Quadrafire Garnet IPI Install Manual

Category
Fireplaces
Type
Install Manual
Quadra-Fire • GARN-MBK-IPI, GARN-D-PMH-IPI, GARN-D-MBK-IPI, GARN-D-CSB-IPI Installation Manual • 2345-980_R5 • 11/141
Installation Manual
Installation and Appliance Setup
INSTALLER: Leave this manual with party responsible for use and operation.
OWNER: Retain this manual for future reference.
This appliance may be installed as an OEM installation
in manufactured home (USA only) or mobile home and
must be installed in accordance with the manufacturer’s
instructions and the manufactured home construction
and safety standard, Title 24 CFR, Part 3280 or Standard
for Installation in Mobile Homes, CAN/CSA Z240MH, in
Canada.
This appliance is only for use with the type(s) of gas
indicated on the rating plate.
In the Commonwealth of Massachusetts installation must

See Table of Contents for location of additional

 DO NOT       
vapors and liquids in the vicinity of this or any other

• Whattodoifyousmellgas
- DO NOT
- DO NOT  DO NOT use

- Immediately call your gas supplier from a neighbor’s

          

 

HOT GLASS WILL CAUSE

DO NOT TOUCH GLASS UNTIL

NEVER ALLOW CHILDREN TO

Models:
GARN-MBK-IPI
GARN-D-PMH-IPI
GARN-D-MBK-IPI
GARN-D-CSB-IPI
NOTICE: DO NOT discard this manual!
R
WARNING: If the information in these instructions is
not followed exactly, a re or explosion may result
causingpropertydamage,personalinjury,ordeath.
WARNING
!
Quadra-Fire • GARN-MBK-IPI, GARN-D-PMH-IPI, GARN-D-MBK-IPI, GARN-D-CSB-IPI Installation Manual • 2345-980_R5 • 11/142
Safety Alert Key:
• DANGER! Indicates a hazardous situation which, if not avoided will result in death or serious injury.
• WARNING! Indicates a hazardous situation which, if not avoided could result in death or serious injury.
• CAUTION! Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
• NOTICE: Used to address practices not related to personal injury.
Installation Standard Work Checklist3
1ProductSpecicandImportantSafetyInformation
 4
 4
 4
 4
 4
  4
4
  5
2GettingStarted
 6
 6
 6
3FramingandClearances
 7
  8
 8
4 Termination Location and Vent Information
 9
 10
  11
  12
 12
 13
13
5VentClearancesandFraming
  24
 24
  25
 25
6 Appliance Preparation
 26
7VentingandChimneys
27
  28
 29
  29
 31
   33
8 Electrical Information
 35
  36
9 Gas Information
 40
 40
 40
 40
  41
10 Appliance Setup
 42
 42
 42
 43
 44
11 Reference Materials
  45
 50

Table of Contents
Quadra-Fire • GARN-MBK-IPI, GARN-D-PMH-IPI, GARN-D-MBK-IPI, GARN-D-CSB-IPI Installation Manual • 2345-980_R5 • 11/143
Installation Standard Work Checklist
Customer:
Lot/Address:
Model (circle one): GARN-MBK-IPI
GARN-D-PMH-IPI
GARN-D-MBK-IPI
GARN-D-CSB-IPI
Date Installed:
Location of Stove:
Installer:
Dealer/Distributor Phone #
Serial #:
Comments: Further description of the issues, who is responsible (Installer/ Builder/ Other Trades, etc) and corrective
action needed _____________________________________________________________________________________
_________________________________________________________________________________________________
_________________________________________________________________________________________________
Comments Communicated to party responsible ____________________ by ______________________on ___________
(Builder / Gen. Contractor/) (Installer) (Date)
Appliance Install YES IF NO, WHY?
Veri ed combustible or non-combustible clearances to walls. (Pg. 8) ___________________________
Stove is installed level. (Pg. 26) ___________________________
Venting/Chimney Section 7 (Pg 27-34)
Venting con guration complies with allowable vent requirements. ___________________________
Venting installed, locked and secured in place with proper clearance. ___________________________
Interior/Exterior restops installed and sealed. ___________________________
Attic insulation shield installed. ___________________________
Exterior wall/Roof ashing installed and sealed. ___________________________
Terminations/Roof ashing installed and sealed. ___________________________
Electrical Section 8 (Pg 35-39)
Unswitched power (110-120 VAC) provided for the appliance. ___________________________
Switch wires properly installed. ___________________________
Gas Section 9 (Pg 40-41)
Appliance con guration matches fuel type. ___________________________
Was a conversion performed? ___________________________
Leak check performed and inlet/outlet pressure veri ed. ___________________________
Set air shutter for optimal ame appearance. ___________________________
Appliance Setup Section 10 (Pg 42-44)
All packaging and protective materials are from removed inside/under/on
the appliance). ___________________________
Logs and embers installed correctly. ___________________________
Glass assembly installed and secured. ___________________________
Accessories installed properly. ___________________________
Manual bag and all of its contents are removed from inside/under
the appliance and given to party responsible for use and operation. ___________________________
Started appliance and veri ed no gas leaks exist. ___________________________
2345-982 5/14
= Contains updated information.
Hearth & Home Technologies recommends the following:
• Photographing the installation and copying this checklist for your le.
• That this checklist remain visible at all times on the appliance until the installation is complete.
This standard work checklist is to be used by the installer in conjunction with, not instead of, the instructions contained in this
installation manual.
WARNING! Risk of Fire or Explosion! Failure to install appliance according to these instructions can
lead to a re or explosion.
ATTENTION INSTALLER:
Follow this Standard Work Checklist
Quadra-Fire • GARN-MBK-IPI, GARN-D-PMH-IPI, GARN-D-MBK-IPI, GARN-D-CSB-IPI Installation Manual • 2345-980_R5 • 11/144
B. GlassSpecications
        


C. BTUSpecications
        
      
Burning Heating Appliances for Manufactured Homes and


NOTICE: This installation must conform with local codes. In
the absence of local codes you must comply with the National
Fuel Gas Code, ANSI Z223.1- latest edition in the U.S.A. and
the CAN/CGA B149 Installation Codes in Canada.
A. ApplianceCertication
NOT INTENDED FOR USE AS A PRIMARY HEAT SOURCE.
This appliance is tested and approved as either supplemental
           

1
ProductSpecicandImportantSafetyInformation
MODELS: GARN-MBK-IPI, GARN-D-PMH-IPI, GARN-D-MBK-
IPI, GARN-D-CSB-IPI
LABORATORY: Underwriters Laboratories, Inc. (UL)
TYPE: Direct Vent Heater
STANDARD: ANSI Z21.88-2009/CSA 2.33-2009
D. HighAltitudeInstallations
NOTICE: If the heating value of the gas has been reduced,
these rules do not apply. Check with your local gas utility or
authorities having jurisdiction.
When installing above 2000 feet elevation:
 


of input rate for elevations up to 4500 feet (1370 m)above

having jurisdiction for installations at elevations above



E. Non-CombustibleMaterialsSpecication

those consisting entirely of steel, iron, brick, tile, concrete,

Materials that are reported as passing ASTM E 136,
Standard Test Method for Behavior of Materials in a
Vertical Tube Furnace at 750 ºC shall be considered non-

F. CombustibleMaterialsSpecication
Materials made of or surfaced with wood, compressed paper,

        

G. Electrical Codes
NOTICE: This appliance must be electrically wired and
grounded in accordance with local codes or, in the absence
of local codes, with National Electric Code ANSI/NFPA
70-latest edition or the Canadian Electric Code CSA
C22.1.
 
with ground-fault circuit-interrupter protection, in
compliance with the applicable electrical codes, when
it is installed in locations such as in bathrooms or near

Models
(U.S. or Canada)

GARN
GARN
GARN
(NG)
(0-2000 FT) 14,500 10,500 49
Maximum
Input BTU/h
Minimum
Input
BTU/h
Orice
Size
(DMS)

GARN
GARN
GARN

(0-2000 FT) 13,000 9750 57
Quadra-Fire • GARN-MBK-IPI, GARN-D-PMH-IPI, GARN-D-MBK-IPI, GARN-D-CSB-IPI Installation Manual • 2345-980_R5 • 11/145
H. Requirements for the Commonwealth of
Massachusetts

installed in every dwelling, building or structure used in
whole or in part for residential purposes, including those
owned or operated by the Commonwealth and where
         
          
including but not limited to decks and porches, the following

Installation of Carbon Monoxide Detectors

        

with an alarm and battery back-up is installed on the
          
        
        
detector with an alarm is installed on each additional level
of the dwelling, building or structure served by the side

responsibility of the property owner to secure the services



equipment is installed in a crawl space or an attic, the hard
       

In the event that the requirements of this subdivision can not
be met at the time of completion of installation, the owner
shall have a period of thirty (30) days to comply with the
above requirements; provided, however, that during said


Approved Carbon Monoxide Detectors



Signage





“GAS VENT DIRECTLY
BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.
Note: The following requirements reference various
Massachusetts and national codes not contained in this

Inspection

vented gas fueled equipment shall not approve the
installation unless, upon inspection, the inspector observes
      
       

Exemptions

(a)1 through 4:
  


 
equipment installed in a room or structure separate from
the dwelling, building or structure used in whole or in part

MANUFACTURER REQUIREMENTS
GasEquipmentVentingSystemProvided
       
      
system design or venting system components with the
equipment, the instructions provided by the manufacturer
for installation of the equipment and the venting system
shall include:
        
system design or the venting system components; and
          

GasEquipmentVentingSystemNOT Provided
       

  
      

 
be included with the appliance or equipment installation
instructions; and
 
by the Board, and the instructions for that system shall


       
venting instructions, all parts lists for venting instructions,


See Gas Connection section for additional
Commonwealth of Massachusetts requirements.
Quadra-Fire • GARN-MBK-IPI, GARN-D-PMH-IPI, GARN-D-MBK-IPI, GARN-D-CSB-IPI Installation Manual • 2345-980_R5 • 11/146
2
GettingStarted
A. DesignandInstallationConsiderations
Heat & Glo direct vent gas appliances are designed to
operate with all combustion air siphoned from outside of the


Installation MUST comply with local, regional, state and
  
       
jurisdiction over restrictions, installation inspection and

Before installing, determine the following:
 
 
 
 
 

C. Inspect Appliance and Components
 

 

 
 

Read all of the instructions before starting the
installation. Follow these instructions carefully
during the installation to ensure maximum safety
andbenet.
WARNING! Risk of Fire or Explosion! Damaged parts
could impair safe operation. DO NOT install damaged,
incomplete or substitute components. Keep appliance
dry.
B. Tools and Supplies Needed
Before beginning the installation be sure that the following

 
 
 
 
 
 
Level Reciprocating saw

Non-corrosive leak check solution

      
rating)

Hearth & Home Technologies disclaims any responsibility for,
and the warranty will be voided by, the following actions:
 

 
        

 
 

Anysuchactionmaycausearehazard.
WARNING! Risk of Fire, Explosion or Electric Shock! DO
NOT use this appliance if any part has been under water.
Call a qualied service technician to inspect the appliance
and to replace any part of the control system and/or gas
control which has been under water.
Improper installation, adjustment, alteration, service or
       


Installation and service of this appliance should be
      



Quadra-Fire • GARN-MBK-IPI, GARN-D-PMH-IPI, GARN-D-MBK-IPI, GARN-D-CSB-IPI Installation Manual • 2345-980_R5 • 11/147
3
FramingandClearances
A. ApplianceDimensionDiagram

Figure3.1ApplianceDimensions
Location Inches Millimeter Location Inches Millimeter
A  454 D  227
B  391 E  451
C  600  441
NOTE:DiagramsshowgasapplianceequippedwithoutoptionalBlower,Part#GFK-160A.
C
GAS LINE
ELECTRICAL CORD
SIDE
BACK
A
D
E
B
FRONT
TOP
F
Quadra-Fire • GARN-MBK-IPI, GARN-D-PMH-IPI, GARN-D-MBK-IPI, GARN-D-CSB-IPI Installation Manual • 2345-980_R5 • 11/148
B. Clearances to Combustibles
When selecting a location for the appliance it is important to

WARNING! Risk of Fire or Burns! Provide adequate
clearance around air openings and for service access. Due
to high temperatures, the appliance should be located out of
trafc and away from furniture and draperies.
NOTICE: Illustrations reect typical installations and are FOR
DESIGN PURPOSES ONLY. Illustrations/diagrams are not
drawn to scale. Actual installation may vary due to individual
design preference.
NOTICE: Some carpet materials may be sensitive to radiant
heat from the appliance causing discoloration or odor.
Figure3.2 ApplianceLocations
A
B
F
E
A
"A"
measurement is from
stove top, not side
D* G*
H
G**
D**
EXTERIOR
WALL
CEILING
C
C
A
G*
A
G**
C. Hearth Extension/Floor Protection
CAUTION! Risk of Fire or Injury! Install appliance on
a stable, level, platform or oor strong enough to support
appliance without tipping.
      
the floor beneath the appliance must be stable, level, and
strong enough to support the appliance without a tipping

NOTE:
      


Note:

Alcove Installation
Model A B C D* D** E F G* G** H

GARN
GARN
GARN
Inches
6 2 2  43 36 30   3
Millimeters
152 51 51 1403 1092 762 762 826 514 76
D* and G*= Vented with minimum vertical pipe as shown.
D** and G**= Horizontally vented, no vertical component.
Quadra-Fire • GARN-MBK-IPI, GARN-D-PMH-IPI, GARN-D-MBK-IPI, GARN-D-CSB-IPI Installation Manual • 2345-980_R5 • 11/149
A. Vent Termination Minimum Clearances
Roof Pitch H (Min.) Ft.













Figure4.1 MinimumHeightFromRoofToLowestDischarge
Opening
HORIZONTAL
OVERHANG
VERTICAL
WALL
GAS DIRECT VENT
TERMINATION CAP
12
X
ROOF PITCH
IS X/ 12
LOWEST
DISCHARGE
OPENING
2 FT.
MIN.
20 INCHES MIN.
H (MIN.) - MINIMUM HEIGHT FROM ROOF
TO LOWEST DISCHARGE OPENING
4
Termination Location and Vent Information

Maintain vent clearance to combustibles as

 DO NOT pack air space with insulation or other



Figure4.2 StaggeredTerminationCaps
Gas, Wood or Fuel Oil
Termination Cap
B
Gas
Term
ination
Cap **
A *
*
If using decorative cap cover(s), this distance may need to be
increased. Refer to the installation instructions supplied with the
decorative cap cover.
**
A B
6 in. (minimum) up to 20 in.
152 mm/508 mm
18 in. minimum
457 mm
20 in. and over 0 in. minimum
In a staggered installation with both gas and wood or fuel oil
terminations, the wood or fuel oil termination cap must be
higher than the gas termination cap.
WARNING
!
Quadra-Fire • GARN-MBK-IPI, GARN-D-PMH-IPI, GARN-D-MBK-IPI, GARN-D-CSB-IPI Installation Manual • 2345-980_R5 • 11/1410
B. ChimneyDiagram
Figure4.3 MinimumClearancesforTermination
A = 12 inchesclearances above grade, veranda,
porch, deck or balcony
B = clearance to window or door that may
be opened, or to permanently closed
window
C = 18 inches
18 inches
30 inchesclearance below vinyl soffits and
electrical service
D = 9 inchesclearance to outside corner
E = 6 inchesclearance to inside corner
  not to be installed above a gas

   
regulator
G = 3 ftclearance to gas service regulator vent
outlet
H = 12 clearance to non-mechanical
(unpowered) air supply inlet,
combustion air inlet or direct-vent
termination
  
clearance to a mechanical (powered)
air supply inlet
All mechanical air intakes within 10 feet of a termination cap must

   On public property: clearance above

A vent shall not terminate directly above a sidewalk or paved
driveway which is located between two single family dwellings and

C
J
B
D
B
F
B
A
E
V
V
V
V
V
V
M
H or i
V
G
X
V
H
A
V
V
H
X
= AIR SUPPLY INLET
V
= VENT TERMINAL
= AREA WHERE TERMINAL IS NOT PERMITTED
O
N
P
R
Q
Electrical
Service
V
K
V
K
V
L
C
V
Q
MIN
R
MAX
1 cap 3 feet 
ACTUAL
2 caps 6 feet 
ACTUAL
3 caps 9 feet 
ACTUAL
4 caps 12 feet 
ACTUAL
Q
MIN
=#terminationcapsx3R
MAX
=(2/#terminationcaps)xQ
ACTUAL
Covered Alcove Applications
(Spaces open only on one side and with an overhang)
N = 6 inches  non-vinyl sidewalls
12 inches  vinyl sidewalls
O = 18 inches  
42 inches  
  


CAUTION! Risk of Burns! Termination caps are HOT, consider
proximity to doors, trafc areas or where people may pass or
gather (sidewalk, deck, patio, etc.). Listed cap shields available.
Contact your dealer.
 
 NOT
 

 
improper performance of the appliance when the venting system

 
M = 18 inches clearance under veranda, porch, deck,
balcony or overhang
42 inches vinyl or composite overhang


K = 6 inches clearance from sides of electrical
service
L = 12 inches clearance above electrical service
Location of the vent termination must not interfere with access to the

Quadra-Fire • GARN-MBK-IPI, GARN-D-PMH-IPI, GARN-D-MBK-IPI, GARN-D-CSB-IPI Installation Manual • 2345-980_R5 • 11/1411
C. Approved Pipe
This appliance is approved for use with Hearth & Home


DO NOT 


is no requirement for inspection openings at each joint

WARNING! Risk of Fire or Asphyxiation. This appliance
requires a separate vent. DO NOT vent to a pipe serving a
separate solid fuel burning appliance.
DO NOT USE FIELD-FABRICATED VENTING
COMPONENTS
        

vent through a Class A or masonry chimney if an approved






 is required

      is required when the

 

 

Quadra-Fire • GARN-MBK-IPI, GARN-D-PMH-IPI, GARN-D-MBK-IPI, GARN-D-CSB-IPI Installation Manual • 2345-980_R5 • 11/1412
D. Use of Elbows

         




         



Figure4.4
HORIZONTAL
VERTICAL
RUN
RISE
EFFECTIVE
LENGTH
Y
X
X
X
Vent Type
X
Inches Millimeters
  286
Figure4.5VerticalandHorizontalOffsetforSLPElbows
Vent
Type
X Y
Inches Millimeters Inches Millimeters
 5 127  298
SLP
Pipe
EffectiveLength Rise/Run
Inches Millimeters Inches Millimeters
 4 102  70
 6 152  108
 12 305  216
 24 610 17 432
 36 914  648
 48 1219 34 864
 3 to 6 76 to 152
 54-108
 3 to 12 76 to 305
 54-216
E. MeasuringStandards
       
diagrams were made using the following standards:
 


      


      

 
Y
X
X
X
Quadra-Fire • GARN-MBK-IPI, GARN-D-PMH-IPI, GARN-D-MBK-IPI, GARN-D-CSB-IPI Installation Manual • 2345-980_R5 • 11/1413
G. VentDiagrams
General Rules:
 

 

 


 

 

F. VentingGuidelinesforHorizontalRuns
C
L
Figure4.6
C
L
REAR VENT
(WITH VERTICAL RISE)
2 FT.
MINIMUM




 


Rise
Min of 2 ft vertical (610 mm)
must be used prior to any




Quadra-Fire • GARN-MBK-IPI, GARN-D-PMH-IPI, GARN-D-MBK-IPI, GARN-D-CSB-IPI Installation Manual • 2345-980_R5 • 11/1414
Rear Vent - Horizontal Termination
Figure4.7
No Elbow
H
1
= 8 in. (203 mm) Maximum
H
1
Quadra-Fire • GARN-MBK-IPI, GARN-D-PMH-IPI, GARN-D-MBK-IPI, GARN-D-CSB-IPI Installation Manual • 2345-980_R5 • 11/1415
Rear Vent - Horizontal Termination - (continued)
Two Elbows
Figure4.8
H
1
H
2
V
1
Note:         

Note:

2 Elbows to Max. Horizontal
V
1
Minimum H
1
Maximum H
1
+ H
2
Maximum
2 ft   203 mm  
   203 mm  1 m
   203 mm  
   203 mm  
   203 mm  
   203 mm  
   203 mm  
   203 mm  
   203 mm  
   203 mm  813 mm
   203 mm  559 mm
Quadra-Fire • GARN-MBK-IPI, GARN-D-PMH-IPI, GARN-D-MBK-IPI, GARN-D-CSB-IPI Installation Manual • 2345-980_R5 • 11/1416
Figure4.9
Three Elbows
INSTALLED
HORIZONTALLY
H
3
H
1
H
2
V
1
Note:         

Note:

3 Elbows to Max. Horizontal
V
1
Minimum H
1
Maximum H
Total
   203 mm  914 mm
   203 mm  
   203 mm  
   203 mm  
   203 mm  737 mm
   203 mm  457 mm
Quadra-Fire • GARN-MBK-IPI, GARN-D-PMH-IPI, GARN-D-MBK-IPI, GARN-D-CSB-IPI Installation Manual • 2345-980_R5 • 11/1417
Rear Vent - Vertical Termination
One Elbow
Figure4.10
H
1
V
1
H
1
Minimum H
1
Maximum V
1
Minimum V
1
Maximum
 152 mm  357 mm    
Note:         

Note:

Quadra-Fire • GARN-MBK-IPI, GARN-D-PMH-IPI, GARN-D-MBK-IPI, GARN-D-CSB-IPI Installation Manual • 2345-980_R5 • 11/1418
V
2
V
1
H
2
H
1
Rear Vent - Vertical Termination - (continued)
Three Elbows
Figure4.11
Note:         

Note:

3 Elbows to Maximum Vertical
V
1
Minimum H
1
Maximum H
Total
V
1
+ V
2
MAXIMUM
   203 mm  914 mm  
   203 mm    
   203 mm    
   203 mm    
   203 mm  737 mm  
   203 mm  457 mm  
Quadra-Fire • GARN-MBK-IPI, GARN-D-PMH-IPI, GARN-D-MBK-IPI, GARN-D-CSB-IPI Installation Manual • 2345-980_R5 • 11/1419
TERMINATION
CAP
EXISTING
METAL
CHIMNEY
SYSTEM
TOP
ADAPTOR
FLASHING
4 in. (102mm)
FLEX PIPE
RETRO CONNECTOR
DIRECT VENT PIPE
Class A Metal Chimney


 


professionals, or technicians under the direction of
       

 

Figure4.14
Figure4.15
 



 
center the retro connector, and attach it to the support

        
connector may be completed with sections of direct vent

Figure4.13
Figure4.12
 
 
    
       

 


          
chimney system, and center the top adapter on the top
         
holes through the top adapter, and into the chimney top,
 



High Wind Termination
Cap
Sheet Metal Screws
Drill Four 1/8 in. (3mm)
Diameter Holes
Quadra-Fire • GARN-MBK-IPI, GARN-D-PMH-IPI, GARN-D-MBK-IPI, GARN-D-CSB-IPI Installation Manual • 2345-980_R5 • 11/1420
ExistingMasonryChimney

 
              

 
Type C - Up & Out Installation Type D - Hearth Mount
Figure4.16
Type A & B Co-Axial to Co-Linear
Chimney Liner
Termination Cap
Co-Axial to
Co-Linear Connector
3 in. (76mm)
Flex Liner
Showing two
30 ft.
(9m)Sections
of Flex Liner
Chimney Liner
Termination Cap
Co-Axial to
Co-Linear Connector
30 ft. (9m) of 3 in.
(76mm) Flex Liner
Exhaust Section
4 ft. (1m) of 3 in. (76mm)
Flex Liner Air Intake Section
This section of the
chimney must be
sealed.
The chimney must be sealed
from the coaxial/colinear
connection to the termination.
TERMINATION
CAP
FLASHING
4 in. (102mm) FLEX
LINER
TOP ADAPTOR
RETRO
CONNECTOR
90° ELBOW
DIRECT
VENT PIPE
Chimney Liner
Termination Cap
30 ft. (9m) of 3 in. (76mm)
Flex Liner Exhaust Section
4 ft. (1m) of 3 in. (76mm) Flex
Liner Air Intake Section
Chimney must be sealed from
the coaxial/colinear
connection to the termination .
This section of the chimney
must be sealed.
Co-Axial to Co-Linear Connector
Alcove Clearance to
Combustibles must be
maintained. See Figure 3.2.
See COAXIAL/COLINEAR
SectionandFigure4.31.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50