Eaton 9910 User manual

Category
Uninterruptible power supplies (UPSs)
Type
User manual
Powerware Series
Eaton 9910 UPS and EBM
User's Guide
®
Powerware Series
Eaton 9910 UPS and EBM
User's Guide
®
Requesting a Declaration of Conformity
Units that are labeled with a CE mark comply with the following harmonized standards and EU directives:
S Harmonized Standards: IEC 62040-1-1 and IEC 62040-2; IEC 60950 Third Edition
S EU Directives: 73/23/EEC, Council Directive on equipment designed for use within certain voltage limits
93/68/EEC, Amending Directive 73/23/EEC
89/336/EEC, Council Directive relating to electromagnetic compatibility
92/31/EEC, Amending Directive 89/336/EEC relating to EMC
The EC Declaration of Conformity is available upon request for products with a CE mark. For copies of the EC
Declaration of Conformity, contact:
Eaton Power Quality Oy
Koskelontie 13
FIN-02920 Espoo
Finland
Phone: +358-9-452 661
Fax: +358-9-452 665 68
Eaton, Powerware, and ABM are registered trademarks of Eaton Corporation or its subsidiaries and affiliates. AIX is
a registered trademark of International Business Machines Corporation. Linux is a registered trademark of Linus
Torvalds. Microsoft and Windows are registered trademarks of Microsoft Corporation in the United States and other
countries. National Electrical Code and NEC are registered trademarks of National Fire Protection Association, Inc.
All other trademarks are property of their respective companies.
ECopyright 2011 Eaton Corporation, Raleigh, NC, USA. All rights reserved. No part of this document may be
reproduced in any way without the express written approval of Eaton Corporation.
Class A EMC Statements
FCC Part 15
NOTE This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to
part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference
when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate
radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful
interference in which case the user will be required to correct the interference at his own expense.
ICES-003
This Class A Interference Causing Equipment meets all requirements of the Canadian Interference Causing
Equipment Regulations ICES‐003.
Cet appareil numérique de la classe A respecte toutes les exigences du Reglement sur le matériel brouilleur du
Canada.
IEC 62040-2
Some configurations are classified under IEC 62040-2 as “Class‐A UPS for Unrestricted Sales Distribution.” For
these configurations, the following applies:
WARNING This is a Class A‐UPS Product. In a domestic environment, this product may cause radio interference, in
which case, the user may be required to take additional measures.
VCCI Notice
Special Symbols
The following are examples of symbols used on the UPS or accessories to alert you to important
information:
RISK OF ELECTRIC SHOCK - Observe the warning associated with the risk of electric
shock symbol.
CAUTION: REFER TO OPERATOR'S MANUAL - Refer to your operator's manual for
additional information, such as important operating and maintenance
instructions.
This symbol indicates that you should not discard the UPS or the UPS batteries
in the trash. This product contains sealed, lead‐acid batteries and must be
disposed of properly. For more information, contact your local recycling/reuse or
hazardous waste center.
This symbol indicates that you should not discard waste electrical or electronic
equipment (WEEE) in the trash. For proper disposal, contact your local
recycling/reuse or hazardous waste center.
Eaton 9910 UPS and EBM User's Guide S P-164000005 Rev 2
i
Table of Contents
1 Introduction 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Features 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
UPS Rear Panels 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 Safety Warnings 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3 Installation 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4 Operation 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Control Panel 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operating Modes 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Normal Mode 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Battery Mode 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Bypass Mode 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Standby Mode 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Turning on the UPS 22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Starting the UPS on Battery 22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Turning off the UPS 22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Display Functions 22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System Status 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Alarm History 24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Meters 24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Control Screens 24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Model Information 25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configuration 26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Transferring the UPS between Modes 29. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Transferring from Normal to Bypass Mode 29. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Transferring from Bypass to Normal Mode 29. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Retrieving the Alarm History 29. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Behavior on Overload 30. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configuring Load Segments 31. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Controlling Load Segments through the LCD 31. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configuring Automatic Start Delay 31. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configuring Automatic on Battery Shutdown 32. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TABLE OF CONTENTS
Eaton 9910 UPS and EBM User's Guide S P-164000005 Rev 2
ii
Configuring Battery Settings 33. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configuring the UPS for an EBM 33. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Running Automatic Battery Tests 34. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configuring Automatic Battery Tests 35. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configuring Automatic Restart 35. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5 Communication Features 37. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
UPS Manager Software 37. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Communication Ports 38. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
USB Port 38. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
RS-232 Port 39. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Communication Cards 40. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6 UPS Maintenance 41. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
UPS and Battery Care 41. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Storing the UPS and Batteries 41. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Replacing the Internal Batteries (3000 VA Models) 42. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Replacing the Internal Batteries (6000 VA Models) 46. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Testing the Battery 50. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Recycling the Used Battery or UPS 51. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7 Specifications 53. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8 Troubleshooting 57. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Silencing the Alarm 57. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Types of Alarms 57. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Accessing Alarms and Conditions 58. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System Status Menu 58. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Alarm History Menu 59. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Serial Connection to a Computer 59. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Typical Alarms and Conditions 62. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Eaton 9910 UPS and EBM User's Guide S P-164000005 Rev 2
1
Chapter 1 Introduction
The Eaton
®
9910 uninterruptible power supply (UPS) is designed to
prevent blackouts, brownouts, sags, and surges from reaching your
servers and other valuable electronic equipment. The UPS filters small
utility line fluctuations and isolates your equipment from large
disturbances by internally disconnecting from the utility line. The UPS
provides continuous power from its internal battery until the utility line
returns to safe levels or the battery is fully discharged.
Features
Providing outstanding performance and reliability, the Eaton 9910's
unique benefits include the following:
S ABM
®
technology that uses advanced battery management to
increase battery service life, optimize recharge time, and provide a
warning before the end of useful battery life.
S Extended runtime with an optional Extended Battery Module (EBM).
S Start‐on‐battery capability for powering up the UPS even if utility
power is not available.
S Hot‐swappable batteries that simplify maintenance by allowing you to
replace them safely without powering down the critical load.
S Emergency shutdown control through the remote emergency
power-off (REPO) port.
S A standard USB port and RS-232 port.
S A communication bay for optional cards (Network Management Card
or Relay-Serial Card) with enhanced communication capabilities for
increased power protection and control.
S Advanced power management software for graceful shutdowns and
power monitoring.
S Sequential shutdown and load management through separate
receptacle groups, called load segments.
S Backed by worldwide agency approvals.
INTRODUCTION
Eaton 9910 UPS and EBM User's Guide S P-164000005 Rev 2
2
UPS Rear Panels
Figure 1 through Figure 4 show the Eaton 9910 UPS rear panels.
NOTE The shaded areas shown in the following figures indicate the load segment
groupings. The shading does not appear on the cabinet.
NOTE The illustrations in this document might differ slightly from your hardware.
REPO
EBM connector
Communication bay
Figure 1. The 9910-E35 UPS Rear Panel
REPO
EBM connector
Communication bay
Figure 2. The 9910-E36 UPS Rear Panel
INTRODUCTION
Eaton 9910 UPS and EBM User's Guide S P-164000005 Rev 2
3
A
L630P
Input plug
Fan
Ground
screw
REPO
Communication
bay
USB
connector
RS232
connector
Two NEM L630R
receptacles
(Load segment 2)
EBM connector
Output
circuit breakers
Four IEC 320C19
receptacles (Load segment 1)
Figure 3. The 9910-E66 UPS Rear Panel
connector
L630P
Communication
bay
USB
connector
RS232
connector
REPO
Ground
screw
P
FanSix IEC 320C13
receptacles
(Load segment 2)
Output
circuit
breaker
EBM connector
Output
circuit
breakers
Four IEC 320C19
receptacles
(Load segment 1)
L630
inlet
Figure 4. The 9910-E67 UPS Rear Panel
INTRODUCTION
Eaton 9910 UPS and EBM User's Guide S P-164000005 Rev 2
4
NOTE (9910-E67 model only) Purchase a detachable power supply cord. Eaton
recommends a Type SJT, 10 AWG/3C, 105°C, 1.8–4.5m long, grounded NEMA L6-50P to
grounded NEMA L6-30R.
Eaton 9910 UPS and EBM User's Guide S P-164000005 Rev 2
5
Chapter 2 Safety Warnings
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions that you should follow during installation and
maintenance of the UPS and batteries. Please read all instructions before operating the
equipment and save this manual for future reference.
D A N G E R
This UPS contains LETHAL VOLTAGES. All repairs and service should be performed by
AUTHORIZED SERVICE PERSONNEL ONLY. There are NO USER SERVICEABLE PARTS
inside the UPS.
W A R N I N G
S This UPS contains its own energy source (batteries). The UPS output may carry live
voltage even when the UPS is not connected to an AC supply.
S To reduce the risk of fire or electric shock, install this UPS in a temperature and humidity
controlled, indoor environment, free of conductive contaminants. Ambient temperature
must not exceed 40°C (104°F). Do not operate near water or excessive humidity
(90% maximum).
S To reduce the risk of fire, connect only to a circuit provided with branch circuit
overcurrent protection in accordance with the National Electrical Code
®
(NEC
®
),
ANSI/NFPA 70, or your local electrical code:
Model Overcurrent Protection
9910-E35, 9910-E36 20A
9910-E66 30A
9910-E67 40A
S Output overcurrent protection and disconnect switch must be provided by others.
S To comply with international standards and wiring regulations, the sum of the leakage
current of the UPS and the total equipment connected to the output of this UPS must not
have an earth leakage current greater than 3.5 milliamperes.
S If the UPS requires any type of transportation, disconnect the internal UPS batteries
before transporting.
SAFETY WARNINGS
Eaton 9910 UPS and EBM User's Guide S P-164000005 Rev 2
6
C A U T I O N
S Servicing of batteries should be performed or supervised by personnel knowledgeable
about batteries and the required precautions. Keep unauthorized personnel away from
batteries.
S Batteries can present a risk of electrical shock or burn from high short-circuit current. The
following precautions should be observed: 1) Remove watches, rings, or other metal
objects; 2) Use tools with insulated handles; 3) Wear rubber gloves and boots; 4) Do not
lay tools or metal parts on top of batteries; 5) Disconnect the charging source prior to
connecting or disconnecting battery terminals.
S Determine if the battery is inadvertently grounded. If inadvertently grounded, remove the
utility source from the ground. Contact with any part of a grounded battery can result in
electrical shock. The likelihood of such shock can be reduced if such grounds are
removed during installation and maintenance (applicable to equipment and remote
battery supplies not having a grounded supply circuit).
S Proper disposal of batteries is required. Refer to your local codes for disposal
requirements.
S Never dispose of batteries in a fire. Batteries may explode when exposed to flame.
S Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the
skin and eyes and may be extremely toxic.
S Replace batteries with the same number and type of batteries as originally installed in
the UPS.
S For PLUGGABLE EQUIPMENT, the power outlet shall be installed near the equipment and
shall be easily accessible.
S The UPS may be connected to a maximum of one Extended Battery Module (EBM).
SAFETY WARNINGS
Eaton 9910 UPS and EBM User's Guide S P-164000005 Rev 2
7
Consignes de sécurité
CONSIGNES DE SÉCURITÉ IMPORTANTES
CONSERVER CES INSTRUCTIONS
Ce manuel comporte des instructions importantes que vous êtes invité à suivre lors de toute
procédure d'installation et de maintenance des batteries et de l'onduleur. Veuillez consulter
entièrement ces instructions avant de faire fonctionner l'équipement et conserver ce manuel
afin de pouvoir vous y reporter ultérieurement.
D A N G E R !
Cet onduleur contient des TENSIONS MORTELLES. Toute opération d'entretien et de
réparation doit être EXCLUSIVEMENT CONFIÉE A UN PERSONNEL QUALIFIÉ AGRÉÉ.
AUCUNE PIÈCE RÉPARABLE PAR L'UTILISATEUR ne se trouve dans l'onduleur.
A V E R T I S S E M E N T !
S Cette onduleur possède sa propre source d'alimentation (batteries). Il est possible que la
sortie de l'onduleur soit sous tension même lorsque l'onduleur n'est pas connectée à une
alimentation CA.
S Pour réduire les risques d'incendie et de décharge électrique, installer l'onduleur
uniquement à l'intérieur, dans un lieu dépourvu de matériaux conducteurs, où la
température et l'humidité ambiantes sont contrôlées. La température ambiante ne doit
pas dépasser 40 °C. Ne pas utiliser à proximité d'eau ou dans une atmosphère
excessivement humide (95 % maximum).
S Afin de réduire le risque d'incendie, connectez seulement à un circuit équipé d'un
dispositif de protection divisionnaire avec un ampérage conforme à votre code électrique
local :
Modèle Protection de surintensité
9910-E35, 9910-E36 20A
9910-E66 30A
9910-E67 40A
S La protection de surintensité de sortie ainsi que le sectionneur doivent être fournis par
des tiers.
S Afin d'être conforme aux normes et règlements internationaux de câblage, le courant de
fuite à la terre de la totalité du matériel branché sur la sortie de l'onduleur ne doit pas
dépasser 3,5 mA.
S Si l'onduleur doit être transporté, débranchez les batteries internes de l'onduleur avant le
transport.
SAFETY WARNINGS
Eaton 9910 UPS and EBM User's Guide S P-164000005 Rev 2
8
A T T E N T I O N !
S La réparation des batteries doit être réalisée ou supervisée par un personnel connaissant
les batteries et les précautions requises. Maintenez le personnel non autorisé éloigné
des batteries.
S Les batteries peuvent présenter un risque de choc électrique ou de brûlure provenant
d'un courant de court-circuit élevé. Les précautions suivantes doivent être respectées :
1) Retirez les montres, bagues ou autres objets métalliques ; 2) Utilisez des outils avec
des poignées isolées ; 3) Portez des gants et des bottes en caoutchouc ; 4) Ne laissez pas
d'outils ou de pièces métalliques sur les batteries ; 5) Déconnectez la source de charge
avant de connecter ou de déconnecter des bornes de batterie.
S Déterminez si la batterie est mise à la terre par mégarde. Si elle est mise à la terre par
mégarde, retirez la source secteur de la terre. Le contact avec toute pièce d'une batterie
mise à la masse peut provoquer un choc électrique. La probabilité d'un tel choc peut être
réduite si de telles mises à la terre sont retirées pendant l'installation et la maintenance
(applicables aux alimentations de batterie de l'équipement et distante n'ayant pas un
circuit d'alimentation relié à la terre).
S Une mise au rebut réglementaire des batteries est obligatoire. Consulter les règlements
en vigueur dans votre localité.
S Ne jamais jeter les batteries au feu. L'exposition aux flammes risque de les faire
exploser.
S N'ouvrez pas ou ne détériorez pas la ou les batteries. L'électrolyte relâché est nocif pour
la peau et les yeux et peut être extrêmement toxique.
S Remplacez les batteries par des batteries de même type et en même nombre que celles
installées à l'origine dans l'onduleur.
S Pour un ÉQUIPEMENT ENFICHABLE, la prise de courant doit être installée près de
l'équipement et facilement accessible.
S L'onduleur peut être connecté au maximum à un Module de batterie externe (EBM).
SAFETY WARNINGS
Eaton 9910 UPS and EBM User's Guide S P-164000005 Rev 2
9
Sicherheitswarnungen
WICHTIGE SICHERHEITSANWEISUNGEN
AUFBEWAREN
Dieses Handbuch enthält wichtige Anweisungen, die Sie während der Installation und
Wartung des USV (Unterbrechungsfreies Stromversorgungssystem) und der Batterien
befolgen müssen. Bitte lesen Sie alle Anweisungen des Handbuches bevor sie mit dem
Gerät arbeiten. Bewaren Sie das Handbuch zum Nachlesen auf.
W A R N U N G
Die USV führt lebensgefährliche Spannungen. Alle Reparatur- und Wartungsarbeiten sollten
nur von Kundendienstfachleuten durchgeführt werden. Die USV enthält keine vom Benutzer
zu wartenden Komponenten.
A C H T U N G
S Dieses USV (Unterbrechungsfreies Stromversorgungssystem) enthält eine eigene
Energiequelle (Batterien). Der USV-Ausgang kann Spannung führen, auch wenn das USV
nicht an eine Wechselstromquelle angeschlossen ist.
S Um die Brand‐ oder Elektroschockgefahr zu verringern, diese USV nur in Gebäuden mit
kontrollierter Temperatur und Luftfeuchtigkeit installieren, in denen keine leitenden
Schmutzstoffen vorhanden sind. Die Umgebungstemperatur darf 40°C nicht übersteigen.
Die USV nicht in der Nähe von Wasser oder in extrem hoher Luftfeuchtigkeit (max. 95 %)
betreiben.
S Zur Vermeidung von Brandgefahr sollte das Gerät nur an einen Stromkreis
angeschlossen werden, der mit einem Überstromschutz mit einem Nennstrom gemäß
Ihren örtlichen Elektrizitätsvorschriften ausgestattet ist:
Modell Überstromschutz
9910-E35, 9910-E36 20A
9910-E66 30A
9910-E67 40A
S Der Ausgangs-Überlaststromschutz und der Trennschalter müssen von anderen
Herstellern geliefert werden.
S Um internationale Normen und Verdrahtungsvorschriften zu erfüllen, dürfen die an den
Ausgang dieser USV angeschlossenen Geräte zusammen einen Erdableitstrom von
insgesamt 3,5 Milliampere nicht überschreiten.
S Muss die USV transportiert werden, so müssen die internen USV-Batterien vor dem
Transport vom Gerät getrennt werden.
SAFETY WARNINGS
Eaton 9910 UPS and EBM User's Guide S P-164000005 Rev 2
10
V O R S I C H T !
S Die Wartung der Batterien sollte unter Befolgung der erforderlichen
Sicherheitsvorkehrungen durch fachkundiges Personal erfolgen oder beaufsichtigt
werden. Nicht ausreichend geschultem Personal ist der Zugang zu den Batterien zu
verwehren.
S Batterien bergen das Risiko eines elektrischen Schlages oder einer Verletzung durch
hohen Kurzschlussstrom. Bitte befolgen Sie die folgenden Sicherheitsvorkehrungen:
1) Nehmen Sie Uhren, Ringe und andere Metallgegenstände ab. 2) Verwenden Sie
Werkzeug mit isoliertem Handgriff. 3) Tragen Sie Gummihandschuhe und Gummistiefel.
4) Legen Sie keine Werkzeuge oder Metallteile auf die Batterien. 5) Trennen Sie die
Aufladequelle vor dem Anschließen oder Trennen der Batterieklemmen.
S Ermitteln Sie, ob die Batterie unbeabsichtigt geerdet ist. Im Falle der unbeabsichtigten
Erdung ist die Netzstromquelle von der Erdung zu entfernen. Durch Berührung von
geerdeten Batterieteilen kann ein elektrischer Schlag verursacht werden. Die
Wahrscheinlichkeit eines solchen Schlages kann verringert werden, wenn derartige
Erdungen bei der Installation und Wartung aufgehoben werden (dies gilt für Geräte und
Remote-Batterieversorgungen ohne geerdeten Versorgungsschaltkreis).
S Die Batterien müssen ordnungsgemäß entsorgt werden. Hierbei sind die örtlichen
Bestimmungen zu beachten.
S Batterien niemals verbrennen, da sie explodieren können.
S Öffnen oder manipulieren Sie die Batterien nicht anderweitig. Auslaufende Batteriesäure
ist schädlich für Haut und Augen und kann hochgiftig sein.
S Ersetzen Sie die Batterie mit einer Batterie des gleichen Typs und in der gleichen Anzahl
sie ursprünglich in der USV installiert.
S Bei AN EINESTECKDOSE ANSCHLOSSENEN GERÄTEN muss sich die Netzsteckdose in
der Nähe des Gerätes befinden und einfach zugänglich sein.
S Die USV darf maximal an ein Externes Batteriemodul (EBM) angeschlossen werden.
SAFETY WARNINGS
Eaton 9910 UPS and EBM User's Guide S P-164000005 Rev 2
11
Regulamentos de Segurança
INSTRUÇÕES DE SEGURANÇA IMPORTANTES
GUARDE ESTAS INSTRUÇÕES
Este manual contém instruções importantes que devem ser seguidas durante a instalação e
manutenção do no-break e das baterias. Leia todas as instruções antes de operar o
equipamento e guarde este manual para consultá-lo futuramente.
C U I D A D O
A UPS contém VOLTAGEM MORTAL. Todos os reparos e assistência técnica devem ser
executados SOMENTE POR PESSOAL DA ASSISTÊNCIA TÉCNICA AUTORIZADO. Não há
nenhuma PEÇA QUE POSSA SER REPARADA PELO USUÁRIO dentro da UPS.
A D V E R T Ê N C I A
S Este no-break possui sua própria fonte de energia (baterias). A saída do no-break pode
estar energizada mesmo que este não esteja conectado a uma fonte de energia elétrica.
S Para reduzir o risco de incêndios ou choques elétricos, instale a UPS em ambiente
interno com temperatura e umidade controladas e livres de contaminadores condutíveis.
A temperatura ambiente não deve exceder 40°C. Não opere próximo a água ou em
umidade excessiva (máx: 90%).
S Para reduzir o risco de incêndio, conecte apenas em um circuito que tenha proteção de
corrente com classificação de amperagem de acordo com seu código elétrico local:
Modelo Proteção da sobrecarga
9910-E35, 9910-E36 20A
9910-E66 30A
9910-E67 40A
S A proteção contra a sobretensão de saída e o disjuntor deve ser fornecida por terceiros.
S Para estar de acordo com os padrões internacionais e os regulamentos de fiação, o
equipamento total conectado à saída desta UPS não deve ter uma corrente de fuga à
terra maior que 3,5 miliampères.
S Se o UPS precisar de qualquer tipo de transporte, desconecte as baterias internas do
UPS antes de transportar.
SAFETY WARNINGS
Eaton 9910 UPS and EBM User's Guide S P-164000005 Rev 2
12
P E R I G O
S O serviço na bateria deve ser feito ou supervisionado por funcionários com conhecimento
de baterias e das precauções necessárias. Mantenha funcionários não autorizados longe
das baterias.
S As baterias podem apresentar um risco de choque elétrico ou queimadura do calor de
curto circuito. As seguintes precauções devem ser observadas: 1) Remova relógios, anéis
ou outros objetos de metal; 2) Use ferramentas com manoplas isoladas; 3) Use luvas e
botas de borracha; 4) Não deixe ferramentas ou peças de metal sobre as baterias;
5) Desconecte a fonte de carga antes de conectar ou desconectar os terminais da
bateria.
S Determine se a bateria está aterrada inadvertidamente. Se aterrada inadvertidamente,
remova a fonte utilitária do aterramento. Tocar qualquer parte de uma bateria aterrada
pode resultar em choque elétrico. A possibilidade de choque elétrico pode ser reduzida
se estes aterramentos forem removidos durante a instalação e manutenção (aplicável ao
equipamento e baterias remotas sem circuito de aterramento).
S Siga as instruções apropriadas ao desfazer‐se das baterias. Consulte os códigos do local
para maiores informações sobre os regulamentos de descarte de produtos.
S Nunca jogue as baterias no fogo, porque há risco de explosão.
S Não abra ou mutile a bateria ou baterias. A liberação de eletrolite é perigosa para a pele
e olhos e pode ser extremamente tóxica.
S Troque as baterias com baterias do mesmo número e tipo que as originais instaladas no
UPS.
S Para EQUIPAMENTO PLUGÁVEL, a tomada de energia deve ser instalada perto do
equipamento e deve ser de fácil acesso.
S O UPS pode ser conectado no máximo em um Módulo Externo de Bateria (EBM).
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76

Eaton 9910 User manual

Category
Uninterruptible power supplies (UPSs)
Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI