmitter with parabolic antenna.
For information about electrical installation and configuration, refer to the
Rosemount 5400 Quick Start Guide
.
Failure to follow safe installation and service guidelines could result in death or serious injury.
Make sure the transmitter is installed by qualified personnel and in accordance with applicable code of
practice.
Use the equipment only as specified in this Quick Start Guide and the Reference Manual. Failure to do so
may impair the protection provided by the equipment.
Any substitution of non-authorized parts or repair, other than exchanging the complete transmitter head or
antenna assembly, may jeopardize safety and is prohibited.
Explosions could result in death or serious injury.
Verify that the operating environment of the transmitter is consistent with the appropriate hazardous
locations specifications.
To prevent ignition of flammable or combustible atmospheres, disconnect power before servicing.
Before connecting a Field Communicator in an explosive atmosphere, make sure the instruments in the
loop are installed in accordance with intrinsically safe or non-incendive field wiring practices.
To avoid process leaks, only use O-rings designed to seal with the corresponding flange adapter.
Do not remove the transmitter while in operation.
Electrical shock can result in death or serious injury.
Avoid contact with the leads and terminals. High voltage that may be present on leads can cause electrical
shock.
Make sure the main power to the Rosemount 5400 Level Transmitter is off and the lines to any other
external power source are disconnected or not powered while wiring the transmitter.
Ground device on non-metallic tanks (e.g. fiberglass tanks) to prevent electrostatic charge build-up.
Contents
Parabolic antenna overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3
Mount the flanged version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4
Mount the threaded version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 5
Mount the welded version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 9
Adjust the inclination of the antenna . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 15
Connect the air purging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 19
Quick Start Guide
3
December 2016
2.0 Parabolic antenna overview
Flanged version
Threaded version
Welded version
page 4
page 5
page 9
December 2016
4
Quick Start Guide
3.0 Mount the flanged version
Step 1: Mount the device on tank
Tighten the bolts and nuts with sufficient torque for the flange and gasket
choice.
Step 2: Adjust the inclination of the antenna (see page 15)
Step 3: Connect the air purging (see page 19)
Gasket
Quick Start Guide
5
December 2016
4.0 Mount the threaded version
Figure 1. Components
A.
B.
C.
D.
Antenna
Purge plug kit (optional with order)
P/N 05400-1200-0001
Threaded sleeve
M20 adapter
E.
F.
G.
Lock nut G 3½" (optional with order)
P/N 05400-1200-0002
Antenna adapter with ball joint
O-ring
2x
1x
E
1x
F
1x
G
1x
D
1x
C
1x
B
1x
A
December 2016
6
Quick Start Guide
Step 1: Remove the lock nut (if applicable)
Step 2: Mount the O-ring
Step 3: Mount the antenna adapter on flange/manhole
cover
Ensure the antenna adapter fits tightly to the flange/manhole cover.
E
F
G
Ø 3.98 ± 0.02 in.
(Ø 101 ± 0.6 mm)
OR
G 3½"
Max. 1.18 in. (30 mm)
> 0.59 in. (15 mm)
Quick Start Guide
7
December 2016
Step 4: Remove the M20 adapter
Visually inspect the O-rings for damage and dirt.
Step 5: Carefully insert the antenna
Step 6: Secure the antenna
O-rings
A
D
C
D
Torque 180 in-lb (20 Nm)
27 mm
December 2016
8
Quick Start Guide
Step 7: Tighten the set screw
Step 8: Mount the antenna assembly on tank
Tighten the bolts and nuts with sufficient torque for the flange and gasket
choice.
Step 9: Adjust the inclination of the antenna (see page 15)
Step 10: Connect the air purging (see page 19)
H2 mm
Torque 5 in-lb (0.5 Nm)
Gasket
Quick Start Guide
9
December 2016
5.0 Mount the welded version
Figure 2. Components
A.
B.
C.
D.
Antenna
Purge plug kit (optional with order)
P/N 05400-1200-0001
Threaded sleeve
M20 adapter
E.
F.
G.
H.
I.
Weld protection plate
Flange ball
Weld protection bar
O-ring
Ball joint
J.
K.
L.
Clamp flange
Washer
M8 screw
2x
E
1x
G
1x
F
1x
H
1x
J
1x
I
1x
D
1x
C
3x
K
3x
L
1x
A
1x
B
December 2016
10
Quick Start Guide
Step 1: Mount the protection plates to flange/manhole
cover
These plates protects the internal surfaces of the flange ball from dust and
sparks during welding.
Ø 3.94 ± 0.02 in.
(Ø 100 ± 0.5 mm)
E
F
G
E
Max. 1.18 in. (30 mm)
Quick Start Guide
11
December 2016
Step 2: Weld the flange ball
Step 3: Remove the protection plates
Visually inspect the internal surfaces of the flange ball for damage and dirt.
