Overview
The RCSN422 code converter converts SensorNet
to RS-422. The converter supports the ADTT16E
controller and MegaPower LT matrix switcher.
Installation
The converter can be placed on a tabletop, or
installed in a rack, under a shelf, or on a wall.
Parts Supplied
Install Kit 0351-1635-01, which includes:
Mounting Bracket (2)
Screw, PHP, M3x8 (4)
Connector, RS-422, 3.5mm, 1x5 (7)
Connector, Power, 5.06mm, 1x3 (1)
Connector, RS-485, 5.06mm, 1x2 (1)
Cable, 16.5ft, 24Vac, 3 Cond., 18AWG (1)
© 2005 Sensormatic Electronics Corporation
Rack Mount
S
e
n
s
o
r
N
e
t
t
o
R
S
4
2
2
C
o
n
v
e
r
t
e
r
Under-Shelf Mount
S
e
n
s
o
r
N
e
t
t
o
R
S
4
2
2
C
o
n
v
e
r
t
e
r
Wall Mount
M3x8 Screws (supplied)
M3x8 Screws (supplied)
M3x8 Screws (supplied)
SENSORNET TO RS-422 CODE CONVERTER 8000-2593-01, REV. C
INSTALLATION GUIDE
2 of 7
Indicators, Connections, and Settings
µP 485 422
~
Front Panel (left to right)
Reset Recessed button used to reset the
code converter (use a paperclip).
Green LED indicates 24Vac is applied.
µP Green LED blinks when processor in
code converter is operating.
485 Green LED shows SensorNet activity:
Off indicates no activity
On indicates network is active with
valid data
Blinks when unit is answering polls.
Red, noise LED lights for 0.5s. Usually
indicates invalid frame lengths or noise
on the line.
422 Green LED blinks to indicate that at
least one RS-422 device is responding
to polls.
Blinks twice when unit is reset or
powered up
First blink indicates a successful
ROM check; second blink indicates
a successful RAM check
LED illuminates continuously when
either check fails, stopping the test
Remains illuminated during
program load.
Rear Panel (left to right)
422 Ports
(Seven)
Each port receives a RS-422 cable
from a dome camera or RJ-860AP
J-Box. An RS-422 line test switch and
LED are adjacent to each port.
LED
Test Switch
Pinouts:
Pin 1 – RXHI+
Pin 2 – RXLO-
Pin 3 – TXHI+
Pin 4 – TXLO-
Pin 5 – Ground
485 Port Receives a SensorNet (RS-485) cable
from the ADTT16E or MegaPower LT.
Terminate
Switch
Set to left (terminated)
Set to right (unterminated)
Address
Switches
x10
x1
Use address 00 for the loopback test
(see page 4).
If MiniDomes are used, set the device
address to 16. If SpeedDomes are
used, set the device address to 32.
24Vac
Connector
Receives 24Vac from a transformer.
Pinouts:
Pin 1 – AC or common
Pin 2 – Ground
Pin 3 – 24Vac
Front
Rear
Pin 1
Pin 1
SENSORNET TO RS-422 CODE CONVERTER 8000-2593-01, REV. C
INSTALLATION GUIDE
3 of 7
Specifications
Electrical
Primary input .............. 110-120, 200-240Vac @ 50-60Hz
RS-422 Converter Input from Transformer
Primary input ...................................... 24Vac @ 50-60Hz
Power consumption ......................................... 20W max.
Allowable line drop.................................................150ms
Environmental
Operating temperature:.............0° to 50°C (32° to 122°F)
Relative humidity: .................... 0 to 90% non-condensing
Mechanical
Height ...................................................... 38.5mm (1.5in)
Width .......................................................435mm (17.1in)
Depth ........................................................ 129mm (5.1in)
Weight ......................................................1.5kg (3.3 lbs.)
Declarations
Regulatory Compliance
REG ID: RS422
EMC........................................................47 CFR, Part 15
ICES-003
EN55022 (CE)
Immunity ................................................ EN50082-1 (CE)
Safety ......................................................... UL 1950 (UL)
cUL CSA C22.2 No. 950
EN 60950 (CE)
FCC COMPLIANCE: This equipment complies with Part 15 of the
FCC rules for intentional radiators and Class A digital devices when
installed and used in accordance with the instruction manual.
Following these rules provides reasonable protection against harmful
interference from equipment operated in a commercial area. This
equipment should not be installed in a residential area as it can radiate
radio frequency energy that could interfere with radio
communications, a situation the user would have to fix at their own
expense.
EQUIPMENT MODIFICATION CAUTION: Equipment changes
or modifications not expressly approved by Sensormatic Electronics
Corporation, the party responsible for FCC compliance, could void the
user's authority to operate the equipment and could create a hazardous
condition.
WARNING! North America power requirements: In North America,
this device is intended to be supplied from a Class 2 power supply.
This installation should be made by a qualified service person and
should conform to all local codes.
WARNING! EU power requirements: This product runs on 24Vac. In
the EU, it is intended to be powered from a Limited Power Source. A
limited power source is a certified source of SELV, and if inherently
limited, with 8 amps maximum output current, and a maximum of
100VA available; or if not inherently limited, fused with a maximum
value of 3.3 Amps, meeting section 2.11 of IEC950, and a maximum
of 250VA available. The power supply can be obtained through
American Dynamics or through another source where the provider can
furnish the verification. This is required to assure electrical safety in
the product.
Stromanforderungen in der EU: Dieses Produkt wird mit 24 V
Wechselstrom betrieben. In der EU ist es für den Betrieb durch eine
begrenzte Stromquelle vorgesehen. Eine begrenzte Stromquelle ist
eine zertifizierte SELV-Quelle (Schutzkleinspannung), bei inhärenter
Begrenzung mit einem maximalen Ausgangsstrom von 8 A und 100
VA maximaler Verfügbarkeit, bei nicht inhärenter Begrenzung mit
einer maximalen Sicherung von 3,3 A gemäß Abschnitt 2.11 der
IEC950 und 250 VA maximaler Verfügbarkeit. Das Netzteil kann über
American Dynamics oder eine andere Quelle bezogen werden, wobei
der Anbieter den Nachweis der Konformität bereitstellen sollte. Dies
ist zur Gewährleistung der elektrischen Sicherheit des Produktes
erforderlich.
Other Declarations
Thank you for using American Dynamics products. We support our
products through an extensive and worldwide network of dealers. The
dealer, through whom you originally purchased this product, is your
point of contact if you have a need for service or support. Our dealers
are fully empowered to provide the very best in customer service and
support. Dealers should contact American Dynamics at
(800) 507-6268 or (561) 912-6259 or on the web at
www.americandynamics.net.
WARRANTY DISCLAIMER: Sensormatic Electronics Corporation
makes no representation or warranty with respect to the contents
hereof and specifically disclaims any implied warranties of
merchantability or fitness for any particular purpose.
NOTICE: The information in this manual was current when
published. The manufacturer reserves the right to revise and improve
its products. All specifications are therefore subject to change without
notice.
LIMITED RIGHTS NOTICE: For units of the Department of
Defense, all documentation and manuals were developed at private
expense and no part of it was developed using Government Funds.
The restrictions governing the use and disclosure of technical data
marked with this legend are set forth in the definition of “limited
rights” in paragraph (a) (15) of the clause of DFARS 252.227.7013.
Unpublished - rights reserved under the Copyright Laws of the United
States.
TRADEMARK NOTICE: American Dynamics and Sensormatic are
trademarks or registered trademarks of Sensormatic Electronics
Corporation. Other product names mentioned herein may be
trademarks or registered trademarks of Sensormatic or other
companies.
COPYRIGHT: Under copyright laws, the contents of this manual
may not be copied, photocopied, reproduced, translated or reduced to
any electronic medium or machine-readable form, in whole or in part,
without prior written consent of Sensormatic Electronics.
MDR 8/05
www.americandynamics.net
SENSORNET TO RS-422 CODE CONVERTER 8000-2593-01, REV. C
INSTALLATION GUIDE
4 of 7
Troubleshooting
The converter's front-panel LEDs indicate when
activity occurs during operation. They also identify
many errors that could occur:
422 LED on
steadily
ROM checksum or RAM
read/write failure. Reload
software from host.
(noise) LED
flashes randomly
Indicates SensorNet
transmission errors.
485 LED off No SensorNet protocol detected.
LED Off
No power.
µP LED flashes
rapidly
Code converter in loopback test.
Addendums
Addendum A:
Performing a SensorNet Ping Test on a
Dome Camera
To conduct a ping test from the controller to a
dome, select the dome camera and run the test
(described in the appropriate operator manual).
Note:
- Address selected at the controller determines
the dome camera tested.
- Dome address switch settings must be correct.
- The code converter responds to pings if the
dome is responding.
- If the code converter is selected, only the
communication line from the controller to the
converter is tested.
- For how to get dome information and to conduct
the ping test from the controller, refer to
ADTT16E (8200-0306-02) and VM16 (8000-
2653-01) operation instructions. For just the
ping test, refer to MegaPower LT operation
instructions (MP-LTHB-1).
Note: If a controller requests device information
from a camera having the same address as the
converter, the controller receives configuration
information from the converter instead of the dome.
Addendum B:
Performing an RS-422 Line Test
For each RS-422 port: Press and hold the port’s
line status test switch and view the adjacent LED.
The LED lights as follows:
Constant green,
Blinking red
RS-422 line correctly wired.
Constant green,
No red
"Data In" – shorted to ground.
Constant red,
Blinking green
"Data In" + and – wires
reversed.
Blinking red,
Green off
"Data In" + shorted to ground.
Both LEDs off "Data In" + and – wires shorted
or open.
Addendum C:
Resetting the Code Converter
If communications cease, press the reset switch on
the front panel using a paper clip. If that fails, try
recycling power.
Addendum D:
Performing an RS-422 Loopback Test
1. Disconnect data lines from all seven RS-422
connectors.
2. Wire each connector’s pins as follows:
Pin 1 white wire (RX+) loops to Pin 3 (TX+)
Pin 2 gray wire (RX–) loops to Pin 4 (TX–)
3. Set the code converter to address 00.
4. Press the RS-422 line test switch to the right of
the port.
5. If the LED adjacent top the port lights, that port
is working. If the LED remains off, the port is not
working.
6. Repeat steps 4 and 5 for the next port.
SENSORNET TO RS-422 CODE CONVERTER 8000-2593-01, REV. C
INSTALLATION GUIDE
5 of 7
Addendum E: ADTT16E to RCSN422 Installation Wiring
J
3
J
1
J
2
0
3
0
0
-
1
0
0
0
-
0
1
E
I
M
D
B
9
R
J
4
5
6
0
0
3
-
0
0
4
7
-
0
1
0
1
0
0
-
2
3
2
4
-
0
3
S
e
n
s
o
r
N
e
t
S
e
n
s
o
r
N
e
t
2
4
V
a
c
G
n
d
.
2
4
V
a
c
A
D
T
T
1
6
E
T
O
U
C
H
T
R
A
C
K
E
R
2
4
v
a
c
2
4
v
a
c
g
n
d
1
2
3
4
5
6
7
8
9
10
11
12
RJ860AP
J-BOX
TX+ TX–
RX+
RX
RS-422
J1 J2 J3 J4 J5
J6 J7 J8 J9 J10
RL-860-AP
J-Box
To
MiniDome
To Unicard
SpeedDome
To
Optima
To
Optima LT
To SpeedDome Ultra
Pigtail
To SpeedDome Ultra
I/O
J1–10 J5 P3 P1 P7
Pin 1 (TX+) Pin 1 (RX+) Pin 7 (RX+) Pin 1 (RX+) Pin 1 (RX+) Pin 6 (RX+) Pin 1 (RX+)
Pin 2 (TX–) Pin 2 (RX–) Pin 6 (RX–) Pin 2 (RX–) Pin 2 (RX–) Pin 7 (RX–) Pin 2 (RX–)
Pin 3 (AC) Pin 3 (AC) Pin 3 (AC) (AC) (AC) Pin 3 (AC) Pin 3 (AC)
Pin 4 (GND) Pin 4 (GND) Pin 4 (GND) (GND) (GND) Pin 4 (GND) Pin 4 (GND)
Pin 5 (AC) Pin 5 (AC) Pin 5 (AC) (AC) (AC) Pin 5 (AC) Pin 5 (AC)
Pin 6 (N/A)
Pin 7 (RX–) Pin 7 (TX–) Pin 1 (TX–) Pin 4 (TX–) Pin 9 (TX–) Pin 4 (TX–)
Pin 8 (RX+) Pin 8 (TX+) Pin 2 (TX+) Pin 3 (TX+) Pin 8 (TX+) Pin 3 (TX+)
Code Converter
SENSORNET TO RS-422 CODE CONVERTER 8000-2593-01, REV. C
INSTALLATION GUIDE
6 of 7
Addendum E: MegaPower LT to RCSN422 Installation Wiring
2
4
v
a
c
2
4
v
a
c
g
n
d
1
2
3
4
5
6
7
8
9
10
11
12
RJ860AP
J-BOX
TX+ TX
RX+
RX–
RS-422
J1 J2 J3 J4 J5
J6 J7 J8 J9 J10
RL-860-AP
J-Box
To
MiniDome
To Unicard
SpeedDome
To
Optima
To
Optima LT
To SpeedDome Ultra
Pigtail
To SpeedDome Ultra
I/O
J1–10 J5 P3 P1 P7
Pin 1 (TX+) Pin 1 (RX+) Pin 7 (RX+) Pin 1 (RX+) Pin 1 (RX+) Pin 6 (RX+) Pin 1 (RX+)
Pin 2 (TX–) Pin 2 (RX–) Pin 6 (RX–) Pin 2 (RX–) Pin 2 (RX–) Pin 7 (RX–) Pin 2 (RX–)
Pin 3 (AC) Pin 3 (AC) Pin 3 (AC) (AC) (AC) Pin 3 (AC) Pin 3 (AC)
Pin 4 (GND) Pin 4 (GND) Pin 4 (GND) (GND) (GND) Pin 4 (GND) Pin 4 (GND)
Pin 5 (AC) Pin 5 (AC) Pin 5 (AC) (AC) (AC) Pin 5 (AC) Pin 5 (AC)
Pin 6 (N/A)
Pin 7 (RX–) Pin 7 (TX–) Pin 1 (TX–) Pin 4 (TX–) Pin 9 (TX–) Pin 4 (TX–)
Pin 8 (RX+) Pin 8 (TX+) Pin 2 (TX+) Pin 3 (TX+) Pin 8 (TX+) Pin 3 (TX+)
SensorNet from
MegaPower LT
Matrix Switcher
Code Converter
SENSORNET TO RS-422 CODE CONVERTER 8000-2593-01, REV. C
INSTALLATION GUIDE
7 of 7
Addendum F: Flashing Firmware on the RCSN422 Using an ADCASNET Module
Procedure
1. Download and install the ADCASNET utility from http://www.americandynamics.net. Click on
Support/Software Downloads/USB Control Module/USB Control Module Utilities/ADUtils_1_00.zip.
2. Download RCSN422 hex file from the web site and copy it to c:\program files\AD_Utilities (Note: This file
must be F2814-0102 or higher).
3. Set the code converter to address 32.
4. Launch the ADCASNET utility and click “Load Utility”.
5. Click the “Scan Network” icon; the load utility will look for the code converter on the right-hand screen.
6. Once it detects the code converter, the firmware version is displayed. For example: 2814-XXXX.
7. Click on the displayed version and then click “Load Snet Device”. A progress bar appears.
8. When complete, close the ADCASNET utility and reboot the code converter.
9. Rescan the code converter and verify firmware was updated.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7

American Dynamics RCSN422 Installation guide

Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI