Eaton 9PX, HotSwap MBP Series, MBP11K208, MBP6K208 User manual

  • Hello! I am an AI chatbot trained to assist you with the Eaton 9PX User manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
ENGLISH
HotSwap MBP
Maintenance Bypass
MBP6K208
MBP11K208
Installation
and user manual
Copyright © 2012 EATON
All rights reserved.
Service and support:
Call your local service representative
SK-90610-Y4_EN
Page 2
SK-90610-Y4_EN
Special symbols
The following are examples of symbols used on the Hotswap MBP to alert you to important
information:
RISK OF ELECTRIC SHOCK - Observe the warning associated with the risk of electric shock symbol.
Important instructions that must always be followed.
This symbol indicates that you should not discard waste electrical or electronic equipment (WEEE)
in the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center.
Information, advice, help.
Refer to the user manual of UPS.
SAVE THESE INSTRUCTIONS. This manual contains important instructions
that should be followed during installation and maintenance of the MBP and UPS.
The Hotswap MBP models that are covered in this manual are intended for installation
in an environment within 0 to 40°C, free of conductive contaminant.
This equipment has been tested and found to comply with Class A UPS,pursuant to Part 15 of the FCC
Rules. These limits are designed to provide reasonable protection against harmful interference when the
equipment is operated in a commercial environment. This equipment generates, uses, and can radiate
radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause
harmful interference to radio communications. Operation of this equipment in a residential area is likely
to cause harmful interference in which case the user will be required to correct the interference at his own
expense.
Certication standards (in use with UPS)
p Safety: IEC/EN 62040-1 / Ed.1: 2008.
UL 1778 4
th
edition
p EMC: IEC 62040-2 / Ed.2: 2005
EN 62040-2 / Ed.2: 2006
FCC part 15 Class A.
p Performance: IEC/EN 62040-3 / Ed.2.0: 2011.
p IEC 61000-4-2 (ESD): level 3.
p IEC 61000-4-3 (Radiated eld): level 3.
p IEC 61000-4-4 (EFT): level 4.
p IEC 61000-4-5 (Fast transients): level 4.
p IEC 61000-4-6 (Electromagnetic eld): level 3.
p IEC 61000-4-8 (Conducted magnetic eld): level 4.
SAFETY INSTRUCTIONS
Page 3
SK-90610-Y4_EN
ENGLISH
Safety of persons
p The system has its own power source when connected to the UPS (UPS battery). Consequently,
the power outlets may be energized even if the system is disconnected from the AC power source.
Dangerous voltage levels are present within the system.
It should be opened exclusively by qualied service personnel.
p The product must be properly grounded, always connect the earth wire rst
Product safety
p The MBP connection instructions and operation described in the manual must be followed
in the indicated order. Disconnection and overcurrent protection devices shall be provided by others
for AC in/out circuits.
p CAUTION - To reduce the risk of re, the unit connects only to a circuit provided with branch circuit
overcurrent protection (please refer to the UPS User Manual for current rating), in accordance with
the National Electric Code, ANSI/NFPA 70 (US installations only).
The upstream circuit breaker must be easily accessible.
The unit can be disconnected from AC power source by opening this circuit breaker, and if still
connected to UPS, by previously shutting down the UPS (refer to the UPS User Manual)
p Check that the indications on the rating plate correspond to your AC powered system and to the
actual electrical consumption of all the equipment to be connected to the system.
p Never install the system near liquids or in an excessively damp environment.
p Never let a foreign body penetrate inside the system.
p Never expose the system to direct sunlight or source of heat.
p If the system must be stored prior to installation, storage must be in a dry place.
p The admissible storage temperature range is -15ºC to +60ºC.
Special precautions
p The Hotswap MBP is designed to work with approved EATON UPS (contact your Eaton reseller for
more information)
p All repairs and service should be performed by AUTHORIZED SERVICE PERSONNEL ONLY.
There are NO USER SERVICEABLE PARTS inside the MBP.