Step 4: Mount the O-ring
H
December 2016
12
Quick Start Guide
Step 5: Mount the ball joint
Insert the ball joint, place the clamp flange with the “7 Nm” marking side up,
and then gradually tighten the M8 screws.
Step 6: Remove the M20 adapter
Visually inspect the O-rings for damage and dirt.
H6 mm
Torque 65 in-lb (7 Nm)
K
L
J
I
O-rings
A
D
Quick Start Guide
13
December 2016
Step 7: Carefully insert the antenna
Step 8: Secure the antenna
C
D
Torque 180 in-lb (20 Nm)
27 mm
December 2016
14
Quick Start Guide
Step 9: Tighten the set screw
Step 10: Mount the antenna assembly on tank
Tighten the bolts and nuts with sufficient torque for the flange and gasket
choice.
Step 11: Adjust the inclination of the antenna (see page 15)
Step 12: Connect the air purging (see page 19)
H2 mm
Torque 5 in-lb (0.5 Nm)
Gasket
Quick Start Guide
15
December 2016
6.0 Adjust the inclination of the antenna
6.1 Orientation
General best practice is to initially align the parabolic antenna vertically to
the ground.
If the surface echo is weak, a small inclination of the antenna toward the
surface slope may improve the performance.
The angle of slope differs during filling and emptying, and thus the signal
strength. Therefore, monitor the entire cycle to verify optimum antenna
inclination.
90°
December 2016
16
Quick Start Guide
6.2 Procedure
Step 1: Remove the transmitter head (if applicable)
Step 2: Loosen the M8 screws until the antenna can tilt
smoothly
Step 3: Place the circular level on top of the antenna
assembly
Contents may be under pressure
Do not loosen the M8 screws while in operation.
Attempting to do so may release pressurized gases, resulting in serious injury or death.
60 mm
H6 mm
Quick Start Guide
17
December 2016
Step 4: Adjust the inclination of the antenna
Step 5: Gradually tighten the M8 screws
H6 mm
Torque 65 in-lb (7 Nm)
December 2016
18
Quick Start Guide
Step 6: Remove the circular level
Step 7: Mount the transmitter head
Torque 355 in-lb (40 Nm)
60 mm
36 mm
Quick Start Guide
19
December 2016
7.0 Connect the air purging
If air purging is not used, plug and seal the entry with the air plug kit (optional
with order) or a suitable blanking plug.
Proceed with electrical installation. For further instructions, see the Rosemount
5400 Quick Start Guide.
G3/8"
Air purging?No Yes
0.3-0.4 in. (8-10 mm)
(gasket excluded)
Torque 180 in-lb (20 Nm)
Use thread sealant or
gasket according to
your site procedures.
17 mm
B
Global Headquarters
Emerson Automation Solutions
6021 Innovation Blvd.
Shakopee, MN 55379, USA
+1 800 999 9307 or +1 952 906 8888
+1 952 949 7001
RFQ.RMD-RCC@Emerson.com
North America Regional Office
Emerson Automation Solutions
8200 Market Blvd.
Chanhassen, MN 55317, USA
+1 800 999 9307 or +1 952 906 8888
+1 952 949 7001
Latin America Regional Office
Emerson Automation Solutions
1300 Concord Terrace, Suite 400
Sunrise, FL 33323, USA
+1 954 846 5030
+1 954 846 5121
Linkedin.com/company/Emerson-Automation-Solutions
Twitter.com/Rosemount_News
Facebook.com/Rosemount
Youtube.com/user/RosemountMeasurement
Google.com/+RosemountMeasurement
Standard Terms and Conditions of Sale can be found on the Ter ms
and Conditions of Sale page.
The Emerson logo is a trademark and service mark of Emerson
Electric Co.
Rosemount and Rosemount logotype are trademarks of Emerson.
All other marks are the property of their respective owners.
© 2016 Emerson. All rights reserved.
Europe Regional Office
Emerson Automation Solutions
Neuhofstrasse 19a P.O. Box 1046
CH 6340 Baar
Switzerland
+41 (0) 41 768 6111
+41 (0) 41 768 6300
Asia Pacific Regional Office
Emerson Automation Solutions
1 Pandan Crescent
Singapore 128461
+65 6777 8211
+65 6777 0947
Enquiries@AP.Emerson.com
Middle East and Africa Regional Office
Emerson Automation Solutions
Emerson FZE P.O. Box 17033
Jebel Ali Free Zone - South 2
Dubai, United Arab Emirates
+971 4 8118100
+971 4 8865465
RFQ.RMTMEA@Emerson.com
Quick Start Guide
00825-0600-4026, Rev BA
December 2016
*00825-0600-4026*
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20

Rosemount 5400 Quick start guide

Type
Quick start guide

Rosemount 5400 is a high-performance level transmitter designed for continuous level measurement in challenging applications. With its advanced technology, Rosemount 5400 offers accurate and reliable level measurement, helping you optimize your process efficiency and safety.

Key features of Rosemount 5400 include:

  • Non-contacting ultrasonic technology for accurate and reliable level measurement
  • Two-wire loop-powered design for easy installation and maintenance
  • HART® communication protocol for remote configuration and diagnostics
  • Advanced echo processing algorithms for reliable measurement in noisy environments