Note
9PX5KP1 and 9PX6KP1 interconnect diagram
Thefollowingstepsoutlinehowtoproperlyinterconnectthe9PX5KP1and9PX6KP1.Eachofthesemodelsisabundle
whichcontainsaUPSandaPPDM.TheUPSisanUninterruptiblePowerSupplywhichcontainspowerelectronicsand
batteries.ThePPDMisaPowerPassDistributionModulewhichcontainsawrap‐aroundmaintenancebypass,astepdown
transformerfor120Voutput,andoutputdistribution(receptaclesandbreakers).
Figure 1. UPS and PPDM before interconnecting
1. Step1:Ensureproperalignment.Forrackmountappl icationstheUPSandPPDMshouldbeinstalled
adjacenttooneanother.Thiswillensurethattheinterconnectcables willbeabletoproperlymake
theconnections.Likewise,installationsinthetowerpositionshouldbeadjacentusingthesteps
showninChapter3
oftheEaton9PXPowerPass®DistributionModulesan dTransformers
9PXTFMR5,9PXPPDM2,9PXTFMR11,and9PXPPDM1User'sGuide.
2. Step2:Connectthe“FromUPSOutput”CableonthePPDMtotheUPS.Thecableshouldconnectto
oneofthe30A,L6‐30receptacles.
UPS
PPDM
UPS “Normal AC Source”
In
ut Cable
PPDM “From UPS Output”
Cable
PPDM “Normal AC Source”
Input Cable