Trend NBOX(B)/CNC2 Installation Instructions Manual

Type
Installation Instructions Manual
NBOX(B)/CNC2 Communications Node Controller Installation Instructions TG200265 Issue 2 , 20-Sep-2012 1
Installation Instructions
NBOX(B)/CNC2
Communications Node Controller
Important: Retain these instructions
These instructions shall be used by trained service personnel only
If the equipment is used in a manner not specied by these instructions, the protection provided by the equipment may be impaired.
1
Dimensions
3 INSTALLATION
3.1 Installation - Mounting
1 UNPACKING
2 STORING
It is recommended that the installation should comply with the local electrical safety installation practices (e.g. HSE
Memorandum of Guidance on Electricity at Work Regulations 1989, USA National Electric Code).
CONTENTS
1 Unpacking .....................................................................1
2 Storing ...........................................................................1
3 Installation .....................................................................1
3.1 Installation - Mounting ...................................................1
3.2 Installation - Conguring ...............................................6
4 Disposal .........................................................................8
HO
2
+50 °C
0
-10 °C
95 %RH
Installation
Instructions,
TG200265
TX
RX
OK
DTRB
DTRA
CTSBCTSA
70 mm230 mm
181 mm
TX
RX
OK
DTRB
DTRA
CTSBCTSA
50 mm
100 mm
../230 only
../24 only
2 NBOX(B)/CNC2 Communications Node Controller Installation Instructions TG200265 Issue 2 , 20-Sep-2012
NBOX(B)/CNC2 Installation Instructions
3
Mount in Enclosure
2
Mounting Requirements
3.1 Installation - Mounting (continued)

 



 


 




 




if using ENCLS/MBOX
HO
2
0 °C
+45 °C
0 %RH
95 %RH
Protection : IP30
Operating Altitude <2000 m (6562’)
Must be installed in an
enclosure rated to at least
IP20 or equivalent
For 24VAC only unit is UL
rated as ‘UL916, accessory
to open energy management
equipment
ENCLS/MBOX/IQ22x
Installation Instructions
TG200203.
xing detaiils for mounting in a third party enclosure
NBOX(B)/CNC2 Communications Node Controller Installation Instructions TG200265 Issue 2 , 20-Sep-2012 3
Installation Instructions NBOX(B)/CNC2
4
Connect Power
3.1 Installation - Mounting (continued)
DO NOT
SWITCH ON
Shrouded plug kit
E N L
~
E N L
/230 version (shrouded plug kit must be used)
Terminal size 0.5 to 2.5
mm
2
(20 to 14 AWG)
/24 version
NBOX/CNC2/230 Consumption < = 7.5 VA
The 230V supply must include a dedicated 5A fuse complying
with BS1362 and a suitably rated switch in close proximity and
be clearly marked as the disconnecting device for the unit. A
5A circuit breaker with high breaking capacity may be used
as an alternative .
Mat-N-LoK
to
terminals
adaptor
(supplied)
This unit is protected to safety class 2.
The earth on this unit is NOT a protective
earth, but it is essential that an earth is tted
for functional reasons.
383501JE
V42
24 Vdc: +24V 0v
24 Vac: 24 Vac 0V
Earth
(ground)
Note that for the UL 24 Vac the
input power connections must
be made using 18 AWG or
larger wire rated at least 9C.
The 24V supply must include a suitably rated switch in close
proximity and be clearly marked as the disconnecting device
for the unit
NBOX/CNC2/24 Consumption < = 7.5 VA
TX
RX
OK
DTRB
DTRA
CTSBCTSA
Earth/ground
the bus bar
TX
RX
OK
DTRB
DTRA
CTSBCTSA
Earth/ground
the bus bar
a b c d e
4 NBOX(B)/CNC2 Communications Node Controller Installation Instructions TG200265 Issue 2 , 20-Sep-2012
NBOX(B)/CNC2 Installation Instructions
5
Connect Trend Lan (Lan A)
6
Connect to Local Device
 




earth bus
T
T
R
R
X
T
T
R
R
T-
T+
R-
R+
LAN A
TX
RX
OK
DTRB
DTRA
CTSBCTSA
earth bus
T
T
R
R
T-
X
T+
R-
R+
LAN A
2 wire
Network Engineering Manual, 92-1735.
additional terminals
Polarity independent
4 wire




25 Way D type, Male
9 Way D type, Female
CABLE/58-0750
PC’s COM port
cable not supplied with unit
e.g PC
(RS232 Port)
terminal size 0.5 to 2.5 mm
2
additional terminals
Connect Auxiliary Supply Output
7
3.1 Installation - Mounting (continued)
Cable 1k2 baud 4k8 baud 9k6 baud 19k2 baud No. of Wires
Belden 9182 1000 m (1090 yds) 1000 m (1090 yds) 1000 m (1090 yds) 700 m (765 yds) 2
Belden 9207 1000 m (1090 yds) 1000 m (1090 yds) 1000 m (1090 yds) 500 m (545 yds) 2
Trend TP/1/1/22/HF/200
IQ system
TP/1/1/22/HF/200
(Belden 8761)
1000 m (1090 yds) 1000 m (1090 yds)
700 m
(765 yds)
350 m (380 yds) 2
Trend TP/2/2/22/HF/200 IIIIII
IQ system
TP/2/2/22/HF/200
(Belden 8723)
1000 m (1090 yds) 1000 m (1090 yds)
500 m
(545 yds)
250 m (270 yds) 4
TX
RX
OK
DTRB
DTRA
CTSBCTSA
24 V
CNC2
24 V
I max = 150 mA
AUX
terminal size 0.5 to 2.5 mm
2
NBOX(B)/CNC2 Communications Node Controller Installation Instructions TG200265 Issue 2 , 20-Sep-2012 5
Installation Instructions NBOX(B)/CNC2
2
Open Enclosure
1
Switch Off
9
Close Enclosure
3.1 Installation - Mounting (continued)
O
I
if tted in ENCLS/MBOX
Other enclosure
3
Open Flap
3.2 Installation-Conguration
if tted in ENCLS/MBOX
Other enclosure
8
Close Flap
6 NBOX(B)/CNC2 Communications Node Controller Installation Instructions TG200265 Issue 2 , 20-Sep-2012
NBOX(B)/CNC2 Installation Instructions
4
Set the Network Address
5
Set Network Baud Rate
6
Set RS232 Port to Local Device Baud Rate
Baud B Baud A
Baud B Baud A
TX
RX
OK
DTRB
DTRA
CTSBCTSA
Network Baud Rate = R1
move link to
set baud rate
e.g 9k6
Baud B Baud A
Baud B Baud A
TX
RX
OK
DTRB
DTRA
CTSBCTSA
RS232 Port Baud Rate = R2
move link to
set baud rate
e.g 19k2
(Baud B)
= R2
CNC2
= R2
(Baud A)
TX
RX
OK
DTRB
DTRA
CTSBCTSA
Address = D
= D
NBOX(B)/CNC2
/
= D
/
= D
/
= D
(Lan A)




NOT SET
SET
e.g.
address
Address = 2+16+64= 82
1, 4 to 9, 11 to 114
0, 2, 3, 10 or >119
3.2 Installation-Conguration (continued)
= R1
= R1
= R1
= R1
NBOX(B)/CNC2 Communications Node Controller Installation Instructions TG200265 Issue 2 , 20-Sep-2012 7
Installation Instructions NBOX(B)/CNC2
9
closeap
10
Check Node Controller
Switch On
7
Set Battery Links On
if NBOXB
8
11
Check Network
(Lan A)
TX
RX
OK
DTRB
DTRA
CTSBCTSA
Check supply
CNC2 Faulty
b
(watchdog)
a (power)
(green)
(red)
TX
RX
OK
DTRB
DTRA
CTSBCTSA


ON
OFF
ON
OFF
Note: Batteries must be charged for 16
hours before they will support unit during
mains failure
NBOX(B)/CNC2
?
NBOX(B)/CNC2
?
   
 
   
 
TX
RX
OK
DTRB
DTRA
CTSBCTSA
b TX
a RX
c OK
CNC2 faulty
Check network cabling
for short circuits with a
multimeter (NOT Megger)
Network Address invalid
0, 2, 3 or >119
OK
OK
NBOX(B)/CNC2
Check baud rate
Power up other nodes until
faulty node is found (OK
). Correct fault.
(yellow)
(yellow)
(green)
3.2 Installation-Conguration (continued)
8 NBOX(B)/CNC2 Communications Node Controller Installation Instructions TG200265 Issue 2 , 20-Sep-2012
NBOX(B)/CNC2 Installation Instructions
Please send any comments about this or any other Trend technical publication to [email protected]
© 2012 Honeywell Technologies Sàrl, ECC Division. All rights reserved. Manufactured for and on behalf of the Environmental and Combustion Controls
Division of Honeywell Technologies Sàrl, Z.A. La Pièce, 16, 1180 Rolle, Switzerland by its Authorized Representative, Trend Control Systems Limited.
Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content hereof without obligation
to notify any person of such revisions or changes.
Trend Control Systems Limited
Albery House, Springeld Road, Horsham, West Sussex, RH12 2PQ, UK. Tel:+44 (0)1403 211888 Fax:+44 (0)1403 241608 www.trendcontrols.com
Trend Control System USA
6670 185th Avenue NE, Redmond, Washington 98052, USA. Tel:(425) 869-3900 Fax:(425) 869-8445 www.trend-americas.com
12
Check System
13
Close MBOX
WEEE Directive:
At the end of their useful life the packaging,
product, and battery (if tted) should be disposed
of by a suitable recycling centre.
Do not dispose of with normal household waste.
Do not burn.
4 DISPOSAL
CNC2
IQ
T=X °C
temperature ?
T=X °C
Lan A
if tted in ENCLS/MBOX/IQ22x
3.2 Installation-Conguration (continued)
Other enclosure
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8