Lenovo RT11.0VA Installation and User Manual

Category
Uninterruptible power supplies (UPSs)
Type
Installation and User Manual

This manual is also suitable for

6U Rack or Tower UPS RT8.0kVA
and RT11.0VA and Maintenance
Bypass Installation and User's Guide
Note:
Beforeusingthisinformationandtheproductitsupports,readthegeneralinformationinAppendix
B“Gettinghelpandtechnicalassistance”onpage69,AppendixC“Notices”onpage73,thesafety
information,warranties,andlicensesinformationontheLenovoWebsiteat:
https://support.lenovo.com/documents/LNVO-DOCS
SecondEdition(February2017)
©CopyrightLenovo2015,2017.
LIMITEDANDRESTRICTEDRIGHTSNOTICE:IfdataorsoftwareisdeliveredpursuanttoaGeneralServices
Administration“GSAcontract,use,reproduction,ordisclosureissubjecttorestrictionssetforthinContractNo.
GS-35F-05925
Contents
Safety.................iii
Guidelinesfortrainedservicetechnicians.....iv
Inspectingforunsafeconditions.......iv
Guidelinesforservicingelectricalequipment..v
Safetystatements..............vi
Productsafety................x
Chapter1.Introduction.........1
Noticesandstatements............1
Environmentalprotection...........1
Chapter2.Presentation.........5
Standardinstallations.............5
Rearpanels.................6
Controlpanel................6
LCDdescription...............7
Displayfunctions...............9
Usersettings...............10
ExtendedBatteryModules(EBMs).......13
HotSwapMBP...............13
StandardinstallationsfortheHotSwapMBP.13
HotSwapMBPcontrols.........14
Chapter3.Installation.........17
Inspectingtheequipment..........17
Unpackingtheunit.............17
Checkingtheaccessorykit:UPS.......18
Checkingtheaccessorykit:HotSwapMBP...19
Mechanicalmounting............21
ConnectingtheEBM(s)...........21
Rackinstallation..............22
PreparingtheEBMforrackmounting....22
RackmountingofUPS,EBM,andaccessory
modules...............23
Towerinstallation..............24
Installingthecommunicationcard.......24
Installationrequirements...........25
Installationdependingonthesystemearthing
arrangement(SEA).............26
Chapter4.Powercables
connection..............27
Accesstoterminalblocks..........27
Commoninputsourcesconnection(1Phase
units)..................28
Commoninputsourcesconnection(3Phase
units)..................28
Separateinputsourceconnection(1Phaseunits).29
Separateinputsourceconnection(3Phaseunits).29
Frequencyconverterconnection(1Phaseunits)..30
Frequencyconverterconnection(3Phaseunits)..30
HotSwapMBPconnection..........31
8/11kVA1Phase............31
8/11kVA3PhasewithcommonNormaland
BypassACsource...........33
8/11kVA3PhasewithseparateNormaland
BypassACsource...........34
Chapter5.Operation.........39
UPSstartupandshutdown..........39
StartingtheUPS............39
StartingtheUPSonBattery........39
ShuttingdowntheUPS.........40
UPSstart-upwithHotSwapMBP.......40
MonitoringtheUPSoperatingmode......41
Operatingmodes:descriptions......41
Operatingmodes:summary.......42
TransferringtheUPSbetweenmodes......42
SettingHighEfficiencymode.........42
ConfiguringBypasssettings.........43
Bypasstransferoutoftolerance......43
Interrupttime.............43
Configuringbatterysettings.........43
RetrievingtheEventlog...........44
RetrievingtheFaultlog...........44
Chapter6.Communication......45
Communicationports............45
ConnectingRS232orUSBcommunication
ports.................45
Relayoutputcontacts..........45
RemoteOn/Off.............46
RemotePowerOff...........46
Connectivitycard............47
Replacingthecommunicationcard......48
UPSPowerManagementsuite........48
Chapter7.UPSmaintenance.....49
Equipmentcare..............49
Storingtheequipment............49
Replacingbatterypacks...........49
Replacingtheinternalbatterypack.....50
ReplacingtheEBM(s)..........51
Testinganewbatterypack........52
ReplacingtheUPS.............52
©CopyrightLenovo2015,2017
i
RemovingtheUPS...........52
Returningtonormaloperation.......54
Recyclingtheusedequipment........55
Chapter8.Troubleshooting......57
Alarmsandfaults..............57
Silencingthealarm.............60
Serviceandsupport............60
Chapter9.Partslisting........61
AppendixA.Specifications......63
UPSspecifications.............63
HotSwapMBPspecifications.........67
AppendixB.Gettinghelpand
technicalassistance.........69
Beforeyoucall...............69
Usingthedocumentation..........70
GettinghelpandinformationfromtheWorldWide
Web...................70
HowtosendDSAdata...........70
Creatingapersonalizedsupportwebpage...70
Softwareserviceandsupport.........71
Hardwareserviceandsupport........71
Taiwanproductservice...........71
AppendixC.Notices..........73
Trademarks................74
Importantnotes..............74
Recyclinginformation............74
Particulatecontamination..........75
Telecommunicationregulatorystatement....75
Electronicemissionnotices..........75
FederalCommunicationsCommission(FCC)
statement...............75
IndustryCanadaClassAemissioncompliance
statement...............76
Avisdeconformitéàlaréglementation
d'IndustrieCanada...........76
AustraliaandNewZealandClassA
statement...............76
EuropeanUnionEMCDirectiveconformance
statement...............76
GermanyClassAstatement.......76
Japaneseelectromagneticcompatibility
statements..............77
KoreaCommunicationsCommission(KCC)
statement...............78
RussiaElectromagneticInterference(EMI)
ClassAstatement...........78
People'sRepublicofChinaClassAelectronic
emissionstatement...........79
TaiwanClassAcompliancestatement...79
TaiwanBSMIRoHSdeclaration......80
Index..................81
ii 6U Rack or Tower UPS RT8.0kVA and RT11.0VA and Maintenance Bypass Installation and User's Guide
Safety
Beforeinstallingthisproduct,readtheSafetyInformation.
Antesdeinstalaresteproduto,leiaasInformaçõesdeSegurança.
Læssikkerhedsforskrifterne,førduinstallererdetteprodukt.
Leesvoordatuditproductinstalleerteerstdeveiligheidsvoorschriften.
Ennenkuinasennattämäntuotteen,lueturvaohjeetkohdastaSafetyInformation.
Avantd'installerceproduit,lisezlesconsignesdesécurité.
VorderInstallationdiesesProduktsdieSicherheitshinweiselesen.
Primadiinstallarequestoprodotto,leggereleInformazionisullaSicurezza.
Lessikkerhetsinformasjonen(SafetyInformation)førduinstallererdetteproduktet.
©CopyrightLenovo2015,2017
iii
Antesdeinstalaresteproduto,leiaasInformaçõessobreSegurança.
Antesdeinstalaresteproducto,lealainformacióndeseguridad.
Lässäkerhetsinformationeninnanduinstallerardenhärprodukten.
Guidelinesfortrainedservicetechnicians
Thissectioncontainsinformationfortrainedservicetechnicians.
Inspectingforunsafeconditions
UsethisinformationtohelpyouidentifypotentialunsafeconditionsinaLenovoproductthatyouare
workingon.
EachLenovoproduct,asitwasdesignedandmanufactured,hasrequiredsafetyitemstoprotectusers
andservicetechniciansfrominjury.Theinformationinthissectionaddressesonlythoseitems.Usegood
judgmenttoidentifypotentialunsafeconditionsthatmightbecausedbyalterationsorattachmentof
non-Lenovofeaturesoroptionaldevicesthatarenotaddressedinthissection.Ifyouidentifyanunsafe
condition,youmustdeterminehowseriousthehazardisandwhetheryoumustcorrecttheproblembefore
youworkontheproduct.
Considerthefollowingconditionsandthesafetyhazardsthattheypresent:
Electricalhazards,especiallyprimarypower.Primaryvoltageontheframecancauseseriousorfatal
electricalshock.
Explosivehazards,suchasadamagedCRTfaceorabulgingcapacitor.
Mechanicalhazards,suchaslooseormissinghardware.
Toinspecttheproductforpotentialunsafeconditions,completethefollowingsteps:
1.Makesurethatthepowerisoffandthepowercordsaredisconnected.
2.Makesurethattheexteriorcoverisnotdamaged,loose,orbroken,andobserveanysharpedges.
3.Checkthepowercords:
Makesurethatthethird-wiregroundconnectorisingoodcondition.Useametertomeasure
third-wiregroundcontinuityfor0.1ohmorlessbetweentheexternalgroundpinandtheframeground.
Makesurethatthepowercordsarethecorrecttype.
iv 6U Rack or Tower UPS RT8.0kVA and RT11.0VA and Maintenance Bypass Installation and User's Guide
Makesurethattheinsulationisnotfrayedorworn.
4.Removethecover.
5.Checkforanyobviousnon-Lenovoalterations.Usegoodjudgmentastothesafetyofanynon-Lenovo
alterations.
6.Checkinsidethesystemforanyobviousunsafeconditions,suchasmetalfilings,contamination,water
orotherliquid,orsignsoffireorsmokedamage.
7.Checkforworn,frayed,orpinchedcables.
8.Makesurethatthepower-supplycoverfasteners(screwsorrivets)havenotbeenremovedortampered
with.
Guidelinesforservicingelectricalequipment
Observetheseguidelineswhenyouserviceelectricalequipment.
Checktheareaforelectricalhazardssuchasmoistfloors,nongroundedpowerextensioncords,and
missingsafetygrounds.
Useonlyapprovedtoolsandtestequipment.Somehandtoolshavehandlesthatarecoveredwithasoft
materialthatdoesnotprovideinsulationfromliveelectricalcurrent.
Regularlyinspectandmaintainyourelectricalhandtoolsforsafeoperationalcondition.Donotuse
wornorbrokentoolsortesters.
Donottouchthereflectivesurfaceofadentalmirrortoaliveelectricalcircuit.Thesurfaceisconductive
andcancausepersonalinjuryorequipmentdamageifittouchesaliveelectricalcircuit.
Somerubberfloormatscontainsmallconductivefiberstodecreaseelectrostaticdischarge.Donotuse
thistypeofmattoprotectyourselffromelectricalshock.
Donotworkaloneunderhazardousconditionsornearequipmentthathashazardousvoltages.
Locatetheemergencypower-off(EPO)switch,disconnectingswitch,orelectricaloutletsothatyoucan
turnoffthepowerquicklyintheeventofanelectricalaccident.
Disconnectallpowerbeforeyouperformamechanicalinspection,worknearpowersupplies,orremove
orinstallmainunits.
Beforeyouworkontheequipment,disconnectthepowercord.Ifyoucannotdisconnectthepower
cord,havethecustomerpower-offthewallboxthatsuppliespowertotheequipmentandlockthe
wallboxintheoffposition.
Neverassumethatpowerhasbeendisconnectedfromacircuit.Checkittomakesurethatithasbeen
disconnected.
Ifyouhavetoworkonequipmentthathasexposedelectricalcircuits,observethefollowingprecautions:
Makesurethatanotherpersonwhoisfamiliarwiththepower-offcontrolsisnearyouandisavailableto
turnoffthepowerifnecessary.
Whenyouworkwithpowered-onelectricalequipment,useonlyonehand.Keeptheotherhandinyour
pocketorbehindyourbacktoavoidcreatingacompletecircuitthatcouldcauseanelectricalshock.
Whenyouuseatester,setthecontrolscorrectlyandusetheapprovedprobeleadsandaccessories
forthattester.
Standonasuitablerubbermattoinsulateyoufromgroundssuchasmetalfloorstripsandequipment
frames.
Useextremecarewhenyoumeasurehighvoltages.
Toensurepropergroundingofcomponentssuchaspowersupplies,pumps,blowers,fans,andmotor
generators,donotservicethesecomponentsoutsideoftheirnormaloperatinglocations.
©CopyrightLenovo2015,2017
v
Ifanelectricalaccidentoccurs,usecaution,turnoffthepower,andsendanotherpersontogetmedical
aid.
Safetystatements
Thesestatementsprovidethecautionanddangerinformationthatisusedinthisdocumentation.
Eachcautionanddangerstatementinthisdocumentationislabeledwithanumber.Thisnumberisusedto
crossreferenceanEnglish-languagecautionordangerstatementwithtranslatedversionsofthecautionor
dangerstatementintheSafetyInformationdocument.
Forexample,ifadangerstatementislabeledD005,translationsforthatcautionstatementareintheSafety
InformationdocumentunderD005.
Besuretoreadallcautionanddangerstatementsinthisdocumentationbeforeyouperformtheprocedures.
Readanyadditionalsafetyinformationthatcomeswithyoursystemoroptionaldevicebeforeyouinstall
thedevice.
L001
DANGER
Hazardousvoltage,current,orenergylevelsarepresentinsideanycomponentthathasthislabel
attached.Donotopenanycoverorbarrierthatcontainsthislabel.Therearenoserviceableparts
insidethesecomponents.Ifyoususpectaproblemwithoneoftheseparts,contactaservice
technician.
DONOTopenupthechassisoranyotherpartsofanyUPSunit.Thiswillvoidtheunitwarranty.
Onlyreplacepartsforwhichaserviceablepartexists,thatisservicinganyUPSunitislimitedto
FRU/CRUreplacementparts.
(L001)
D005
DANGER
Whenworkingonoraroundthesystem,observethefollowingprecautions:Electricalvoltageand
currentfrompower,telephone,andcommunicationcablesarehazardous.Toavoidashockhazard:
IfLenovosuppliedapowercord(s),connectpowertothisunitonlywiththeLenovo-provided
powercord.DonotusetheLenovo-providedpowercordforanyotherproduct.
Donotopenorserviceanypowersupplyassembly.
Donotconnectordisconnectanycablesorperforminstallation,maintenance,orreconfiguration
ofthisproductduringanelectricalstorm.
Theproductmightbeequippedwithmultiplepowercords.Toremoveallhazardousvoltages,
disconnectallpowercords.
vi 6U Rack or Tower UPS RT8.0kVA and RT11.0VA and Maintenance Bypass Installation and User's Guide
Connectallpowercordstoaproperlywiredandgroundedelectricaloutlet.Ensurethatthe
outletsuppliespropervoltageandphaserotationaccordingtothesystemratingplate.
Connectanyequipmentthatwillbeattachedtothisproducttoproperlywiredoutlets.
Whenpossible,useonehandonlytoconnectordisconnectsignalcables.
Neverturnonanyequipmentwhenthereisevidenceoffire,water,orstructuraldamage.
Disconnecttheattachedpowercords,telecommunicationssystems,networks,andmodems
beforeyouopenthedevicecovers,unlessinstructedotherwiseintheinstallationand
configurationprocedures.
Connectanddisconnectcablesasdescribedinthefollowingprocedureswheninstalling,
moving,oropeningcoversonthisproductorattacheddevices.T odisconnect:
1.Turnoffeverything(unlessinstructedotherwise).
2.Removethepowercordsfromtheoutlets.
3.Removethesignalcablesfromtheconnectors.
4.Removeallcablesfromthedevices.
Toconnect:
1.Turnoffeverything(unlessinstructedotherwise).
2.Attachallcablestothedevices.
3.Attachthesignalcablestotheconnectors.
4.Attachthepowercordstotheoutlets.
5.Turnonthedevices.
Sharpedges,cornersandjointsmightbepresentinandaroundthesystem.Usecarewhen
handlingequipmenttoavoidcuts,scrapesandpinching.(D005)
C004
CAUTION:
Lead-acidbatteriescanpresentariskofelectricalburnfromhigh,short-circuitcurrent.Avoidbattery
contactwithmetalmaterials;removewatches,rings,orothermetalobjects,andusetoolswith
insulatedhandles.Toavoidpossibleexplosion,donotburn.
ExchangeonlywiththeLenovo-approvedpart.Recycleordiscardthebatteryasinstructedby
localregulations.IntheUnitedStates,Lenovohasaprocessforthecollectionofthisbattery.For
information,call1-800-426-4333.HavetheLenovopartnumberforthebatteryunitavailablewhen
youcall.
DONOTmixoldandnewbatteriesinanUninterruptiblePowerSupplyunit.
DONOTopenupanybatterypackretrievedfromanUninterruptiblePowerSupplyunit.
WearsafetygogglesforyourownprotectionwhenreplacingbatteriesofanUninterruptiblePower
Supplyunit.(C004)
C009
©CopyrightLenovo2015,2017
vii
CAUTION:
or or Theweightofthispartorunitisbetween18
and32kg(39.7and70.5lb).Ittakestwopersonstosafelyliftthispartorunit.(C009)
C011
CAUTION:
or or Theweightofthispartorunitismorethan55
kg(121.2lb).Ittakesspeciallytrainedpersons,aliftingdevice,orbothtosafelyliftthispartor
unit.(C011)
C022
CAUTION:
Thisproductmightbeequippedwithahard-wiredpowercable.Ensurethatalicensedelectrician
performstheinstallationperthenationalelectricalcode.(C022)
R001
Important:Thefollowinggeneralsafetyinformationshouldbeusedforallrack-mounteddevices:
DANGER
ObservethefollowingprecautionswhenworkingonoraroundyourITracksystem:
Heavyequipment—personalinjuryorequipmentdamagemightresultifmishandled.
Alwayslowerthelevelingpadsontherackcabinet.
Alwaysinstallstabilizerbracketsontherackcabinet.
Toavoidhazardousconditionsduetounevenmechanicalloading,alwaysinstalltheheaviest
devicesinthebottomoftherackcabinet.Alwaysinstallserversandoptionaldevicesstarting
fromthebottomoftherackcabinet.
viii 6U Rack or Tower UPS RT8.0kVA and RT11.0VA and Maintenance Bypass Installation and User's Guide
Rack-mounteddevicesarenottobeusedasshelvesorworkspaces.Donotplaceobjectson
topofrack-mounteddevices.
Eachrackcabinetmighthavemorethanonepowercord.Besuretodisconnectallpowercords
intherackcabinetwhendirectedtodisconnectpowerduringservicing.
Connectalldevicesinstalledinarackcabinettopowerdevicesinstalledinthesamerack
cabinet.Donotplugapowercordfromadeviceinstalledinonerackcabinetintoapower
deviceinstalledinadifferentrackcabinet.
Anelectricaloutletthatisnotcorrectlywiredcouldplacehazardousvoltageonthemetalparts
ofthesystemorthedevicesthatattachtothesystem.Itistheresponsibilityofthecustomerto
ensurethattheoutletiscorrectlywiredandgroundedtopreventanelectricalshock.
(R001part1of2)
CAUTION:
Donotinstallaunitinarackwheretheinternalrackambienttemperatureswillexceedthe
manufacturer’srecommendedambienttemperatureforallyourrack-mounteddevices.
Donotinstallaunitinarackwheretheairflowiscompromised.Ensurethatairflowisnotblocked
orreducedonanyside,front,orbackofaunitusedforairflowthroughtheunit.
Considerationshouldbegiventotheconnectionoftheequipmenttothesupplycircuitsothat
overloadingofthecircuitsdoesnotcompromisethesupplywiringorovercurrentprotection.To
providethecorrectpowerconnectiontoarack,refertotheratinglabelslocatedontheequipment
intheracktodeterminethetotalpowerrequirementofthesupplycircuit.
(Forslidingdrawers)Donotpulloutorinstallanydrawerorfeatureiftherackstabilizerbracketsare
notattachedtotherack.Donotpulloutmorethanonedraweratatime.Therackmightbecome
unstableifyoupulloutmorethanonedraweratatime.
(Forfixeddrawers)Thisdrawerisafixeddrawerandmustnotbemovedforservicingunless
specifiedbythemanufacturer.Attemptingtomovethedrawerpartiallyorcompletelyoutofthe
rackmightcausetheracktobecomeunstableorcausethedrawertofalloutoftherack.
(R001part2of2)
Outputpowerandampereratings
Important:Makesurethatthepowerreceptacleisneartheequipmentandiseasilyaccessiblesothatthe
uninterruptiblepowersupply(UPS)canbedisconnectedquickly.
Toreducetheriskoffire,connectonlytoacircuitprovidedwithbranchcircuitovercurrentprotection
withanampereratinginaccordancewiththeNationalElectricalCode(NEC),ANSI/NFPA70oryourlocal
electricalcode:
©CopyrightLenovo2015,2017
ix
UPSoutputpower120V208V230V
1500VA15ANotapplicable10A
2200VA20ANotapplicable10A
3000VA30A20A16A
Productsafety
TheUPSconnectioninstructionsandoperationsdescribedinthemanualmustbefollowedinthe
indicatedorder.
Important:Toreducetheriskoffire,theunitconnectsonlytoacircuitprovidedwithbranchcircuit
overcurrentprotectionasdescribedinthismanual,inaccordancewiththeNationalElectricCode,
ANSI/NFPA70.
TheupstreamcircuitbreakerforNormalACandBypassACmustbeeasilyaccessible.Theunitcanbe
disconnectedfromACpowersourcebyopeningthiscircuitbreaker.Thiscircuitbreakerisusedfor
backfeedprotectionandmustcomplywithIEC/EN62040-1(thecreepageandclearancedistancesshall
meetthebasicinsulationrequirementsforpollutiondegree2).
Disconnectionandovercurrentprotectiondevicesshallbeprovidedbyothersforpermanentlyconnected
ACinput(NormalACandBypassAC)andACoutputcircuits.
CheckthattheindicationsontheratingplatecorrespondtoyourACpoweredsystemandtotheactual
electricalconsumptionofalltheequipmenttobeconnectedtothesystem.
ForPLUGGABLEEQUIPMENT,thesocket-outletshallbeinstalledneartheequipmentandshallbe
easilyaccessible.
Neverinstallthesystemnearliquidsorinanexcessivelydampenvironment.
Neverletaforeignbodypenetrateinsidethesystem.
Neverblocktheventilationgratesofthesystem.
Neverexposethesystemtodirectsunlightorsourceofheat.
Ifthesystemmustbestoredpriortoinstallation,storagemustbeinadryplace.
Theadmissiblestoragetemperaturerangeis-15ºCto+50ºC.
ThisunitisnotdesignedtoconformtoANSI/NFPA75andthereforeisnotforuseinANSI/NFPA
75-certifieddatacenters.
AlthoughtheUPSdoesnotcontainanti-backfeed(ABF)relays,somebackfeedprotectionisprovided.
Forexample,ifsomecomponentsaredamagedinbatterymode,theoutputvoltagemayfeedback
totheinput.Inthiscase,acurrenttransformer(CT)isusedtodetectthebypasscurrentfeedback
voltage.Ifacurrentbackfeedfaultconditionisdetected,theUPSwillterminatetheinverteroutputto
avoidpersonalinjury.
x 6U Rack or Tower UPS RT8.0kVA and RT11.0VA and Maintenance Bypass Installation and User's Guide
Chapter1.Introduction
ThankyouforselectingaLenovoproducttoprotectyourelectricalequipment.
Readthismanualtotakefulladvantageofthefeaturesofyourequipment.
Beforeinstallingyourequipment,readthesafetyinstructions.Then,followtheinstructionsinthismanual
forsettingupandusingtheproduct.
TodiscovertheentirerangeofLenovoproductsandtheoptionsavailablefortheLenovoUPSdevice,we
inviteyoutovisitourwebsiteorcontactyourLenovorepresentative.
Noticesandstatements
ThecautionanddangerstatementsinthisdocumentarealsointhemultilingualSafetyInformation
document,whichisontheLenovoWebsiteathttps://support.lenovo.com/documents/LNVO-DOCS.Each
statementisnumberedforreferencetothecorrespondingstatementintheSafetyInformationdocument.
Noticesandstatementsinthisdocument
Thefollowingnoticesandstatementsareusedinthisdocument:
Note:Thesenoticesprovideimportanttips,guidance,oradvice.
Important:Thesenoticesprovideinformationoradvicethatmighthelpyouavoidinconvenientor
problemsituations.
Attention:Thesenoticesindicatepossibledamagetoprograms,devices,ordata.Anattentionnoticeis
placedjustbeforetheinstructionorsituationinwhichdamagemightoccur.
Caution:Thesestatementsindicatesituationsthatcanbepotentiallyhazardoustoyou.Acaution
statementisplacedjustbeforethedescriptionofapotentiallyhazardousproceduresteporsituation.
Danger:Thesestatementsindicatesituationsthatcanbepotentiallylethalorhazardoustoyou.A
dangerstatementisplacedjustbeforethedescriptionofapotentiallylethalorhazardousprocedure
steporsituation.
Environmentalprotection
Lenovohasimplementedanenvironmental-protectionpolicy.Productsaredevelopedaccordingtoan
eco-designapproach.
Substances
ThisproductdoesnotcontainCFCs,HCFCsorasbestos.
Packing
Toimprovewastetreatmentandfacilitaterecycling,separatethevariouspackingcomponents.
Thecardboardweusecomprisesover50%ofrecycledcardboard.
Sacksandbagsaremadeofpolyethylene.
©CopyrightLenovo2015,2017
1
Packingmaterialsarerecyclableandbeartheappropriateidentificationsymbol .
MaterialsAbbreviations
Numberinthesymbols
PolyethyleneterephthalatPET01
High-densitypolyethyleneHDPE02
Polyvinylchloride
PVC
03
Low-densitypolyethyleneLDPE04
PolypropylenePP05
Polystyrene
PS
06
Follow all local regulations for the disposal of packing materials.
Refer to the Lenovo Environmental Notices and User's Guide, provided on the Lenovo Web site at
https://support.lenovo.com/documents/LNVO-DOCS.
End of life
Lenovo will process products at the end of their service life in compliance with local regulations. Lenovo
works with companies in charge of collecting and eliminating our products at the end of their service life.
Product
The product is made up of recyclable materials. Dismantling and destruction must take place in compliance
with all local regulations concerning waste. At the end of its service life, the product must be transported to a
processing center for electrical and electronic waste.
Battery
The product contains lead-acid batteries that must be processed according to applicable local regulations
concerning batteries.
The battery pack can be removed to comply with regulations and in view of correct disposal.
With the Lenovo UPS device, you can eliminate the effects of power disturbances and guard the integrity
of your equipment. Providing outstanding performance and reliability, the Lenovo UPS device's unique
benefits include:
2 6U Rack or Tower UPS RT8.0kVA and RT11.0VA and Maintenance Bypass Installation and User's Guide
Trueonlinedouble-conversiontechnologywithhighpowerdensity,utilityfrequencyindependence,and
powergeneratorcompatibility.
AdvancedBatteryManagement(®ABM)technologythatusesadvancedbatterymanagementtoincrease
batteryservicelife,optimizerechargetime,andprovideawarningbeforetheendofusefulbatterylife.
SelectableHighEfficiencymodeofoperation.
Standardcommunicationoptions:oneRS-232communicationport,oneUSBcommunicationport,and
relayoutputcontacts.
UPSNetworkManagementCardwithenhancedcommunicationcapabilities.
ExtendedruntimewithuptofourExtendedBatteryModules(EBMs)perUPS.
Firmwarethatiseasilyupgradablewithoutaservicecall.
RemoteOn/OffcontrolthroughRemoteOn/Off(ROO)andRemotePowerOff(RPO)ports.
Chapter1.Introduction3
4 6U Rack or Tower UPS RT8.0kVA and RT11.0VA and Maintenance Bypass Installation and User's Guide
Chapter2.Presentation
Standardinstallations
Description
Weights
(lb/kg)
Dimensions(inch/mm)
DxWxH
8kVA3:1PowerModule
51/2327.6x17.3x5.1/700x440x130
8kVAPowerModule(1:1)42/1927.6x17.3x5.1/700x440x130
11kVA3:1PowerModule
51/2327.6x17.3x5.1/700x440x130
11kVAPowerModule(1:1)46/2127.6x17.3x5.1/700x440x130
8kVA/11kVABatteryModule143/6526.8x17.3x5.1/680x440x130
Rackinstallation
Towerinstallation
Shippingbracketkit
IfyouareshippingtheUPSanditsassociatedEBMspreinstalledinarack,youmustusetheshipping
bracketkittopreventdamageduringshipment.ThekitisavailablefromLenovo.Refertotheinstructionsin
thekittoinstallthebracketsproperly.ThebracketsarenotrequiredwhentheUPSandEBMsareinstalledin
apre-positionedrack.
©CopyrightLenovo2015,2017
5
Rearpanels
Figure1.5594-8KX,5594-8PX
Figure2.5594-9KX,5594-9PX
RS232communicationport
USBcommunicationport
Dry(relay)contactscommunicationport
ConnectorforRemoteOn/Off(ROO)control
Connectorsforautomaticrecognitionofbattery
module
ConnectorforRemotePowerOff(RPO)control
SlotwhereUPSNetworkManagementCardis
installed
Connectorforbatterymodulepower
TerminalblocksforACpowerinputandoutput
ConnectorforHotSwapMBPdetection
Figure3.5594-9BXExtendedBatteryModule
Connectorsforbatterymodules(totheUPSor
totheotherbatterymodules)
Connectorsforautomaticrecognitionofbattery
modules(UPS-to-EBMorEBM-to-EBM)
Batterycircuitbreaker
Controlpanel
TheUPShasafive-buttongraphicalLCDfrontpanel.ItprovidesusefulinformationabouttheUPSitself,
loadstatus,events,measurements,andsettings.Italsoprovidesamethodtochangesettings.
6 6U Rack or Tower UPS RT8.0kVA and RT11.0VA and Maintenance Bypass Installation and User's Guide
Thefollowingtableshowstheindicatorstatusanddescription:
IndicatorStatusDescription
Green
OnTheUPSisoperatingnormallyin
OnlineorinHighEfficiencymode.
Orange
OnTheUPSisinBatterymode.
Orange
OnTheUPSisinBypassmode.
Red
OnTheUPShasanactivealarmorfault.
SeeChapter8“Troubleshooting”on
page57foradditionalinformation.
LCDdescription
After5minutesofinactivity,theLCDdisplaysthescreensaver.
TheLCDbacklightautomaticallydimsafter10minutesofinactivity.Pressanybuttontorestorethescreen.
Chapter2.Presentation7
ThefollowingtabledescribesthestatusinformationprovidedbytheUPS.
Note:Ifanyotherindicatordisplays,seeChapter8“Troubleshooting”onpage57foradditionalinformation.
Operation
statusCauseDescription
IsBatteryBeing
Charged?
Standbymode TheUPSoutputisOff.
Equipmentisnotpowereduntil
buttonispressed.
Yes
Onlinemode TheUPSisoperatingnormally.TheUPSispoweringandprotecting
theequipment.
Yes
Batterymode
1beepevery10
seconds
Autilitypowerfailurehasoccurred
andtheUPSisinBatterymode.
TheUPSispoweringtheequipment
withbatterypower.Prepareyour
equipmentforshutdown.
No
Endofbackup
time
1beepevery3
seconds
TheUPSisinBatterymodeandthe
batterypacksarerunninglow.
Thiswarningisapproximate,andthe
actualtimetoshutdownmightvary
significantly.
DependingontheUPSloadand
numberofExtendedBatteryModules
(EBMs),the"BatteryLow"warning
mightoccurbeforethebatterypacks
reach20%capacity.
No
8 6U Rack or Tower UPS RT8.0kVA and RT11.0VA and Maintenance Bypass Installation and User's Guide
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96

Lenovo RT11.0VA Installation and User Manual

Category
Uninterruptible power supplies (UPSs)
Type
Installation and User Manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI