Hazardous Voltage
Will cause death, severe personal injury, or property damage.
Only qualified personnel should work on or around this equipment after
becoming thoroughly familiar with this document and other publications
regarding this equipment.
!
DANGER
Qualified Person
Only qualified trained and competent
personnel that understand proper safety
procedures must select, install and service
this equipment.
Read and understand these instructions be-
fore installing, operating or maintaining this
equipment.
This guide is not a substitute for adequate
training and experience in safety procedures
for this type of equipment.
Signal Words
The signal words “DANGER,” “WARNING”
and “CAUTION” (along with their assigned
symbol) throughout this manual indicate the
degree of hazard the user may encounter.
These symbols and words are defined as:
DANGER indicates an imminently hazardous
situation which, if not avoided, will result in
death or serious injury.
WARNING indicates a potentially hazardous
situation which, if not avoided, could result in
death or serious injury.
CAUTION indicates a potentially hazardous
situation which, if not avoided, may result in
moderate or minor injury.
CAUTION used without the safety alert sym-
bol indicates a potentially hazardous situation
which, if not avoided, may result in property
damage.
▲
!
DANGER
!
WARNING
!
CAUTION
CAUTION
Product
The products covered by this manual are
the BPF fused substation by-pass switches
for medium voltage electrical distribution
switching.
These products are designed for distribution
switching only at their rated capacities. They
cannot be field modified for capacities other
than what was shipped with the units. If a
different capacity is desired, contact your
supervisor or factory representative to se-
cure the appropriate unit.
Overview
Function
These products are non-loadbreak discon-
nect switch and fuse combinations designed
to provide a means for by-passing, discon-
necting and isolating reclosers on the elec-
trical distribution system.
General
The BPF By-Pass Switch is a single-phase
fused hook stick operated switch. It is nor-
mally used with a companion switch such
as a Chance M3S, station class hook stick
switch. The BPF By-Pass switch is used for
manually disconnecting a recloser without
interrupting normal electrical service while
continuing to provide over-current protec-
tion. Standard variations are:
A. Left or right fuse mounting.
B. Te rminal connectors.
The BPF disconnect switch has no inherent
current making or breaking rating. The fuse
is capable of interrupting over-currents
within its assigned rating. Both switch and
fuse include load break hooks for use with a
load break tool. The BPF has no dead-end-
ing provisions.
Specifications
Select the proper BPF switch for each in-
stallation with consideration to system and
short circuit recovery voltage, continuous
current, available short circuit over-current,
short time current withstand, lightning im-
pulse withstand and variations. If there is
concern about the use of this switch as
rated, consult your supervisor before instal-
lation.
• Nominal voltage ratings of 14.4kV or
25kV (model dependent)
• Lightning impulse peak withstand ratings
of 110kV or 150kV (model dependent)
• Switch continuous current rating of 600
amperes
• Switch short time current withstand
rating:
– 25kA symmetrical, 1 second
– 65kA peak
• Fuse continuous current ratings of 100 or
200 amperes (model dependent)
• Fuse interrupt ratings of:
14.4kV nominal voltage rating
– 7.1kA symmetrical, 10kA asymmetrical
for 100 ampere fuse holder
– 8kA symmetrical, 12kA asymmetrical
for 200 ampere fuse holder
25kV nominal voltage rating
– 5.3kA symmetrical, 8kA asymmetrical
for 100 ampere fuse holder
– 6.6kA symmetrical, 10kA asymmetrical
for 200 ampere fuse holder
• Rating of the fuse holder is given on the
switch name plate. Consult factory repre-
sentative prior to using any other fuse
holder.
Switch Variations
A. Left or Right Fuse Mounting
Left or right fuse mounting may be speci-
fied. A left mounted fuse is to the left of the
operator when viewed from the front of the
switch. A right mounted fuse is to the right
of the operator when viewed from the front
of the switch. This selection allows the BPF
to be tailored to fit the requirements of the
application. Illustrations in this manual show
only a left fuse mounting. Right fuse mount-
ing will be opposite as shown but does not
change the installation or operation
procedures. (continued next page)