Eaton Powerware Prestige Series 1500 VA Installation And Operator's Manual

Category
Uninterruptible power supplies (UPSs)
Type
Installation And Operator's Manual

This manual is also suitable for

powerware
®
Prestige Series
650 VA - 1500 VA
Installation and Operators Manual for IBM Applications
Requesting a Declaration of Conformity
Units that are labeled with a CE mark comply with the following harmonic standards and EU directives:
Harmonic Standards: EN 50091-1-1 and EN 50091-2
EU Directives: 73/23/EEC, Council Directive on equipment designed for use within certain voltage limits
93/68/EEC, Amending Directive 73/23/EEC
89/336/EEC, Council Directive relating to electromagnetic compatibility
92/31/EEC, Amending Directive 89/336/EEC relating to EMC
The EC Declaration of Conformity is available upon request for products with a CE mark. For copies of the EC
Declaration of Conformity, contact:
Powerware Corporation
Koskelontie 13
FIN-02920 Espoo
Finland
Phone: +358-9-452 661
Fax: +358-9-452 665 68
Powerware, PowerPass, Powercare, OnliNet, and OnliSafe are registered trademarks of Powerware Corporation.
IBM and AS/400 are registered trademarks of International Business Machines Corp.
Novell is a registered trademark of Novell, Inc.
3Com is a registered trademark of 3Com Corporation.
Copyright 1995-2000 Powerware Corporation, Raleigh, North Carolina, USA. All rights reserved. No part of this
document may be reproduced in any way without the express written approval of Powerware Corporation.
Class A EMC Statements
FCC Part 15
NOTE This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to
part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when
the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency
energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio
communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case
the user will be required to correct the interference at his own expense.
ICES-003
This Class A Interference Causing Equipment meets all requirements of the Canadian Interference Causing Equipment
Regulations ICES-003.
Cet appareil numérique de la classe A respecte toutes les exigences du Reglement sur le matériel brouilleur du Canada.
EN50091-2
Some configurations are classified under EN50091-2 as “Class-A UPS for Unrestricted Sales Distribution.” For these
configurations, the following applies:
WARNING This is a Class A-UPS Product. In a domestic environment, this product may cause radio interference, in
which case, the user may be required to take additional measures.
Class B EMC Statements
FCC Part 15
NOTE This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to
part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a
residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and
used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no
guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to
radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try
to correct the interference by one or more of the following measures:
Reorient or relocate the receiving antenna.
Increase the separation between the equipment and the receiver.
Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
Consult the dealer or an experienced radio/TV technician for help.
ICES-003
This Class B Interference Causing Equipment meets all requirements of the Canadian Interference Causing Equipment
Regulations ICES-003.
Cet appareil numérique de la classe B respecte toutes les exigences du Reglement sur le matériel brouilleur du Canada.
Thispage intentionally left blank.
QUICK INSTALL
120V Model Installation
1 If you are connecting the UPS to an AS/400, the QUPSDLYTIM system value for the UPS
Monitoring feature should be set. See “UPS Monitoring” on page 54 for instructions.
2
3 For the AS/400 interface, plug the AS/400 communications cable into the serial port on the
UPS rear panel. Plug the other end of the cable into the connector, located on the back of
the system unit, labeled “UPS” (AS/400 Models 2xx/4xx/170).
4
Quick Install
230V Model Installation
NOTE For 208,220, or240V models,followthe instructionsfor changing the outputvoltage on
page 39.
1 If you are connecting the UPS to an AS/400, the QUPSDLYTIM system value for the UPS
Monitoring feature should be set. See “UPS Monitoring” on page 54 for instructions.
2
3 For the AS/400 interface, plug the AS/400 communications cable into the serial port on the
UPS rear panel. Plug the other end of the cable into the connector, located on the back of
the system unit, labeled “UPS” (AS/400 Models 2xx/4xx/170).
4
Quick Install
UPS with Optional 120V PPDM Installation
1 If you are connecting the UPS to an AS/400, the QUPSDLYTIM system value for the UPS
Monitoring feature should be set. See “UPS Monitoring” on page 54 for instructions.
2
Battery
Cabinet
UPS
Cabinet
PowerPass
Distribution
Module
(PPDM)
3
Bypass Switch
(NORMAL Position)
4
Battery
Breaker
I
O
ON
OFF
I
O
ON
OFF
Quick Install
5
6 For the AS/400 interface, plug the AS/400 communications cable into the serial port on the
UPS rear panel. Plug the other end of the cable into the connector, located on the back of
the system unit, labeled “UPS” (AS/400 Models 600 and S10).
7
Quick Install
UPS with Optional 230V PPDM Installation
NOTE For 208,220, or240V models,followthe instructionsfor changing the outputvoltage on
page 47.
1 If you are connecting the UPS to an AS/400, the QUPSDLYTIM system value for the UPS
Monitoring feature should be set. See “UPS Monitoring” on page 54 for instructions.
2
Battery
Cabinet
UPS
Cabinet
PowerPass
Distribution
Module
(PPDM)
3
Bypass Switch
(NORMAL Position)
Quick Install
4
Battery
Breaker
I
O
ON
OFF
I
O
ON
OFF
5
6 For the AS/400 interface, plug the AS/400 communications cable into the serial port on the
UPS rear panel. Plug the other end of the cable into the connector, located on the back of
the system unit, labeled “UPS” (AS/400 Models 600 and S10).
7
i
Powerware
®
PrestigeSeriesInstallation and Operators Manualfor IBM Applications(650VA-1500 VA)Uncontrolled Copy
TABLE OF CONTENTS
1 Introduction 1....................................................
UPSModel andBattery Configurations 2..............................................
LoadRequirements 2.........................................................
ApproximateBattery Times 3....................................................
Prestige Product Models 5.....................................................
Special Symbols 7..............................................................
2 Safety Warnings 9.................................................
3 Installation 35.....................................................
Unpacking andInspection 35.......................................................
UPSand BatteryCabinetStorage 35...............................................
Selecting anInstallation Option 36...................................................
UPSand BatteryCabinetInstallation 36...............................................
UPSStartup for120VModels 38..................................................
UPSStartup for208V-240V Models 39..............................................
UPSwithOptionalPPDM Installation 41...............................................
UPSwithPPDM Startup for120V Models 46.........................................
UPSwithPPDM Startup for208V-240V Models 47.....................................
Troubleshooting Tips 48...........................................................
4 UPS Operation 49..................................................
UPSFront Panel 49..............................................................
Operating Modes 50.............................................................
NormalMode 50.............................................................
Bypass Mode 51.............................................................
BatteryMode 51.............................................................
Diagnostics 52.................................................................
BatteryTestonDemand 52......................................................
BatteryStart 53................................................................
UPSShutdown 53...............................................................
Changingthe OutputVoltage 53.....................................................
UPSMonitoring 54..............................................................
Usingthe PPDM 55..............................................................
Disconnecting theUPS 55.......................................................
Reconnecting theUPS 58.......................................................
Table of Contents
ii
Powerware
®
PrestigeSeriesInstallation andOperators ManualforIBMApplications (650 VA- 1500VA)UncontrolledCopy
5 Communication 59.................................................
InitialCommunicationsSettings 59...................................................
FrontPanel CommunicationsAccess 60...............................................
UPSSerialCommunications Menu 62.................................................
PowerManagement Software 65....................................................
UPSCommunicationsInterface Port 66................................................
Communications ModeReferenceChart 67.............................................
6 Specifications 69..................................................
Prestige UPS ModelSpecifications 69................................................
Prestige UPS PhysicalSpecifications 69...............................................
Prestige UPS TechnicalSpecifications 70..............................................
Part Numbers 71................................................................
BaseEquipment 71...........................................................
Standard Accessories 71........................................................
OptionalAccessories 71........................................................
Manuals 71.................................................................
7 Troubleshooting 73.................................................
Resetting the UPS 75............................................................
SilencingtheAlarm 75...........................................................
8 AS/400 Service 77..................................................
Index 83.........................................................
1
Powerware
®
PrestigeSeriesInstallation andOperators ManualforIBMApplications (650 VA- 1500VA)UncontrolledCopy
CHAPTER 1
INTRODUCTION
Congratulations on the purchase of your Powerware Prestige Series
uninterruptible power system (UPS). The Prestige UPS meets the
toughest measures of superior design and manufacturing, including
ISO 9001. You now own the most reliable power protection available.
The Prestige provides a steady, well-regulated power supply for your
computingand communications equipment,while protecting it from the
frequent irregularities that are inherent in commercially available power.
Voltage spikes, power surges, brownouts, and power failures have the
potential to corrupt critical data, destroy unsaved work sessions, and in
some instances, damage expensive hardware.
With the Prestige, you can safely eliminate the effects of electrical line
disturbances and guard the integrity of your systems and equipment.
The optional PowerPass
Distribution Module (PPDM) has a
Maintenance Bypass feature that supplies power to your equipment even
when the UPS electronics are removed for maintenance or upgrades.
Figure 1 shows the Prestige UPS.
Figure1.PrestigeUPS
Introduction
2
Powerware
®
PrestigeSeriesInstallation andOperators ManualforIBMApplications (650 VA- 1500VA)UncontrolledCopy
UPS Model and Battery Configurations
This UPS is designed to work with single-phase, three-wire,AC power
sources. There are two important considerations whenselecting the UPS
model and battery configuration to properly safeguard your equipment:
Load requirements
Battery times
Load Requirements
The load is the equipment to be protected by the UPS.Select the UPS
model that meets the power consumption requirements of the load in
volt-amperes (VA). The total load VA should not exceed the UPS VA
rating. To determine the total load requirements:
1. Obtain the load ratings from either the nameplate or operator’s
manual of the equipment to be protected by the UPS. The
ratings are listed in either watts (W), amperes or amperes
max (A), or volt-amperes.
2. If the rating is in watts, multiply by 1.4 to obtain the VA
requirement (this is the typical relationship betweenwatts and
volt-ampere ratings in most computing equipment). However,
in some new computing equipment, the power supply is
power-factor corrected and the watts rating equals the VA
requirement. Check with the manufacturer to determine
applicability.
If the rating is inamperes or amperes max, multiply by the
input voltage to obtain the VA requirement.
NOTE FortheloadratingsofAS/400modelsandattachabledevices,seeChapter 9of
“AS/400Physical PlanningReference,” SC41-5109.
Introduction
3
Powerware
®
PrestigeSeriesInstallation andOperators ManualforIBMApplications (650 VA- 1500VA)UncontrolledCopy
3. Add all of the resultant VA ratings together to obtain the total
load requirements of the equipment to be protected (see
Figure 2). If the load consists of the power-factor corrected
supplies, it is recommended to use total watts for the load
requirements.
COMPUTER MONITOR EXTERNAL
MODEM
100 WATTS x 1.4 = 140 VA
2AMPERESx120=240VA
50 VA
140 VA + 240 VA + 50 VA = 430 VA (Total Load Requirements)
100WATTS 2AMPS 50VA
or 1 AMPERE x 240 = 240 VA
Figure 2. Volt-Amperes Calculation Example
If the total load requirements of the equipment exceeds the capacity of
the UPS, you must either reduce the number of pieces of equipment, or
use a UPS with a larger load capacity.
When deciding on which pieces of equipment to remove from the UPS,
select equipment that has a lower priority for power protection.
Computers, monitors, and modems typically have a higher priority
because they could be processing or transmitting data when a power
outage occurs.
Approximate Battery Times
During a power failure, the UPS battery supplies power to your
equipment, providing time to complete computing activities prior to
UPS shutdown. The duration of this time period is directly related to the
UPS battery configuration. By adding battery cabinets (EXT models
only), you can customize the UPS to provide enough battery time for
normal processing activities.
Introduction
4
Powerware
®
PrestigeSeriesInstallation andOperators ManualforIBMApplications (650 VA- 1500VA)UncontrolledCopy
To prepare for a power outage at your installation, ensure that you have
sufficient battery time available. To do this, take a few minutes to
determine your approximate battery time by completing the following
steps:
Load
Battery Time
L
o
a
d
Requirements
(VA)
UPS Model BatteryCabinets TotalBatteryTimeMinutes
(Approximate)
Figure 3. Determining Approximate Battery Time
1. See Load Requirements” on page 2 for assistance in
determining the total load requirements for your UPS. Round
this number up to the next Load (VA) entry in the “Prestige
Product Models” table on page 5, and enter the number in
Figure 3.
2. If you have installed battery cabinets, skip to Step 3.
If you do not have any battery cabinets, enter your UPS Model
number in Figure 3 (for example, 650, 650 EXT, 1250 EXT,
1500 EXT). Find the appropriate Load (VA) and UPS Model in
the “Prestige Product Models” table on page 5. The
intersection of these two parameters shows the approximate
number of minutes of battery time your UPS Model will have at
full load (enter this number in Figure 3, Total Battery Time
Minutes).
3. In Figure 3, enter the number of battery cabinets that you
have installed. Find the intersection point of the appropriate
Load (VA) and number of battery cabinets in the “Prestige with
Additional Battery Cabinets” table on page 6. Enter this
number in Figure 3, Total Battery Time Minutes.
If changes take place in yourinstallation, such as different load
parameters or changes to battery cabinet configuration,take time to
reevaluate your approximate battery time availability.
NOTE Fordetailedinformationregardingcalculationof9910UPSbatterycapacityand
run time foryour load,reference: “AS/400PhysicalPlanning,SA41-5109,“AS/400
AdvancedSeriesBackupand Recovery -Advanced,” SC41-4305 (see Chapter10),or
AS/400e seriesBackup andRecovery,”SC41-5304 (see Chapter37).
Introduction
5
Powerware
®
PrestigeSeriesInstallation andOperators ManualforIBMApplications (650 VA- 1500VA)UncontrolledCopy
Prestige Product Models
Load
PrestigeProductModelswith InternalBattery
(ApproximateBatteryTime in Minutes)
(VA)
a
t
Load
(
W
)
120V Models
a
t
.7 PF*
(
W
)
650 650
EXT
1250
EXT
1500
EXT
200 140 48 68 68 68
400 280 23 32 32 32
600 420 14 20 20 20
800 560 14 14
1000 700 11 11
1250 875 8 8
1500 1050 6
208V-240V Models
200 140 56 56 55
400 280 29 29 27
600 420 19 19 18
800 560 13 13
1000 700 10 10
1250 875 8 8
1500 1050 6
Typical Power Factor (PF)
The EXT Models have “P2” in the rating label model number.
Introduction
6
Powerware
®
PrestigeSeriesInstallation andOperators ManualforIBMApplications (650 VA- 1500VA)UncontrolledCopy
Prestige with Additional Battery Cabinets
Load
(
V
A
)
L
o
a
d
BatteryCabinetConfigurationsforEXT Models
(ApproximateBatteryTime in Minutes)
(
V
A
)
at
*
L
oa
d
(W)
120V EXT Models
.7 PF*
(
)
1Cabinet 2Cabinets 3Cabinets 4Cabinets
200 140 240 404 570 737
400 280 128 220 311 402
600 420 81 152 215 277
800 560 57 110 162 210
1000 700 43 83 127 168
1250 875 33 62 95 131
1500 1050 25 48 74 101
208V-240V EXT Models
200 140 203 346 491 637
400 280 117 201 285 371
600 420 76 141 200 260
800 560 55 105 153 199
1000 700 42 81 124 161
1250 875 32 61 94 129
1500 1050 25 49 74 102
Typical Power Factor (PF)
The EXT Models have “P2” in the rating label model number.
NOTE For AS/400 usage,see“BaseEquipment”on page 71.
Introduction
7
Powerware
®
PrestigeSeriesInstallation andOperators ManualforIBMApplications (650 VA- 1500VA)UncontrolledCopy
Special Symbols
The following common symbols may be found on the UPS:
LOAD ON - Press the button with this symbol to energize the
output receptacles (Output On).
LOAD OFF - Press the button with this symbol to de-energize
the output receptacles (Output Off).
SAFETY EARTHING TERMINAL - Indicates the primary safety
ground.
RISK OF ELECTRIC SHOCK - Indicates that a risk of electric
shock is present and the associated warning should be
observed.
CAUTION: REFER TO OPERATORS MANUAL - Refer to your
operator’s manual for additional information.
This symbol indicates that the UPS batteries should not be
discarded in the trash. The UPS contains sealed lead
batteries and must be disposed of properly. For battery
replacement or removal, see Chapter 8, “AS/400 Service” on
page 77 for assistance.
Introduction
8
Powerware
®
PrestigeSeriesInstallation andOperators ManualforIBMApplications (650 VA- 1500VA)UncontrolledCopy
Thispage intentionally left blank.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102

Eaton Powerware Prestige Series 1500 VA Installation And Operator's Manual

Category
Uninterruptible power supplies (UPSs)
Type
Installation And Operator's Manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI