BOMBARDIER SD3-60 Maintenance Manual

Type
Maintenance Manual
Jun 30/01
21-00-00
Page 1
EFFECTIVITY:
All
z
SD3-60 AIRCRAFT MAINTENANCE MANUAL
AMM21-00-00 1.0.0.0AIR CONDITIONING - DESCRIPTION AND OPERATION
1. General
Refer to Figure 1.
A single air conditioning system supplies conditioned air to the flight and passenger
compartments with separate temperature control for each.
The system derives its hot air from bleeds on both engines but will continue to work, with reduced
performance on a supply from one engine only.
2. Bleed air conditioning
Refer to Figure 1. Refer to Figure 2 (Sheet 1).
Bleed air is taken via fixed orifices from the P2.5 and P3 bleed connections on each engine. At
low power settings, when the P3 bleed pressure is below 35 p.s.i.g., the temperature control
valve (TCV) is fully open admitting P3 bleed air only, to operate the system. At high power
settings, when pressure in the P3 bleed line exceeds 35 p.s.i.g. a pressure switch operates to
initiate modulation control via the solenoid selector valve and temperature sensor (TS), initially
closing the TCV. Due to the absence of P3 pressure, the check valve in the P2.5 bleed line
opens, maintaining system requirements on P2.5 bleed air only. Should the temperature in the
common bleed line fall to below 300° F whilst operating on P2.5 bleed air, a temperature sensor
(TS) will modulate the TCV to open, allowing P3 bleed air to mix with P2.5 thus maintaining the
bleed air temperature above 250° F. To prevent spurious over-pressure warning being caused by
a cold TS, a time delay is included to postpone the opening of the TCV until 10 seconds after the
HA/SOV is selected open.
Downstream of the TS air passes through a hot air shut-off valve (HA/SOV), a venturi and a
check valve to a common line. The check valves in each half system prevent cross-flow between
engines and the dumping of all bleed air, should either duct fracture.
Air in the common line passes to a refrigeration unit consisting of a dual heat exchanger and a
three-wheel air cycle machine (ACM). In the heat exchanger the bleed air is cooled in the primary
section, compressed and then intercooled in the secondary section. The cooling medium in the
heat exchanger is ambient air driven through the heat exchanger by the fan of the ACM. The
NACA inlet for ambient air is located in the fuselage roof fairing. A flap at the top rear is spring-
loaded closed and will open inwards to supplement the supply during static running should the
demands of the ACM cause a partial depression within the fairing. A lip at the rear of the flap (aft
hinge point) provides for aerodynamic assistance of flap closure during flight (in addition to spring
action).
From the secondary section of the heat exchanger, the bleed air is ducted to the turbine inlet and
to one half of a dual bypass valve; the outlets from both units combine and deliver the air to a
water separator. The cooled air from the secondary section expands in the turbine and produces
a low temperature and condensed mixture (fog); it also provides the power to drive the
compressor and the fan. The water separator coalesces the fog into drops which, when
Jun 30/01
21-00-00
Page 2
EFFECTIVITY:
All
z
SD3-60 AIRCRAFT MAINTENANCE MANUAL
collected, are delivered as water to an aspirator which sprays into the cooling air stream of the
heat exchanger.
Beyond the water separator, the ducting divides to provide for the various services detailed in
para 4.
3. Bleed air control, indication and warning
A. HA/SOV control and indication
The left and right motorised HA/SOVs are each controlled by ON/OFF switch modules having
integral line indication of valves open/shut condition on the AIR CONDITIONING panel 9P.
Line indication, which is controlled by 'travel limit' switches within each HA/SOV is provided
by coloured strip lights in the cap of each module. On post-mod A8033 aircraft, indication of
engine bleed point is given by P2.5 (Green letters)/P3 (yellow letters) indicators, one for each
engine.
Power supplies for the left and right control switches are respectively taken from the 28V dc
left shedding busbar and the 28V dc ground services busbar (via 5 amp circuit breakers Nos
90 and 211 on distribution panels 1D and 2D). The power supply for indication is taken from
the 28V dc right essential services busbar via 5 amp circuit breaker No. 196 on distribution
panel 2D.
The HA/SOVs will close automatically in the following contingencies:-
(1) When the Reserve Power System is activated for either engine a supply will be made
available from the relevant reserve power relay to the 'close' field of the HA/SOV on that
side.
(2) Each HA/SOV will close under the influence of its control relay (located on control panel
1C-left, 2C right) should the centre duct temperature exceed 525° F or the centre duct
pressure exceed 35 p.s.i.g.
The initiating circuitry for the control relays is taken from a temperature sensor and an
over-pressure switch situated upstream of the primary heat exchanger in the centre duct.
Jun 30/01
21-00-00
Page 3
EFFECTIVITY:
All
z
SD3-60 AIRCRAFT MAINTENANCE MANUAL
Air Conditioning Schematic
Figure 1
Jun 30/01
21-00-00
Page 4
EFFECTIVITY:
All
z
SD3-60 AIRCRAFT MAINTENANCE MANUAL
When either the temperature or pressure switch settings are exceeded the respective
switch contacts make to:-
(a) illuminate the BLEED air caption on the centralised warning panel and the duct
OVERHEAT or OVER PRESSURE light on panel 9P as appropriate.
(b) energise the control relays which 'lock on' providing a supply to the 'close' field of the
HA/SOV.
NOTE: The system is reset by tripping and resetting circuit breakers Nos 90 and 211 on
respective distribution panels 1D and 2D when warning lights are extinguished i.e.
bleed air temperature or pressure has returned to normal.
B. Spar box overheat warning
A thermostat is located in the centre-wing spar box bay left and right at station 68.80. Should
the ambient temperature at either position rise to 110°C, possibly as a result of a leak in
either the air-conditioning or aerofoil bleed air piping, the contact of the thermostat will close
to illuminate:-
(1) The BLEED caption on the centralised warning panel 1P.
(2) The SPAR BOX OVERHEAT lights on panel 9P and the Anti-icing Services Panel 4P.
Power supplies for operation are taken from the 28V d.c. right essential services busbar,
via C/B No. 196 on distribution panel 2D.
NOTE: Upon receipt of a warning, the crew adopt a drill to determine and isolate the source of
seepage.
C. Duct low pressure warning
Warning of duct low pressure is afforded by three LP switches, two of which sense the
pressure of the bleed air ducting immediately downstream of the venturi in each half system
and the other sensing the pressure in the common (centre) duct upstream of the primary heat
exchanger.
Each switch 'breaks' on a rising pressure not greater than 6 p.s.i.g. and 'makes on' a falling
pressure less than the break pressure but not less than 5 ± 0.25 p.s.i.g.
Power supplies for signalling operation are taken from the 28V d.c. right essential services
busbar via C/B No. 196 on distribution panel 2D.
The LP switch in each half system is wired in parallel with the LP switch in the centre duct
and becomes operational only when the HA/SOV is fully open ie. the valve's limit switch has
tripped (open) providing power to operate the LP circuit control relay.
Jun 30/01
21-00-00
Page 5
EFFECTIVITY:
All
z
SD3-60 AIRCRAFT MAINTENANCE MANUAL
With flow in both half systems, should the pressure at any of the three LP switches fall below
the make pressure, a supply will be completed to illuminate the BLEED caption on the
centralised warning panel and the DUCT LOW PRESSURE warning light on panel 9P.
When there is flow in one half system only, the warning lights will illuminate should either the
LP switch in that half system or in the common duct fall below the make setting.
D. Duct overpressure warning
A high pressure switch is tapped into the centre duct upstream of the primary heat
exchanger. The HP switch makes on a rising pressure of 35 ± 1 p.s.i.g. and breaks on a
falling pressure less than the make pressure but not less than 29 p.s.i.g.
NOTE: To avoid initial surge activation of overpressure warning, a 3 second interval should be
observed between ON selection of both engine bleeds.
Should the make pressure be operationally exceeded as a result of a system malfunction a
supply will be completed to illuminate the BLEED caption on the centralised warning panel
and the duct OVER PRESSure light on panel 9P. Power supplies for operation are taken from
the 28V dc right essential services busbar via C/B no. 196 on distribution panel 2D.