SAFETY INSTRUCTIONS
Page 4
SK-90610-Y4_EN
1. Introduction ....................................................................................... 5
1.1 Environmental protection ...................................................................................................5
2. Presentation ...................................................................................... 6
2.1 Standard positions .............................................................................................................6
2.2 Description / Panels ........................................................................................................... 8
3. Installation ........................................................................................ 9
3.1 Inspecting the equipment ..................................................................................................9
3.2 Unpacking the MBP ...........................................................................................................9
3.3 Checking the accessory kit ................................................................................................ 9
3.4 Mechanical Mounting ...................................................................................................... 10
3.5 Installation requirements ................................................................................................. 10
4. Power cables connection ................................................................11
4.1 MBP6K208 ...................................................................................................................... 11
4.2 MBP11K208 ..................................................................................................................... 12
5. Operations ....................................................................................... 14
5.1 UPS start-up with HotSwap MBP .................................................................................... 14
5.2 UPS replacement with HotSwap MBP ............................................................................ 15
5.3 UPS maintenance with HotSwap MBP ........................................................................... 17
6. Specifications .................................................................................. 18
Contents
Page 5
SK-90610-Y4_EN
ENGLISH
1. Introduction
Thank you for selecting an EATON product to protect your electrical equipment.
The HotSwap MBP range has been designed with the utmost care.
We recommend that you take the time to read this manual to take full advantage of the many features
of your MBP (Maintenance Bypass).
Before installing your HotSwap MBP with your UPS, please read rst the safety instructions.
Then follow the indications in this manual, which completes the UPS Installation and User Manual.
To discover the entire range of EATON products, we invite you to visit our web site at www.eaton.com/
powerquality or contact your EATON representative.
1.1 Environmental protection
EATON has implemented an environmental-protection policy.
Products are developed according to an eco-design approach.
Substances
This product does not contain CFCs, HCFCs or asbestos.
Packing
To improve waste treatment and facilitate recycling, separate the various packing components.
p The cardboard we use comprises over 50% of recycled cardboard.
p Sacks and bags are made of polyethylene.
p Packing materials are recyclable and bear the appropriate identication symbol
01
PET
Materials Abbreviations
Number in
01
PET
the symbols
Polyethylene terephthalat PET 01
High-density polyethylene HDPE 02
Polyvinyl chloride PVC 03
Low-density polyethylene LDPE 04
Polypropylene PP 05
Polystyrene PS 06
Follow all local regulations for the disposal of packing materials.
End of life
EATON will process products at the end of their service life in compliance with local regulations. EATON
works with companies in charge of collecting and eliminating our products at the end of their service life.
Product
The product is made up of recyclable materials.
Dismantling and destruction must take place in compliance with all local regulations concerning waste.
At the end of its service life, the product must be transported to a processing center for electrical and
electronic waste.
Page 6
SK-90610-Y4_EN
2. Presentation
The Eaton® HotSwap MBP module makes it possible to service or even replace the UPS without affecting
the connected loads (HotSwap function).
You can safely eliminate the effects of UPS maintenance and guard the integrity of your equipment.
Providing outstanding reliability, the Eaton HotSwap MBP unique benets include:
p Easy and fast connection to UPS due to Input/Output and signal “all in one” patented connector
(Hotswap MBP 5/6kVA range)
p “make before break” feature to allow full servicing (electrical power continuity) when switching from
UPS position to Bypass (and vice versa)
p Communication feature with UPS*: detection of MBP connection and switch position (Normal or Bypass)
(* works only with some approved EATON UPS - contact your Eaton reseller for more information)
p Load connection by both terminal blocks and NEMA outlets (30 A L6-30R)
p Adjustable 19’’ Rack kit and multiple positions Tower installation kit provided
p Backed by worldwide agency approvals.
2.1 Standard positions
MBP6K208
Tower installation
Rack installation Wall mounting
Page 7
SK-90610-Y4_EN
ENGLISH
2. Presentation
MBP11K208
Tower installation
Rack installation Wall mounting
Description Weight
(lb/kg)
Dimensions (inch/mm)
D x W x H
MBP6K208 5.5 / 2.5 4.3 x 7.0 x 5.1 / 110 x 177 x 130
MBP11K208 13.7 / 6.2 8.7 x 13.2 x 5.1 / 220 x 336 x 130
D
W
H
D
W
H
Page 8
SK-90610-Y4_EN
2. Presentation
2.2 Description / Panels
The HotSwap MBP has a manual Bypass rotary switch with two positions:
p UPS
the load is supplied by the UPS
p Bypass
the load is supplied directly by the AC power source
2 lights indicate the Hotswap MBP power status:
p "UPS supply" green light: when active, the UPS output is available, the Bypass switch can be safely
turned to UPS position
p "Bypass mode" red light: when active, indicates that the Hotswap MBP is on "Bypass mode" (Bypass
switch turned to Bypass position)
Normal AC source switch
Allow to safely switch off the AC source of the UPS, for UPS maintenance / replacing
MBP status detection:
A signal cable, with RJ11 connector to plug to the UPS, allows the communication to the UPS to manage
the MBP status, and the indication on UPS display panel of both following status:
p MBP connection to UPS
p Bypass switch position
Check the UPS user manual to check the compatibility of this feature, or contact Eaton reseller for more
information
MBP6K208
5 34
167 2
MBP11K208
6 1 4 3
298 57
(1) Input/Output terminal blocks
(2) Input/Output terminal blocks for
connection to the UPS
(3) Normal AC source switch
(4) Signal cable for MBP detection to
the UPS
(5) Manual Bypass switch
(6) (3) 30A outlets
(7) 30A circuit breaker
(8) UPS supply green light
(9) "Bypass" mode red light
(1) Input/Output terminal blocks
(2) Normal AC source switch
(3) Input/Output/MBP-Detection
connector to the UPS
(4) Manual Bypass switch
(5) (2) 30A outlets
(6) UPS supply green light
(7) "Bypass" mode red light
Page 9
SK-90610-Y4_EN
ENGLISH
3. Installation
3.1 Inspecting the equipment
If any equipment has been damaged during shipment, keep the shipping cartons and packing materials
for the carrier or place of purchase and le a claim for shipping damage. If you discover damage after
acceptance, le a claim for concealed damage.
To le a claim for shipping damage or concealed damage:
1) File with the carrier within 15 days of receipt of the equipment;
2) Send a copy of the damage claim within 15 days to your service representative.
3.2 Unpacking the MBP
Unpack the equipment and remove all the packing materials and shipping carton.
Discard or recycle the packaging in a responsible manner, or store it for future use.
Place the cabinet in a protected area that has adequate airow and is free of humidity, ammable gas,
and corrosion.
Packing materials must be disposed of in compliance with all local regulations concerning waste.
Recycling symbols are printed on the packing materials to facilitate sorting.
3.3 Checking the accessory kit
p Verify that the following additional items are included with the MBP:
MBP6K208
1
2
5
3
6
4
(1) Input/Output UPS cord set
(2) (2) cable glands
(3) Rack kit for 19-inch enclosures
(4) Fixation kit for Rack mounting
(including square nuts ans
screws)
(5) Tower and wall mouting kit
(including 2 ears and screws)
(6) Installation and user manual
MBP11K208
1
2
3
4
6
9
8
7
5
(1) MBP I/O cover
(2) MBP I/O "UPS connection" cover
(3) (2) conduits with internal wires
for UPS Input/Output connection
(4) (4) conduit fittings
(5) Fixation kit for MBP I/O covers
(including screws)
(6) Rack kit for 19-inch enclosures
(7) Fixation kit for Rack mounting
(including square nuts and
screws)
(8) Tower and wall mounting kit
(including 2 ears and screws)
(9) Installation and User manual
Page 10
SK-90610-Y4_EN
3.4 Mechanical Mounting
p Mount the MBP (on the UPS, on the EBM, in the rack or on the wall), see 2.1.
3.5 Installation requirements
Recommended protective devices and cable cross-sections
1. Recommended upstream protection
Refer to the UPS User Manual for circuit breaker current rating.
The circuit breaker has to be installed upstream the MBP Normal AC source.
2. Recommended cable cross-sections
3. Installation
Terminal
position
Wire
function
Terminal wire
size rating
Minimum input wire
size rating
Tightening
torque
MBP6K208
L1 Phase
0.5-10 mm
2
(20-8 AWG)
6 mm
2
(10 AWG) 105°C
10 mm
2
(8 AWG) 75°C
10 lb in
L2 Phase
Ground
MBP11K208
with
8kVA UPS
L1 Phase
4-25 mm
2
(12-4 AWG)
10 mm
2
(8 AWG) 105°C
16 mm
2
(6 AWG) 75°C
18 lb in
L2 Phase
Ground
MBP11K208
with
11kVA UPS
L1 Phase
4-25 mm
2
(12-4 AWG)
16 mm
2
(6 AWG) 90°C
25 mm
2
(4 AWG) 75°C
18 lb in
L2 Phase
Ground
Copper wire, solid or stranded.
Page 11
SK-90610-Y4_EN
ENGLISH
4. Power cables connection
This type of connection must be carried out by qualied electrical personnel.
Before carrying out any connection, check that the upstream protection device (Normal AC source)
is open "O" (Off).
Before proceeding to connect the HotSwap MBP to the UPS, make sure the UPS has been properly shut
down (refer to the UPS user manual).
Always connect the ground wire first.
4.1 MBP6K208
1. Remove the L6-30P input power cable from the UPS I/O terminal blocks – refer to the UPS user manual for
UPS I/O terminal blocks cover access.
2. Connect the 2 power cables of I/O cord Set (1) to the UPS I/O terminal blocks, following color coding on
the cables and the UPS I/O cover (blue for UPS Input / red for UPS Output) – refer to the UPS user manual
to check the UPS terminal blocks connection.
3. Connect the MBP detection cable from the I/O cord Set (1) to the specic UPS connector (MBP detect,
refer to UPS User Manual).
Only with compatible EATON UPS, contact your Eaton reseller for more information.
4. Slide the MBP I/O cover (2) after removing the 4 screws, to access to MBP terminal blocks.
5. Punch the knockouts and insert the provided
cable glands inside.
6. Insert the L6-30P input power cable through the
cable gland.
7. Connect the wires to the Normal AC source (Input)
terminal blocks.
8. Insert the Output cable through the cable gland.
9. Connect the wires to the Output terminal blocks.
10. Tighten the cable glands.
11. Slide back and secure the MBP I/O cover (2) with the 4 screws.
12. Connect the I/O cord Set (1) connector to the MBP, and secure it by xing the 2 locking screws.
ion
1
2
Utility
Power
Load
to UPS output
RJ11 MBP detection
to UPS Normal
AC Source
OUTPUT
L1 L2 t
INPUT
L1 L2 t
2
OUTPUT
L1 L2 t
INPUT
L1 L2 t
Output cable Normal AC Source
cable
2
1
1
Page 12
SK-90610-Y4_EN
4. Power cables connection
4.2 MBP11K208
1. Remove the top cover (5) of the MBP I/O "UPS connection" cover (2) after removing the 3 screws.
2. Punch the knockouts of the MBP I/O UPS connection cover (2) and insert 2 provided conduit ttings
inside.
1
1
3. Insert the provided conduit with blue color coding (3), through the "TO UPS NORMAL AC SOURCE"
conduit tting
take care to leave the conduit end with blue label on opposite side (for connection to UPS).
4. Connect the 3 wires of this blue color conduit (3) to the "TO UPS NORMAL AC SOURCE" MBP terminal
blocks.
5. Insert the provided conduit with red color coding (4), through the "FROM UPS OUTPUT" conduit tting
take care to leave the conduit end with red label on opposite side (for connection to UPS).
6. Connect the 3 wires of this red color conduit (4) to the "FROM UPS OUTPUT" MBP terminal blocks.
7. Put back the MBP I/O "UPS connection" cover (2) and secure it with 4 screws on the MBP casing.
8. Put back the top cover (5) of the MBP I/O "UPS connection" cover (2) and secure it with 3 screws.
9. Remove the I/O terminal blocks cover of the UPS - refer to the UPS user manual
10. Punch the Input and Output knockouts of the UPS I/O TB cover and insert 2 provided conduit ttings
inside.
11. Insert the conduits (3) and (4) through the previously mounted conduit ttings of the UPS I/O TB cover,
following color coding on the conduits and the UPS I/O TB cover (blue for UPS Input / red for UPS
Output) – also do not remove the UPS Input Bypass jumper inside the UPS I/O TB cover - refer to the UPS
User Manual
12. Connect the wires of the conduit with blue color coding (3) to the "NORMAL AC SOURCE" terminal
blocks of UPS, and the wires of the conduit with red color coding (4) to the "OUTPUT" terminal blocks of
UPS - refer to the UPS User Manual to check the UPS terminal blocks connection
13. Connect the MBP detection cable (6) to the specific UPS connector (MBP detect, refer to the UPS User
Manual).
Only with compatible EATON UPS, contact your Eaton reseller for more information.
14. Put back and secure the I/O terminal blocks cover of the UPS - refer to the UPS user manual.
15. Remove the top cover (5) of the MBP I/O cover (1) after removing the 3 screws.
2
6
4
3
5
to UPS output
to UPS
Normal
AC Source
Page 13
SK-90610-Y4_EN
ENGLISH
4. Power cables connection
16. Punch the knockouts of MBP I/O cover (1) and insert cable glands of UPS (or conduit ttings) inside.
1
1
17. Insert the Normal AC source cable through the cable gland (or a conduit through the conduit tting).
18. Connect the wires to the Normal AC source (Input) terminal blocks of MBP.
19. Insert the Output cable through the cable gland (or a conduit through the conduit tting).
20. Connect the wires to the Output terminal blocks of MBP.
21. Put back the MBP I/O cover (1) and secure it with 4 screws on the MBP casing.
22. Put back the top cover (5) of the MBP I/O cover (1) and secure it with 3 screws.
23. Tighten the cable glands (if used instead of conduit ttings).
6
4
3
5
1
2
RJ11 MBP
detection
Normale AC Source
conduit
Utility Power Output conduitLoad
Page 14
SK-90610-Y4_EN
5. Operations
UPSBYPASS
UPSBYPASS
5.1 UPS start-up with HotSwap MBP
Verify that the total equipment ratings do not exceed the UPS capacity to prevent an overload alarm.
1. Check that the UPS is correctly connected to the HotSwap MBP (see previous chapter 4)
If the UPS if equipped with outlets, those outlets can no longer be used (loads can only be connected to the
MBP outlets or the MBP Output terminal blocks).
2. Verify that the MBP terminal blocks are connected to the AC source.
3. Check that the MBP manual Bypass switch is to the "Bypass" position.
4. Set the upstream circuit breaker (not provided) to the "I" position (On) to switch On the utility power.
5. Verify that the "Bypass mode" red light of the MBP goes On, indicating that the load is now powered by
the AC source.
6. Set the Normal AC source switch of the MBP to the "I" position.
7. Verify that the UPS is correctly powered (UPS display panel illuminates).
8. Press the UPS "ON" button to start the UPS.
9. Put the UPS in "internal Bypass mode" (refer to the UPS User Manual).
10. Verify that the UPS is on Bypass mode by checking UPS display panel (refer to the UPS user manual).
11. Verify that the "UPS mode" green light of the MBP goes On, indicating that the UPS output power is
available on the MBP.
Important: do not continue to next step if the "UPS mode" green light of the MBP is still Off
(the load will be lost).
12. Set the MBP manual Bypass switch to the "UPS" position: the "Bypass mode" red light of the MBP goes
Off, indicating that the load is now powered by the UPS.
13. Put the UPS in "normal mode" (refer to the UPS User Manual).
14. Check that the UPS is in Online mode by checking UPS display panel (refer to the UPS user manual)
the load is now protected by the UPS.
Page 15
SK-90610-Y4_EN
ENGLISH
5. Operations
5.2 UPS replacement with HotSwap MBP
UPS Removing (please follow the MANDATORY step below):
MBP6K208:
1. Put the UPS in “internal Bypass mode (refer to the UPS user manual)
2. Verify that the UPS is on Bypass mode by checking UPS display panel (refer to the UPS user manual)
3. Set the MBP manual Bypass switch to “Bypass” position. The “Bypass mode” red light of the MBP goes
On, indicating that the load is supplied directly by AC source
4. Switch the Normal AC source switch of the MBP to the "0" position and wait 30 seconds
5. UPS stops, the UPS can now be disconnected, as described below:
p First disconnect the I/O cord Set (1) from the MBP, after removing the 2 screws.
1
p After opening the UPS I/O terminal blocks cover, check if hazardous voltage is no longer present on UPS
terminal blocks by using an electrical safety tester.
p Disconnect the 2 power cables, and the MBP detection cable (following UPS versions), of the MBP I/O
cord Set (1).
p Replace the UPS.
Hazardous voltage and lost load risk: do not manipulate the MBP manual Bypass switch without UPS
connected via the I/O cord Set (1).
UPSBYPASS
Page 16
SK-90610-Y4_EN
5. Operations
UPSBYPASS
MBP11K208:
1. Put the UPS in “internal Bypass mode (refer to the UPS user manual)
2. Verify that the UPS is on Bypass mode by checking UPS display panel (refer to the UPS user manual)
3. Set the MBP manual Bypass switch to "Bypass" position. The "Bypass mode" red light of the MBP goes
On, indicating that the load is supplied directly by AC source
4. Switch the Normal AC source switch of the MBP to the "0" position and wait 30 seconds
5. UPS stops, the UPS can now be disconnected, as described below:
p First lock the Normal AC source switch (3) of the MBP to the "0" position (the switch protection frame is
able to t a cable tie or a metallic locker).
3
p After opening the I/O terminal blocks cover of UPS, check if hazardous voltage is no longer present on
UPS terminal blocks by using an electrical safety tester
p Disconnect the MBP conduits, and the MBP detection cable (following UPS versions)
p On both MBP conduits just disconnected from the UPS, link the internal wires together (line 1 and line 2
wires linked to ground wire)
p Replace the UPS
Hazardous voltage and lost load risk: do not manipulate the MBP manual Bypass switch without UPS
connected to the MBP power conduits
.
Page 17
SK-90610-Y4_EN
ENGLISH
5. Operations
UPSBYPASS
UPSBYPASS
UPSBYPASS
Return to normal operation:
1. Check that the new UPS is correctly connected to the MBP, as described below:
MBP6K208:
p After opening the UPS I/O terminal blocks cover, connect to UPS the 2 power cables, and the MBP
detection cable (following UPS versions), of the MBP I/O cord Set (1)– see 4.1 for more details
p Connect the I/O cord Set (1) connector to the MBP, and secure it by xing the 2 locking screws
MBP11K208:
p First check that the Normal AC source switch (3) of the MBP is still locked to the "0" position
p Remove the previously installed safety wires links on both MBP conduits
p After opening the UPS I/O terminal blocks cover, connect to UPS the MBP conduits, and the MBP
detection cable (following UPS versions) – see 4.2 for more details
p Unlock the Normal AC source switch (3) of the MBP
2. Set the Normal AC source switch of the MBP to the "I" position.
3. Verify that the UPS is correctly powered (UPS display panel illuminates)
4. Press the UPS "ON" button to start the UPS
5. Put the UPS in “internal Bypass mode (refer to the UPS User Manual)
6. Verify that the UPS is on Bypass mode by checking UPS display panel (refer to the UPS user manual)
7. Verify that the "UPS mode" green light of the MBP goes On, indicating that the UPS output power is
available on the MBP.
Important: do not continue to next step if the "UPS mode" green light of the MBP is still Off
(the load will be lost)
8. Set the MBP manual Bypass switch to the "UPS" position: the "Bypass mode" red light of the MBP goes
Off, indicating that the load is now powered by the UPS
9. Put the UPS in “normal mode (refer to the UPS User Manual)
10. Check that the UPS is in Online mode by checking UPS display panel (refer to the UPS user manual)
the load is now protected by the UPS
5.3 UPS maintenance with HotSwap MBP
Go to maintenance Bypass operation (please follow the MANDATORY steps below):
1. Put the UPS in "internal Bypass mode" (refer to the UPS user manual)
2. Verify that the UPS is on Bypass mode by checking UPS display panel (refer to the UPS user manual)
3. Set the MBP manual Bypass switch to "Bypass" position. The "Bypass mode" red light of the MBP goes
On, indicating that the load is supplied directly by AC source
4. Proceed to maintenance operations on UPS (refer to the UPS User Manual)
Return to normal operation:
1. Verify that the UPS is on Bypass mode by checking UPS display panel (refer to the UPS user manual)
2. Verify that the "UPS mode" green light of the MBP is On, indicating that the UPS output power is
available on the MBP
Important: do not continue to next step if the "UPS mode" green light of the MBP is Off
(the load will be lost)
3. Set the MBP manual Bypass switch to the "UPS" position: the "Bypass mode" red light of the MBP goes
Off, indicating that the load is now powered by the UPS
4. Put the UPS in "normal mode" (refer to the UPS User Manual)
5. Check that the UPS is in Online mode by checking UPS display panel (refer to the UPS user manual)
the load is now protected by the UPS.
Page 18
SK-90610-Y4_EN
6. Specifications
MBP6K208 MBP11K208
Input
Terminal blocks
Output
2 L6-30R + Terminal blocks 3 L6-30R + Terminal blocks
Overall dimensions D x W x H (inch / mm)
5.6 x 7.0 x 5.1 /
142 x 177 x 130
10.2 x 13.2 x 5.1 /
260 x 336 x 130
Weight (lb / kg)
5.5 / 2.5 13.7 / 6.2
Performance
Nominal voltage 200 - 240 V ~ 200 - 240 V ~
Frequency 50/60 Hz
Input nominal
current
24A 50A
Maximal power 6000 VA 11000 VA
Standards (HotSwap MBP used with UPS)
Safety IEC/EN 62040-1 / Ed.1: 2008. UL 1778 4
th
edition.
EMC IEC 62040-2 / Ed.2: 2005. EN 62040-2 / Ed.2: 2006. FCC part 15 Class A.
Performance IEC/EN 62040-3 / Ed.2.0: 2011.
ESD IEC 61000-4-2 : level 3.
Radiated eld IEC 61000-4-3 : level 3.
EFT IEC 61000-4-4 : level 4.
Fast transients IEC 61000-4-5 : level 4.
Electromagnetic eld IEC 61000-4-6 : level 3.
Conducted
magnetic eld
IEC 61000-4-8 : level 4.
Marking
cULus Listed / CE
Environment
Operating
temperature
0 to 40°C (32 to 104°F)
Storage temperature -15 to 60°C (5 to 140°F)
Transit temperature -25 to 55°C (-13 to 130°F)
Humidity 0 to 95% no condensing
Operation Altitude Up to 3,000 meters (9,843 ft) above sea level with 10% derating per 1000m
Transit Altitude Up to 10,000 meters (32,808 ft) above sea level
Recommended upstream protection
UPS power rating Upstream circuit breaker
5000VA D curve - 30A
6000VA D curve - 30A
8000VA D curve - 50A
11000VA D curve - 70A
G N(L2) L1
N(L2) to UPS Normal AC source
2 poles circuit breaker
L1
/