Installation Manual
Installation and Appliance Setup
INSTALLER: Leave this manual with party responsible for use and operation.
OWNER: Retain this manual for future reference.
NOTICE: DO NOT discard this manual!
This appliance may be installed as an OEM installation
in manufactured home (USA only) or mobile home and
must be installed in accordance with the manufacturer’s
instructions and the manufactured home construction
and safety standard, Title 24 CFR, Part 3280 or Standard
for Installation in Mobile Homes, CAN/CSA Z240MH, in
Canada.
This appliance is only for use with the type(s) of gas
indicated on the rating plate.
In the Commonwealth of Massachusetts installation must be

See Table of Contents for location of additional Commonwealth

WARNING: If the information in these
instructions is not followed exactly, a re
or explosion may result causing property
damage, personal injury, or death.
 DO NOT store or use gasoline or other


What to do if you smell gas
- DO NOT
- DO NOT     DO
NOT
- Immediately call your gas supplier from a


- If you cannot reach your gas supplier, call

 


Models:
TIARAI-BK-IPI
TIARAI-BR-IPI
TIARAI-CES-IPI
TIARAI-BK-IPIL
TIARAI-BR-IPIL
TIARAI-CES-IPIL
HOT GLASS WILL CAUSE

DO NOT TOUCH GLASS UNTIL

NEVER ALLOW CHILDREN TO

WARNING
!
Heat & Glo • TIARAI-BK-IPI, TIARAI-BR-IPI, TIARAI-CES-IPI Installation Manual • 2342-980_R8 • 11/142
Safety Alert Key:
• DANGER! Indicates a hazardous situation which, if not avoided will result in death or serious injury.
• WARNING! Indicates a hazardous situation which, if not avoided could result in death or serious injury.
• CAUTION! Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
• NOTICE: Used to address practices not related to personal injury.
Installation Standard Work Checklist3
1 Product Specic and Important Safety Information
 4
 4
 4
 4
 4
  4
4
   5
2 Getting Started
 6
 6
 6
3 Framing and Clearances
 7
  8
 8
4 Termination Location and Vent Information
 9
 10
  11
  12
 12
 13
13
5 Vent Clearances and Framing
  30
 30
 31
  31
6 Appliance Preparation
32
 35
7 Venting and Chimneys
36
  37
  38
  38
 40
  42
8 Electrical Information
 44
  45
9 Gas Information
 48
 48
 48
 48
  49
10 Appliance Setup
  50
  50
 50
  51
  52
11 Reference Materials
  53
 58

Table of Contents
Heat & Glo • TIARAI-BK-IPI, TIARAI-BR-IPI, TIARAI-CES-IPI Installation Manual • 2342-980_R8 • 11/143
Installation Standard Work Checklist
Customer:
Lot/Address:
Model (circle one): TIARAI-BK-IPI TIARAI-BK-IPIL
TIARAI-BR-IPI TIARAI-BR-IPIL
TIARAI-CES-IPI TIARAI-CES-IPIL
Date Installed:
Location of Stove:
Installer:
Dealer/Distributor Phone #
Serial #:
Comments: Further description of the issues, who is responsible (Installer/ Builder/ Other Trades, etc) and corrective
action needed _____________________________________________________________________________________
_________________________________________________________________________________________________
_________________________________________________________________________________________________
Comments Communicated to party responsible ____________________ by ______________________on ___________
(Builder / Gen. Contractor/) (Installer) (Date)
Appliance Install YES IF NO, WHY?
Veri ed combustible or non-combustible clearances to walls. (Pg. 8) ___________________________
Stove is installed level. (Pg. 35) ___________________________
Venting/Chimney Section 7 (Pg 36-43)
Venting con guration complies with allowable vent requirements. ___________________________
Venting installed, locked and secured in place with proper clearance. ___________________________
Interior/Exterior restops installed and sealed. ___________________________
Attic insulation shield installed. ___________________________
Exterior wall/Roof ashing installed and sealed. ___________________________
Terminations/Roof ashing installed and sealed. ___________________________
Electrical Section 8 (Pg 44-47)
Unswitched power (110-120 VAC) provided for the appliance. ___________________________
Switch wires properly installed. ___________________________
Gas Section 9 (Pg 48-49)
Appliance con guration matches fuel type. ___________________________
Was a conversion performed? ___________________________
Leak check performed and inlet/outlet pressure veri ed. ___________________________
Set air shutter for optimal ame appearance. ___________________________
Appliance Setup Section 10 (Pg 50-52)
All packaging and protective materials are from removed inside/under/on
the appliance). ___________________________
Refractories, logs, and embers installed correctly. ___________________________
Glass assembly installed and secured. ___________________________
Accessories installed properly. ___________________________
Mesh, doors, or decorative front properly installed. ___________________________
Manual bag and all of its contents are removed from inside/under
the appliance and given to party responsible for use and operation. ___________________________
Started appliance and veri ed no gas leaks exist. ___________________________
2342-982 Rev. B 2/14
= Contains updated information.
Hearth & Home Technologies recommends the following:
• Photographing the installation and copying this checklist for your le.
• That this checklist remain visible at all times on the appliance until the installation is complete.
This standard work checklist is to be used by the installer in conjunction with, not instead of, the instructions contained in
this
installation manual.
WARNING! Risk of Fire or Explosion! Failure to install appliance according to these instructions can
lead to a re or explosion.
ATTENTION INSTALLER:
Follow this Standard Work Checklist
Heat & Glo • TIARAI-BK-IPI, TIARAI-BR-IPI, TIARAI-CES-IPI Installation Manual • 2342-980_R8 • 11/144
B. Glass Specications
        


C. BTU Specications
        
      
Burning Heating Appliances for Manufactured Homes and


NOTICE: This installation must conform with local codes. In
the absence of local codes you must comply with the National
Fuel Gas Code, ANSI Z223.1-latest edition in the U.S.A. and
the CAN/CGA B149 Installation Codes in Canada.
A. Appliance Certication
NOT INTENDED FOR USE AS A PRIMARY HEAT SOURCE.

           

1 Product Specic and Important Safety Information
MODELS: TIARAI-BK-IPI, TIARAI-BR-IPI, TIARAI-CES-IPI
LABORATORY: Underwriters Laboratories, Inc. (UL)
TYPE: Direct Vent Heater
STANDARD: ANSI Z21.88-2009/CSA 2.33-2009
D. High Altitude Installations
NOTICE: If the heating value of the gas has been reduced,
these rules do not apply. Check with your local gas utility or
authorities having jurisdiction.

 




      



E. Non-Combustible Materials Specication

those consisting entirely of steel, iron, brick, tile, concrete,

Materials that are reported as passing ASTM E 136,
Standard Test Method for Behavior of Materials in a
Vertical Tube Furnace at 750 ºC shall be considered non-

F. Combustible Materials Specication
Materials made of or surfaced with wood, compressed paper,

        

G. Electrical Codes
NOTICE: This appliance must be electrically wired and
grounded in accordance with local codes or, in the absence
of local codes, with National Electric Code ANSI/NFPA
70-latest edition or the Canadian Electric Code CSA
C22.1.
 
with ground-fault circuit-interrupter protection, in
compliance with the applicable electrical codes, when
it is installed in locations such as in bathrooms or near

Models
(U.S. or Canada)
Maximum
Input
BTU/h
Minimum
Input
BTU/h
Orice
Size
(DMS)



(NG)
(0-2000 FT) 25,000 19,500 42




(0-2000 FT) 22,500 16,500 54
Heat & Glo • TIARAI-BK-IPI, TIARAI-BR-IPI, TIARAI-CES-IPI Installation Manual • 2342-980_R8 • 11/145
H. Requirements for the Commonwealth of
Massachusetts
 
        
whole or in part for residential purposes, including those
owned or operated by the Commonwealth and where
         
          
including but not limited to decks and porches, the following

Installation of Carbon Monoxide Detectors

        

with an alarm and battery back-up is installed on the
          
        
        

         





equipment is installed in a crawl space or an attic, the hard
       


be met at the time of completion of installation, the owner
           
      


Approved Carbon Monoxide Detectors



Signage





“GAS VENT DIRECTLY
BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.
Note:     
Massachusetts and national codes not contained in this

Inspection

       

      
       

Exemptions


   


 
equipment installed in a room or structure separate from
the dwelling, building or structure used in whole or in part

MANUFACTURER REQUIREMENTS
Gas Equipment Venting System Provided
       
      
       
      
        

        

          

Gas Equipment Venting System NOT Provided
       

 
      

 
be included with the appliance or equipment installation

 
by the Board, and the instructions for that system shall


       
       


See Gas Connection section for additional
Commonwealth of Massachusetts requirements.
Heat & Glo • TIARAI-BK-IPI, TIARAI-BR-IPI, TIARAI-CES-IPI Installation Manual • 2342-980_R8 • 11/146
2 Getting Started
A. Design and Installation Considerations
         
operate with all combustion air siphoned from outside of the


Installation MUST comply with local, regional, state and
    
       
     

Before
 
 
 
 
 

C. Inspect Appliance and Components
 

       

 
         

Read all of the instructions before starting the
installation. Follow these instructions carefully during
the installation to ensure maximum safety and benet.
WARNING! Risk of Fire or Explosion! Damaged parts
could impair safe operation. DO NOT install damaged,
incomplete or substitute components. Keep appliance dry.
B. Tools and Supplies Needed
Before beginning the installation be sure that the following

 
 
 
 
 
 
 



     
rating)

Hearth & Home Technologies disclaims any responsibility for,

 

 
        

 
 

Any such action may cause a re hazard.
WARNING! Risk of Fire, Explosion or Electric Shock! DO
NOT use this appliance if any part has been under water.
Call a qualied service technician to inspect the appliance
and to replace any part of the control system and/or gas
control which has been under water.
     
       



      



Heat & Glo • TIARAI-BK-IPI, TIARAI-BR-IPI, TIARAI-CES-IPI Installation Manual • 2342-980_R8 • 11/147
3 Framing and Clearances
A. Appliance Dimension Diagram

Figure 3.1 Appliance Dimensions
Location Inches Millimeter Location Inches Millimeter
A 590 D  514
B 237 E  298
C 27 686 20 506
NOTE: Diagrams show gas appliance equipped without optional Blower, Part #GFK-160A.
FRONT SIDE
A
B
C
D
E
F
BACK
GAS LINE
ELECTRICAL
CORD
Heat & Glo • TIARAI-BK-IPI, TIARAI-BR-IPI, TIARAI-CES-IPI Installation Manual • 2342-980_R8 • 11/148
B. Clearances to Combustibles
When selecting a location for the appliance it is important to

WARNING! Risk of Fire or Burns! Provide adequate
clearance around air openings and for service access. Due
to high temperatures, the appliance should be located out of
trafc and away from furniture and draperies.
NOTICE: Illustrations reect typical installations and are FOR
DESIGN PURPOSES ONLY. Illustrations/diagrams are not
drawn to scale. Actual installation may vary due to individual
design preference.
NOTICE: Some carpet materials may be sensitive to radiant
heat from the appliance causing discoloration or odor.
Figure 3.2 Appliance Locations
Model A B C D E F G
H
Top of
pipe
Side of
pipe
Inside Outside
corner wall

TIARAI-IPI
Inches    54 36  27 3 1 9
Millimeters 216 6 10 1372 914 1022 686 76 25 229
A
B
F
E
A
"A"
measurement is from
stove top, not side
G
H
D
C
C
A
G
A
C. Hearth Extension/Floor Protection
CAUTION! Risk of Fire or Injury! Install appliance on
a stable, level, platform or oor strong enough to support
appliance without tipping.
        

strong enough to support the appliance without a tipping

NOTE:
      


Note:

Alcove Installation
Heat & Glo • TIARAI-BK-IPI, TIARAI-BR-IPI, TIARAI-CES-IPI Installation Manual • 2342-980_R8 • 11/149
A. Vent Termination Minimum Clearances
Roof Pitch H (Min.) Ft.





 
 
 

Figure 4.1 Minimum Height From Roof To Lowest Discharge Opening
HORIZONTAL
OVERHANG
VERTICAL
WALL
GAS DIRECT VENT
TERMINATION CAP
12
X
ROOF PITCH
IS X/ 12
LOWEST
DISCHARGE
OPENING
2 FT.
MIN.
20 INCHES MIN.
H (MIN.) - MINIMUM HEIGHT FROM ROOF
TO LOWEST DISCHARGE OPENING
4 Termination Location and Vent Information

     

 DO NOT pack air space with insulation or other



Figure 4.2 Staggered Termination Caps
Gas, Wood or Fuel Oil
Termination Cap
B
Gas
Termination
Cap **
A *
*If using decorative cap cover(s), this distance may need to be
increased. Refer to the installation instructions supplied with the
decorative cap cover.
**
A B
6 in. (minimum) up to 20 in.
152 mm/508 mm
18 in. minimum
457 mm
20 in. and over 0 in. minimum
In a staggered installation with both gas and wood or fuel oil
terminations, the wood or fuel oil termination cap must be
higher than the gas termination cap.
WARNING
!
Heat & Glo • TIARAI-BK-IPI, TIARAI-BR-IPI, TIARAI-CES-IPI Installation Manual • 2342-980_R8 • 11/1410
B. Chimney Diagram
Figure 4.3 Minimum Clearances for Termination
A = 12 inches   
porch, deck or balcony
B = clearance to window or door that may
be opened, or to permanently closed
window
C = 18 inches
18 inches
30 inches    

D = 9 inchesclearance to outside corner
E = 6 inchesclearance to inside corner
        

   
regulator
G = 3 ft
outlet
H = 12 clearance to non-mechanical
(unpowered) air supply inlet,
    
termination
  
 clearance to a mechanical (powered)
air supply inlet
All mechanical air intakes within 10 feet of a termination cap must

   On public

          


C
JB
D
B
F
B
A
E
V
V
V
V
V
V
M
H or i
V
G
X
VH
A
VV
H
X= AIR SUPPLY INLET
V= VENT TERMINAL
= AREA WHERE TERMINAL IS NOT PERMITTED
O
N
P
R
Q
Electrical
Service
V
K
V K
V
L
C
V
QMIN RMAX
1 cap 3 feet ACTUAL
2 caps 6 feet ACTUAL
3 caps 9 feet ACTUAL
4 caps 12 feet ACTUAL
QMIN = # termination caps x 3 RMAX = (2 / # termination caps) x QACTUAL
Covered Alcove Applications

N = 6 inches  
12 inches  
O = 18 inches  
42 inches  
  


CAUTION! Risk of Burns! Termination caps are HOT, consider
proximity to doors, trafc areas or where people may pass or
gather (sidewalk, deck, patio, etc.). Listed cap shields available.
Contact your dealer.
 
 NOT
 

 


 
M = 18 inches     

42 inches 


K = 6 inches clearance from sides of electrical

L = 12 inches


Heat & Glo • TIARAI-BK-IPI, TIARAI-BR-IPI, TIARAI-CES-IPI Installation Manual • 2342-980_R8 • 11/1411
C. Approved Pipe
         


DO NOT 


        

WARNING! Risk of Fire or Asphyxiation. This appliance
requires a separate vent. DO NOT vent to a pipe serving a
separate solid fuel burning appliance.
DO NOT USE FIELD-FABRICATED VENTING
COMPONENTS
        








  is required

      is required when the

 

 

Heat & Glo • TIARAI-BK-IPI, TIARAI-BR-IPI, TIARAI-CES-IPI Installation Manual • 2342-980_R8 • 11/1412
D. Use of Elbows

         




         



Figure 4.4
HORIZONTAL
VERTICAL
RUN
RISE
EFFECTIVE
LENGTH
Y
X
X
X
Vent Type X
Inches Millimeters
  286
Vent
Type
X Y
Inches Millimeters Inches Millimeters
 5 127  298
SLP
Pipe
Effective Length Rise/Run
Inches Millimeters Inches Millimeters
 4 102  70
 6 152  108
 12 305  216
 24 610 17 432
 36 914  648
 48 1219 34 864
 3 to 6 76 to 152  54-108
 3 to 12 76 to 305  54-216
Figure 4.5 Vertical and Horizontal Offset for SLP Elbows
E. Measuring Standards
       

 


      


      

 
Y
X
X
X
Heat & Glo • TIARAI-BK-IPI, TIARAI-BR-IPI, TIARAI-CES-IPI Installation Manual • 2342-980_R8 • 11/1413
G. Vent Diagrams

     


 

 

 


 

 


       

4 ft min.
(1.22 m)
Figure 4.7
Figure 4.6
F. Venting Guidelines for Horizontal Runs
C
L
Snorkel Kit



Snorkel kit and derating


 
is 10 ft (3m)

o
Elbow (No Rise)

Snorkel kit and derating



Rise

must be used prior to any
-






one -

Heat & Glo • TIARAI-BK-IPI, TIARAI-BR-IPI, TIARAI-CES-IPI Installation Manual • 2342-980_R8 • 11/1414
Figure 4.8
One Elbow
Top Vent - Horizontal Termination
V1H1 Maximum
 305 mm  356 mm
 610 mm  
   
   
   
   
   
   
   
   
   
   
H1
V1
Heat & Glo • TIARAI-BK-IPI, TIARAI-BR-IPI, TIARAI-CES-IPI Installation Manual • 2342-980_R8 • 11/1415
Two Elbows
INSTALLED
HORIZONTALLY
H1
H2
V1
2 Elbows to Max. Horizontal
V1 Minimum H1 + H2 Maximum
 610 mm  
   
   
   
   
   
   
   
   
   787 mm
   533 mm
Figure 4.9
Heat & Glo • TIARAI-BK-IPI, TIARAI-BR-IPI, TIARAI-CES-IPI Installation Manual • 2342-980_R8 • 11/1416
H2
H1
V2
V1
Figure 4.10
Top Vent - Horizontal Termination - (continued)
Three Elbows
3 Elbows to Max. Horizontal
V1 Minimum H1 + H2 Maximum
 610 mm  914 mm
   
   
   
   
   
   
   
   457 mm
   279 mm
   279 mm
Heat & Glo • TIARAI-BK-IPI, TIARAI-BR-IPI, TIARAI-CES-IPI Installation Manual • 2342-980_R8 • 11/1417
Top Vent - Vertical Termination
No Elbow
Figure 4.11
V1
V1 = 30 ft. Max. (9.1 m)
V1 = 6 ft. Min. (1.8 m)
Heat & Glo • TIARAI-BK-IPI, TIARAI-BR-IPI, TIARAI-CES-IPI Installation Manual • 2342-980_R8 • 11/1418
Figure 4.12
Two Elbows
H1
V1
V2
2 Elbows to Max. Horizontal
V1 Minimum V1 + V2 Maximum H1 Maximum
 610 mm    
     
     
     
     
     
     
     
     
     787 mm
Heat & Glo • TIARAI-BK-IPI, TIARAI-BR-IPI, TIARAI-CES-IPI Installation Manual • 2342-980_R8 • 11/1419
Figure 4.13
Top Vent - Vertical Termination - (continued)
Three Elbows
INSTALLED
HORIZONTALLY
H1
H2V1
V2
3 Elbows to Max. Horizontal
V1 Minimum V1 + V2 Maximum H1 + H2 Maximum
 610 mm    
     
     
     
     
     
     
     
     457 mm
Heat & Glo • TIARAI-BK-IPI, TIARAI-BR-IPI, TIARAI-CES-IPI Installation Manual • 2342-980_R8 • 11/1420
Rear Vent - Horizontal Termination
Figure 4.14
Figure 4.15
No Elbow
H1 = 14 in. (356 mm) Maximum
H1 = 14 in. (356 mm) Maximum
Note:      

Note:      

Note:

Note:

NOTICE: An SLK-SNKD is required for this
vent conguration.
NOTICE: An SLK-SNKD is required for this
vent conguration.
H1
H1
One 45º Elbow
Rear Vent - Horizontal Termination
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58