Upon a receipt of a warning, the crew adopt a drill to identify and isolate the faulty HA/SOV.
4. Air conditioning services
NOTE: On 300F series aircraft (post-mod A8593), all reference to passenger compartment
services are to be ignored.
- Pre Mod A8593 Air Conditioning Control Panel 9P - Refer to Figure 2 (Sheet 1).
- Post Mod A8593 Air Conditioning Control Panel 9P - Refer to Figure 2 (Sheet 2)).
The deleted services on Figure 2 (Sheet 2) are inhibited.
A. Flight compartment conditioned air
A cold air tapping is taken from downstream of the water separator and is connected to a hot
bleed air junction controlled by an electrically operated, single/dual (-300F series aircraft
bypass valve. The junction forms an ejector type mixer and is connected to a distribution duct
which supplies two floor level distributors located on the left and right of the flight
compartment. The conditioned air enters the flight compartment through a series of holes in
the forward faces of each floor level distributor. The air flow is controlled by manually
operated butterfly valves located at the aft end of each distributor. The valves are identified
CABIN HEAT - ON/OFF.
Jun 30/01
21-00-00
Page 6
EFFECTIVITY:
All
z
SD3-60 AIRCRAFT MAINTENANCE MANUAL
A temperature sensor and a duct overheat switch are located in the common duct to the flight
compartment. The temperature control is described in para 6.
NOTE: Except for -300F series aircraft, conditioned air from the passenger compartment
system is available through two gaspers located on the flight compartment aft
bulkhead. See para 4.C.
B. Windshield and side window demisting
Two tappings are taken from the flight compartment conditioned air duct and routed to a
manually controlled butterfly valve located at either side of the flight compartment on the
forward face of station 74 at rear window height. The valves are identified DEMIST - ON/OFF
and control the demist air flow to the flight compartment side windows and windshields.
C. Passenger compartment conditioned air
A cold tapping is taken from downstream of the water separator and is connected to a mixing
box. Hot bleed air is also connected to the mixing box through one half of an electrically
controlled dual bypass valve.
The mixing box forms an ejector type mixer and supplies conditioned air to a distribution duct.
The temperature of the conditioned air is determined by the amount of bleed air allowed to
enter the mixing box via the dual bypass valve.
The distribution duct delivers warm conditioned air to the left and right floor level distributors
or cold conditioned air to the left and right ceiling level distributors. The conditioned air enters
the passenger compartment through a series of holes in the face of each distributor.
The distribution of conditioned air to either the floor level distributors or the ceiling level
distributors is controlled by two manually operated valves located on the left and right of the
flight compartment aft bulkhead. Each valve has two positions:-
(1) SUMMER - with the control lever in this position the duct to the floor level distributors is
blocked off and cold conditioned air is delivered to the ceiling level distributors.
(2) WINTER - with the control lever in this position the duct to the ceiling level distributors is
blocked off and warm conditioned air is supplied to the floor level distributors.
Two tappings are taken from the common duct to the passenger compartment and are
connected to two gaspers, one located on the right and one on the left of the flight
compartment aft bulkhead. The gaspers provide a secondary source of air conditioning
for the flight compartment.
D. Compartment Anti-Fog System
NOTE: On 300F series aircraft (post mod A8593) subsequent reference to passenger
compartment
in the following text is to be read as flight compartment.
Jun 30/01
21-00-00
Page 7
EFFECTIVITY:
All
z
SD3-60 AIRCRAFT MAINTENANCE MANUAL
In hot, humid conditions, with the air conditioning system operating in the full cooling mode
fogging may appear in the passenger compartment.
This condition ensues when the passenger compartment duct sensor detects an actual
temperature several degrees higher than that at the water separator inlet, modulating both
portions of the dual by-pass valve to close. This may cause the water separator to freeze,
thus activating its integral by-pass and permitting turbine delivered fog from the ACM to enter
the compartment.
In this contingency the ANTI-FOG ON/OFF switch (panel 9P) which series-links a 33K.ohm
resistor with the duct sensor and passenger compartment controller is selected ON.
This will bring the duct sensed temperature, in the full cooling mode to approximate more
closely to that of the water separator.
The sensor will then signal the low temperature limiting circuitry of the controller to modulate
the dual by-pass valve such that the water separator inlet temperature remains above 35° F.
The ANTI-FOG ON/OFF switch should not be switched ON in normal conditions, so that, in
the heating mode, the passenger compartment duct temperature upper limit of 160° F (71°)
remains effective and full advantage of the cooling mode is available when fog would not
ensue.
E. Individual ventilation
(1) Passenger compartment
Individual ventilation is provided by air outlets (gaspers) located on the passenger
service units (PSUs). The PSUs are located above the seats on each side of the
passenger compartment. The right hand side PSUs have double gasper installations.
Each gasper comprises a manually operated butterfly valve which is opened and closed
by a knurled ring located on the bottom of each gasper.
Two cold air tappings are taken from downstream of the water separator. One tapping is
connected, via a flap valve, to the right gasper system and the other is connected, via a
second flap valve, to the left gasper system. The flap valves prevent feed back from the
gasper fans.
Jun 30/01
21-00-00
Page 8
EFFECTIVITY:
All
z
SD3-60 AIRCRAFT MAINTENANCE MANUAL
Control Panel 9P (Pre-mod A8593)
Figure 2 (Sheet 1)
Jun 30/01
21-00-00
Page 9
EFFECTIVITY:
All
z
SD3-60 AIRCRAFT MAINTENANCE MANUAL
Control Panel 9P (Post-Mod A8593)
Figure 2 (Sheet 2)
Jun 30/01
21-00-00
Page 10
EFFECTIVITY:
All
z
SD3-60 AIRCRAFT MAINTENANCE MANUAL
(2) Flight compartment
Two gaspers, one for the left side and one for the right side, are located on the main
instrument panel 1P and provide cool, conditioned air for the flight compartment.
Pre Mod A8593
The cool air for the flight compartment gaspers is tapped from the left and right supply to
the passenger compartment. The tappings are taken downstream of each flap valve and
are connected to the associated gasper via a collector box. The collector box prevents
ingress of water and/or condensation when the gasper boost system is in operation. See
para 4.F.(2).
Post Mod A8593
From the two tappings in the water separator outlet duct, cold air is ducted to either side
of the aircraft to individual gaspers positioned in the flight deck. There is no gasper ram/
fan system.
F. On-ground ventilation
On-ground ventilation, with engines shut down, may be taken from any of the following
independent sources.
(1) Main Fan
The fan, situated within the fuselage roof between stations 74 and 137 supplies ambient
air via a tapping in the main ducting immediately downstream of the water separator. A
shut-off valve in the fan duct prevents back flow through the fan when the normal air
conditioning is operating.
(a) Shut-off valve
The shut-off valve idented HR6, is actuated by a split field (open-shut) series wound
motor, incorporating limit switches which prevent overtravel and control an indicator
module displaying line indication of valve open/shut condition.
(b) Power supplies and control
Electrical power is derived from the 28V dc ground services busbar (right) via a 5
amp circuit breaker No. 211 (for shut-off valve operation) and a 25 amp circuit
breaker No. 212 (for fan operation) on distribution panel 2D.
Control is by a three position switch ON-RAM-OFF on AIR CONDITIONING panel
9P.
The control circuitry is such that, following an ON selection at the control switch,
power will not be available to drive the fan until the control valve is fully opened (limit
Jun 30/01
21-00-00
Page 11
EFFECTIVITY:
All
z
SD3-60 AIRCRAFT MAINTENANCE MANUAL
switch tripped). The fan circuit is also subject to the overriding authority of the
landing gear weight switch and is operational on ground only.
In flight, the control valve may be opened (RAM selection) as a boost to the bleed air
flow or to provide an alternative supply of air at ambient conditions following a total
loss of bleed air.
(2) Gasper boost system (Pre-Mod A8593 only)
Refer to Figure 1
A gasper boost unit is sitted on either side of the aircraft within the fuselage roof structure
between stations 89 and 146 and is employed to increase flow from the gaspers when
the aircraft is on the ground or to provide gasper supply in periods of flight (take-off and
landing) when normal air conditioning is unavailable (engine bleeds OFF).
(a) Left installation
The left sub-system is served by an intake scoop mounted on the fuselage side wall
at station 89. The supply ducting, fitted upstream of the collector box incorporates a
gasper boost control valve, a fan and a flap valve.
The flap valve is employed to prevent back-flow when the fan (which is utilised for
ground use only) is operating.
Beyond the collector box, flexible distribution ducting is routed through the fuselage
sidewall to the flight and passenger compartment gaspers, located respectively on
main instrument panel 1P and the passenger service units.
A branch pipe from the flight compartment distribution duct incorporates a flap valve
which closes when the boost system is in use and open to permit 'aircraft en-route'
delivery of conditioned air when the basic air-conditioning system is operating.
(b) Right installation
The right sub-system is similar to the left, except that two fans are fitted in series to
ensure that adequate delivery velocity is available from the double gasper
installations on this side.
(c) Gasper boost shut-off valves
The valves, idented 1HM4 - left and 2HM4 - right are actuated by a split field (open -
shut) series wound motor and incorporate limit switches to prevent over-travel.
Indicator modules on panel 9P are controlled by the limit switches and display line
indication of the appropriate valves open/shut condition.
For valve control aspects - refer to para 4.F.(2)(e).
Jun 30/01
21-00-00
Page 12
EFFECTIVITY:
All
z
SD3-60 AIRCRAFT MAINTENANCE MANUAL
(d) Power supplies and controls
Power supplies are derived from the 28V dc Ground Services Busbar via 5 amp
circuit breakers Nos 209 and 211 (for boost control valve operation) and a 15 amp
circuit breaker No. 210 (for fan operation) on distribution panel 2D.
Control is by a three position switch ON-RAM-OFF on the AIR CONDITIONING
panel 9P.
(e) Operation
With power made available (para (d)) and the aircraft on the ground, selection of the
control switch on panel 9P to ON will operate all three fans and provide appropriate
'on line' indication when each boost shut-off valve has reached the fully open
position (limit switch tripped). Fan inducted ambient air will then be available to the
gaspers.
The fans will operate throughout the take-off run until the supply is interrupted by
weight switch action when the aircraft becomes airborne. Operationally the switch is
left at ON (thus admitting ram air via the open boost valves) until conditioned air is
again made available i.e. engine bleeds are opened. The switch is then selected
OFF providing subsequent 'off line' indication when the valve is fully closed (limit
switch tripped).
(3) Recirculation/Ground inlet fan (pre-mod A8593 only)
The fan, which is situated within the fuselage roof between stations 137 and 179 may be
used in the recirculation or ground inlet modes in hot, humid conditions to augment the
movement of air within the passenger compartment.
(a) Recirculation
In the recirculation mode the fan draws air through the kicking strip ducts and
delivers it back to the passenger compartment via the high level ducts. Recirculation
may be selected on in flight to supplement the normal air conditioning.
(b) Ground inlet
In the ground inlet mode the fan draws ambient air through a grille in the fuselage
roof and delivers it directly to the high level ducts. This facility is for ground use only
and should not be selected on in flight.
(c) Control valves
The valves, idented 2H53 (recirculation) and 1H53 (ground air) are actuated by split
field (open-shut) series wound motors and incorporate limit switches to prevent
over-travel. Indicator modules on Panel 9P are controlled by the limit switches and
display line indication of the appropriate valves open/shut condition.
Jun 30/01
21-00-00
Page 13
EFFECTIVITY:
All
z
SD3-60 AIRCRAFT MAINTENANCE MANUAL
(d) Power supplies and controls
Electrical supplies are derived from the 28V dc ground services busbar via a 5 amp
circuit breaker No. 208 (for control valve operation) and a 10 amp circuit breaker No.
207 (for fan operation) on distribution panel 2D. Control is by a GND AIR - RE-CIRC-
OFF switch on panel 9P.
(4) Ground connection
When in extreme climatic conditions, conditioned air may be supplied to the aircraft via a
ground connection using a suitable Ground Service Unit (G.S.U.).
The ground connection is tapped into the right vertical duct between stations 74 and 89,
15.6 in. above the water line.
Air is delivered from the G.S.U. with the right S/W valve set at WINTER and the left S/W
valve set at SUMMER. Conditioned air is then delivered to the pass. compt. via the right
kicking strip and left high level duct. An orifice plate contained in the ground connection
prevent the aircraft from being over-pressurised by the G.S.U.
5. Extraction system
A. Passenger compartment
The majority of passenger compartment air is extracted via a grille on top of the galley unit
and is ducted to an under-floor louvred outlet in the aft baggage compartment, where it is
discharged overboard.
A portion of the passenger compartment air is extracted through grilles above the forward-
facing overhead lockers at the rear, passes through the toilet compartment and aft bulkhead
grilles to be discharged through a separate underfloor outlet in the aft baggage compartment.
B. Flight compartment
Air is extracted from the compartment via a grille positioned on the upper left hand side of the
rear bulkhead from which flexible ducting is routed to a louvred outlet on the aircraft bottom
skin below the left side of the pass. compt. A similar louvred outlet on the opposite side
provides extraction for the equipment bays below the flight compartment floor.
6. Temperature control (Flight and passenger compartment)
NOTE: On 300F series aircraft (post-mod A8593) passenger compartment conditioned air
distribution is inhibited; ducting is blanked and the supply re-directed to the flight
compartment services.
The temperature controller hitherto associated with the passenger compartment is used in
conjunction with the dual bypass valve and flight compartment temperature sensors to
control flight compartment temperature. Flight Attendants Panel 12P is not fitted on - 300F
series aircraft.
Jun 30/01
21-00-00
Page 14
EFFECTIVITY:
All
z
SD3-60 AIRCRAFT MAINTENANCE MANUAL
The passenger compartment automatic temperature control system consists of a controller
(electronic analogue type computer) a temperature selector and two temperature sensors, one
within the compartment and the other in the supply duct. The controller compares the selected
temperatures with the compartment and duct sensed temperature and modulates the dual by-
pass valve accordingly. A similar system in the flight compartment modulates the single bypass
valve.
The AUTO TEMPerature selector switch on the pilot's control panel 9P is duplicated on the flight
attendant's panel 12P and becomes operational by the flight attendant only when the AUTO
CONTROL PILOT/ATTD'T switch (9P) is selected to ATTD'T.
The duct temperature sensors in the flight and passenger supply ducts downstream of the hot
line connections additionally signal the temperature controllers to limit respective duct
temperatures throughout the conditioning range of operation (auto mode) to between 35° F (2°
C) and 160° F (71° C).
The lower limit is of particular importance with regard to the passenger compartment controller,
ensuring that delivery air to the water separator is maintained above freezing point.
If a failure occurs and the upper temperature limit is exceeded, an overtemperature switch in the
appropriate duct will illuminate the BLEED air caption on the centralized warning panel and the
associated duct OVERHEAT light on the AIR CONDITIONING services panel 9P.
NOTE: The passenger compartment overtemperature switch operates when the duct temperature
reaches 185° F to 195° F (85° C to 90° C) and the flight compartment switch at 235° F to
245° F (113° C to 118° C).
Receipt of an overheat warning is a signal to select the affected systems mode switch on panel
9P from AUTO to MANUAL (thus isolating the controller). Operation of the appropriate bypass
valve (dual or single) will then be subject to the control of the associated HOT/COOL manual
control switch on panel 9P; this switch is held momentarily in the required position to modulate
the relevant bypass valve.
On aircraft post Service Bulletin SD360-21-13, crew indication of the ambient temperature in the
passenger compartment is provided by a temperature gauge on panel 9P. Refer to 21-61-00,
pb1.
Jun 30/01
21-00-01
Page 201
EFFECTIVITY:
All
z
SD3-60 AIRCRAFT MAINTENANCE MANUAL
AMM21-00-01 2.0.0.0GASPER BOOST SYSTEM - MAINTENANCE PRACTICES
1. Adjustment/Test
A. Function check the system
(1) Provide electrical power and close C/B No. 209, 210 and 211 on distribution panel 2D.
Refer to 12-09-03, pb301.
(2) With the control switch OFF/RAM/ON on panel 9P set at OFF, check that the left and
right gasper boost valves are shut (indicator modules display off-line).
(3) Select control switch to RAM and check that both valves (indicator modules display in-
line).
(4) Fully open gasper units on flight compartment panel 1P and along the left and right sides
of passenger compartment.
(5) Advance control switch to ON and check that all three fans are activated i.e. balanced
delivery velocity of inducted air is available between the left and right hand sides of the
compartments at corresponding lateral positions.
(6) Check fan flight inhibiting circuitry as follows:-
WARNING: ENSURE THAT GROUND LOCKING PINS ARE FITTED TO THE LANDING
GEAR, PREVENTING RETRACTION, SHOULD THE SELECTOR SWITCH BE
OPERATED INADVERTENTLY DURING OPERATION (D).
(a) Gain access to TB74, situated in the right landing gear bay (Stn.316), by removing
the access panel from the bulkhead.
(b) With fan selected ON, connect a switchable 28V d.c. power supply (control switch
open) to the coil of the weight switch relay via terminal No.2 on TB74.
(c) Close the power supply control switch, thus energising the coil of the weight switch
control relay and check that flow from the gaspers has ceased - fans deactivated.
(d) Disconnect power supply and replace access panel.
Jun 30/01
21-00-06
Page 201
EFFECTIVITY:
All
z
SD3-60 AIRCRAFT MAINTENANCE MANUAL
AMM21-00-06 3.0.0.0HEAT EXCHANGER - MAINTENANCE PRACTICES
1. Removal/Installation
Refer to Figure 201.
A. Remove a heat exchanger.
(1) Remove access panels 240 AR, 240 BR, 240 AL, 240 BL, 240 CL, 240 DL and 240 EL
on forward fairing. Refer to 6-30-00, pb1.
(2) Remove detachable fairing structure between frame stations 74 and 179.8. Note
positions and method of attachments for subsequent re-installation.
(3) Disconnect ducting as follows:-
(a) Heat exchanger to air cycle machine (detail C)
(b) Heat exchanger to compressor inlet (detail A)
(c) Heat exchanger to turbine and by-pass valve (detail A).
(d) Compressor to heat exchanger (detail A)
(e) Engine supply duct to heat exchanger (detail B)
(4) Disconnect drain tube from heat exchanger.
(5) Detach heat exchanger and channel assemblies where secured to vertical support posts.
(6) Remove unit complete with channel assemblies.
NOTE: Slacken adjacent ducting as necessary to negotiate removal of heat exchanger
noting positions for re-tightening during subsequent re-installation.
B. Install a heat exchanger
NOTE: Operation (1) only applies if unit is not that previously removed (para 1.A.).
(1) Remove the four bolts, nuts and washers which secure the channel assemblies, gasket
and duct to the top of the heat exchanger and fit these items to the replacement unit.
(2) Install heat exchanger with top channel assemblies to support posts and attach using
bolts nuts and washers.
NOTE: At aft inboard corner two vertical bolt positions to be left redundant until forward
fairing is installed.
(3) Connect drain tube to heat exchanger and tighten jubilee clip.
Jun 30/01
21-00-06
Page 202
EFFECTIVITY:
All
z
SD3-60 AIRCRAFT MAINTENANCE MANUAL
Heat Exchanger - Removal/Installation
Figure 201
Jun 30/01
21-00-06
Page 203
EFFECTIVITY:
All
z
SD3-60 AIRCRAFT MAINTENANCE MANUAL
(4) Refer to Figure 201. Make the following ducting connections with reference to the
appropriate detail using new 'O' ring seals where required.
(a) Heat exchanger to air cycle machine (detail C).
(b) Compressor to heat exchanger (detail A) using seal Pt. No. 56A 460 225.
(c) Engine supply duct to heat exchanger (detail B).
(d) Heat exchanger to turbine by-pass valve (detail A) using seal Pt. No. 56A 460 175.
(e) Heat exchanger to compressor inlet (detail A) using seal Pt. No. 56A 460 250.
(5) Refit fairing detachable structure between frame stations 74 and 179.8 securing as noted
during removal operations.
(6) Install access panels 240 AR, 240 BR, 240 AL, 240 BL, 240 CL, 240 DL and 240 EL on
forward fairing.
Jun 30/01
21-00-11
Page 201
EFFECTIVITY:
All
z
SD3-60 AIRCRAFT MAINTENANCE MANUAL
AMM21-00-11 4.0.0.0AIR CYCLE MACHINE - MAINTENANCE PRACTICES
1. Servicing
A. Check oil level in sump
(1) Open access panel 240 DL in forward fairing on fuselage roof.
(2) By the use of a mirror inspect the oil level sight plug, situated on the forward side of the
air cycle machine beneath the outlet ducting, to ensure that the sight bulb is full of oil.
(3) Close access panel 240 DL.
B. Replace oil in sump
(1) Remove access panel 240 DL in forward fairing on fuselage roof.
(2) Break locking wire of filler plug, adjacent to oil level sight plug, and remove filler plug and
pre-formed packing. Retain filler plug and discard packing.
(3) Siphon-drain sump through filler plug orifice.
(4) Fill sump to filler port level with Exxon 2380 oil.
NOTE: Exxon 2380 oil per MIL-L-23699 is the recommended lubricant for maximum
service life. If not available MIL-L-7808G is suggested for use in cooler climates
and other oils per MIL-L-23699 for operation in warmer climates.
(5) Install filler plug and new pre-formed packing 69494 K11 and tighten to 15 to 25 lb.in.
torque.
(6) Wire lock plug to sump.
(7) Replace access panel 240 DL.
2. Removal/Installation
A. Remove an air cycle machine (ACM)
Refer to Figure 201.
(1) Open circuit breaker No. 196 on right distribution panel 2D.
(2) Remove access panels 240 AL, 240 CL, 240 DL and 240 EL in forward fairing on
fuselage roof.
(3) Disconnect bayonet type electrical connection from over temperature switch.
Jun 30/01
21-00-11
Page 202
EFFECTIVITY:
All
z
SD3-60 AIRCRAFT MAINTENANCE MANUAL
(4) Disconnect the following ducts at the air cycle machine:-
- ACM turbine outlet (detail A)
- Heat exchanger to compressor inlet (detail A)
- Compressor outlet to heat exchanger (detail A).
- ACM turbine inlet (detail B).
- ACM to heat exchanger (detail C).
(5) Remove split pins, nuts, washers and bolts holding ACM to mounting platform, and
retain.
(6) Remove bushes from inboard attachment holes and retain.
(7) Lift ACM clear and remove from aircraft.
NOTE: Slacken adjacent ducting as necessary to negotiate removal of ACM noting
positions for re-tightening during subsequent re-installation.
B. Install an air cycle machine
NOTE: Operation (1) only applies if unit is not that previously removed in para 2.A.
(1) If ACM is unserviceable, transfer turbine outlet elbow and attachments to replacement
ACM, using HYLOMAR jointing compound Part No. SQ32.
NOTE: Alternatively a gasket, Hamilton Standard Part No. 753443-2 may be substituted
for the jointing compound;
(2) Align ACM with attachment holes in mounting platform and fit bushes to the two inboard
holes, with the bush flanges on the outboard side. All bolts to be entered from outboard
side, washers fitted under nuts, nuts tightened and split pinned.
(3) Refer to Figure 201. Make the following duct connections with reference to the
appropriate detail using new 'O' ring seals as required:-
- ACM to heat exchanger (detail C).
- ACM turbine inlet (detail B) using seal Part No. 69494-J-132.
- Compressor outlet to heat exchanger (detail A).
- Heat exchanger to compressor inlet (detail A).
- ACM turbine outlet (detail A).
(4) Reconnect bayonet type electrical connection to over temperature switch.
(5) Replace access panels 240 AL, 240 CL, 240 DL and 240 EL.
(6) Close circuit breaker No. 196 on right distribution panel 2D.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102

BOMBARDIER SD3-60 Maintenance Manual

Type
Maintenance Manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI