Emerson Rosemount 5400 Series is designed to provide accurate and reliable level measurement in various industrial applications. Its advanced technology and features make it suitable for measuring levels of liquids, slurries, and solids in storage tanks, process vessels, and other containers. With its non-contact measurement principle and advanced signal processing algorithms, the 5400 Series delivers high accuracy and repeatability even in challenging measurement conditions. The device can be configured to meet specific application requirements, making it versatile and adaptable to different industries and processes.

Emerson Rosemount 5400 Series is designed to provide accurate and reliable level measurement in various industrial applications. Its advanced technology and features make it suitable for measuring levels of liquids, slurries, and solids in storage tanks, process vessels, and other containers. With its non-contact measurement principle and advanced signal processing algorithms, the 5400 Series delivers high accuracy and repeatability even in challenging measurement conditions. The device can be configured to meet specific application requirements, making it versatile and adaptable to different industries and processes.

Quick Start Guide
00825-0600-4026, Rev AA
March 2016
Rosemount
5400 Level Transmitter
Mounting Instructions for Parabolic Antenna
March 2016
2
Quick Start Guide
1.0 About this guide
This Quick Start Guide provides mechanical installation instructions for the
Rosemount 5402 Level Transmitter with parabolic antenna.
For information about electrical installation and configuration, refer to the
Rosemount 5400 Series Quick Start Guide (document number
00825-0100-4026).
Failure to follow safe installation and service guidelines could result in death or serious injury.
Make sure the transmitter is installed by qualified personnel and in accordance with applicable code of
practice.
Use the equipment only as specified in this Quick Start Guide and the Reference Manual. Failure to do so
may impair the protection provided by the equipment.
Any substitution of non-authorized parts or repair, other than exchanging the complete transmitter head
or antenna assembly, may jeopardize safety and is prohibited.
Explosions could result in death or serious injury.
Verify that the operating environment of the transmitter is consistent with the appropriate hazardous
locations specifications.
To prevent ignition of flammable or combustible atmospheres, disconnect power before servicing.
Before connecting a Field Communicator in an explosive atmosphere, make sure the instruments in the
loop are installed in accordance with intrinsically safe or non-incendive field wiring practices.
To avoid process leaks, only use O-rings designed to seal with the corresponding flange adapter.
Do not remove the transmitter while in operation.
Electrical shock can result in death or serious injury.
Avoid contact with the leads and terminals. High voltage that may be present on leads can cause electrical
shock.
Make sure the main power to the Rosemount 5400 Level Transmitter is off and the lines to any other
external power source are disconnected or not powered while wiring the transmitter.
Ground device on non-metallic tanks (e.g. fiberglass tanks) to prevent electrostatic charge build-up.
Contents
Parabolic antenna overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3
Mount the flanged version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4
Mount the welded version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 6
Mount the threaded version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 13
Adjust inclination of antenna . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 19
Quick Start Guide
3
March 2016
2.0 Parabolic antenna overview
Flanged version
Welded version
Threaded version
page 4-5
page 6-12
page 13-18
March 2016
4
Quick Start Guide
3.0 Mount the flanged version
Step 1: Mount antenna assembly on tank
Step 2: Adjust inclination of antenna
Refer to section “Adjust inclination of antenna” on page 19 for further
information.
Gasket
Quick Start Guide
5
March 2016
Step 3: Tighten blind plug or install air purging system
Proceed with electrical installation. For further instructions, see the Rosemount
5400 Series Quick Start Guide (document number 00825-0100-4026).
G3/8"
Air purging?No Yes
0.3-0.4 in. (8-10 mm)
(gasket excluded)
Torque 180 in-lb (20 Nm)
Use thread sealant or
gasket according to
your site procedures.
March 2016
6
Quick Start Guide
4.0 Mount the welded version
Figure 1. Components
A.
B.
C.
D.
E.
Weld protection plate
Weld protection bar
Flange ball
O-ring
Clamp flange
F.
G.
H.
I.
J.
Washer
M8 screw
Antenna
Ball joint
Threaded sleeve
K.
L.
M.
M20 adapter
G3/8" bonded seal
Blind plug
2x 1x 1x
1x
1x
1x 1x
1x
1x
3x 3x
A
B
C
D
E
F
G
I
H
1x
K
1x
J
L
M
Quick Start Guide
7
March 2016
Step 1: Mount protection plates to flange/manhole cover
These plates protects the internal surfaces of the flange ball from welding sparks.
Ø 3.94 ± 0.02 in.
(Ø 100 ± 0.5 mm)
A
C
B
A
Max. 1.18 in. (30 mm)
March 2016
8
Quick Start Guide
Step 2: Weld flange ball
Step 3: Remove protection plates
Visually inspect the internal surfaces of the flange ball for damage and dirt.
Step 4: Mount O-ring
D
Quick Start Guide
9
March 2016
Step 5: Mount ball joint
Gradually tighten the M8 nuts.
Step 6: Remove protection cap
Visually inspect the O-rings for damage and dirt.
M8
Torque 90 in-lb (10 Nm)
F
G
E
I
O-rings
H
March 2016
10
Quick Start Guide
Step 7: Carefully insert antenna
Step 8: Secure antenna
J
K
Torque 180 in-lb (20 Nm)
Quick Start Guide
11
March 2016
Step 9: Tighten set screw
Step 10: Mount antenna assembly on tank
Step 11: Adjust inclination of antenna
Refer to section “Adjust inclination of antenna” on page 19 for further
information.
M4
Torque 5 in-lb (0.5 Nm)
Gasket
March 2016
12
Quick Start Guide
Step 12: Tighten blind plug or install air purging system
Proceed with electrical installation. For further instructions, see the Rosemount
5400 Series Quick Start Guide (document number 00825-0100-4026).
G3/8"
Air purging?No Yes
0.3-0.4 in. (8-10 mm)
(gasket excluded)
Torque 180 in-lb (20 Nm)
Use thread sealant or
gasket according to
your site procedures.
L
M
Quick Start Guide
13
March 2016
5.0 Mount the threaded version
Figure 2. Components
A.
B.
C.
Lock nut
Antenna adapter with ball joint
O-ring
D.
E.
F.
Antenna
Threaded sleeve
M20 adapter
G.
H.
G3/8" bonded seal
Blind plug
2x
1x 1x
1x
1x
1x 1x
A
B
C
D
1x
F
1x
E
G
H
March 2016
14
Quick Start Guide
Step 1: Remove lock nut
Step 2: Mount O-ring
A
B
C
Quick Start Guide
15
March 2016
Step 3: Mount antenna adapter on flange/manhole cover
Make sure the antenna adapter fits tightly to the flange/manhole cover.
Step 4: Remove protection cap
Visually inspect the O-rings for damage and dirt.
Ø 3.98 ± 0.02 in.
(Ø 101 ± 0.6 mm)
OR
G3½"
Max. 1.18 in. (30 mm)
> 0.59 in. (15 mm)
O-rings
D
March 2016
16
Quick Start Guide
Step 5: Carefully insert antenna
Step 6: Secure antenna
E
F
Torque 180 in-lb (20 Nm)
Quick Start Guide
17
March 2016
Step 7: Tighten set screw
Step 8: Mount antenna assembly on tank
M4
Torque 5 in-lb (0.5 Nm)
Gasket
March 2016
18
Quick Start Guide
Step 9: Adjust inclination of antenna
Refer to section “Adjust inclination of antenna” on page 19 for further
information.
Step 10: Tighten blind plug or install air purging system
Proceed with electrical installation. For further instructions, see the Rosemount
5400 Series Quick Start Guide (document number 00825-0100-4026).
G3/8"
Air purging?No Yes
0.3-0.4 in. (8-10 mm)
(gasket excluded)
Torque 180 in-lb (20 Nm)
Use thread sealant or
gasket according to
your site procedures.
G
H
Quick Start Guide
19
March 2016
6.0 Adjust inclination of antenna
6.1 Orientation
General best practice is to initially align the parabolic antenna vertically to the
ground.
If the surface echo is weak, a small inclination of the antenna toward the
surface slope may improve the performance.
The angle of slope differs during filling and emptying, and thus the signal
strength. Therefore, monitor the entire cycle to verify optimum antenna
inclination.
90°
March 2016
20
Quick Start Guide
6.2 Procedure
Step 1: Remove transmitter housing (if applicable)
Step 2: Loosen M8 screws until antenna can tilt smoothly
Contents may be under pressure
Do not loosen the M8 screws while in operation.
Attempting to do so may release pressurized gases, resulting in serious injury or death.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24

Emerson Rosemount 5400 Series Quick start guide

Type
Quick start guide

Emerson Rosemount 5400 Series is designed to provide accurate and reliable level measurement in various industrial applications. Its advanced technology and features make it suitable for measuring levels of liquids, slurries, and solids in storage tanks, process vessels, and other containers. With its non-contact measurement principle and advanced signal processing algorithms, the 5400 Series delivers high accuracy and repeatability even in challenging measurement conditions. The device can be configured to meet specific application requirements, making it versatile and adaptable to different industries and processes.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI