  • Hello! I'm your chat assistant. I've reviewed the Installation Manual for Heat & Glo fireplaces models TIARAI-BK-IPI, TIARAI-BR-IPI, TIARAI-BK-IPIL, and TIARAI-BR-IPIL. This document includes detailed instructions on how to install your direct vent gas heater, with important safety information regarding clearances, gas connections, and dealing with hot surfaces. I can answer your questions about these fireplaces, so feel free to ask!
  • What should I do if I smell gas?
    Can this appliance be installed in a mobile home?
    What type of gas is this appliance for?
    Who should install this appliance?
Heat & Glo • TIARAI-IPI Installation Manual • 2342-980_R29 • 06/221
Installation Manual
Installation and Appliance Setup
INSTALLER: Leave this manual with party responsible for use and operation.
OWNER: Retain this manual for future reference.
This appliance may be installed as an OEM installation
in manufactured home (USA only) or mobile home and
must be installed in accordance with the manufacturer’s
instructions and the manufactured home construction
and safety standard, Title 24 CFR, Part 3280 or Standard
for Installation in Mobile Homes, CAN/CSA Z240MH, in
Canada.
This appliance is only for use with the type(s) of gas
indicated on the rating plate.
In the Commonwealth of Massachusetts installation must be
performed by a licensed plumber or gas tter.
See Table of Contents for location of additional Commonwealth
of Massachusetts requirements.
NOTICE: DO NOT discard this manual!
Models:
TIARAI-BK-IPI
TIARAI-BR-IPI
TIARAI-BK-IPIL
TIARAI-BR-IPIL
- DO NOT store or use gasoline or other ammable
vapors and liquids in the vicinity of this or any other
appliance.
- What to do if you smell gas
DO NOT try to light any appliance.
DO NOT touch any electrical switch; do not use any
phone in your building.
• Immediately call your gas supplier from a neighbor’s
phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the re
department.
- Installation and service must be performed by a qualied
installer, service agency, or the gas supplier.
WARNING: If the information in these
instructions is not followed exactly, a fire or
explosion may result causing property damage,
personal injury, or death.
Installation and service of this appliance should be performed by
qualied personnel. Hearth & Home Technologies recommends
HHT Factory Trained or NFI certied professionals.
This unit has been retired.
DANGER
HOT GLASS WILL
CAUSE BURNS.
DO NOT TOUCH GLASS
UNTIL COOLED.
NEVER ALLOW CHILDREN
TO TOUCH GLASS.
Un panneau vitré chaud peut
causer des brûlures.
Laissez refroidir le panneau
vitré avant d’y toucher.
Ne laisser jamais les enfants
toucher le panneau vitré.
A barrier designed to reduce the risk of burns from
the hot viewing glass is provided with this
appliance and shall be installed.
Une barrière visant à réduire le risque de brûlure
par le hublot chaude est fournie avec cet
appareil et doit être installé.
DANGER
Heat & Glo • TIARAI-IPI Installation Manual • 2342-980_R29 • 06/222
Safety Alert Key:
DANGER! Indicates a hazardous situation which, if not avoided will result in death or serious injury.
WARNING! Indicates a hazardous situation which, if not avoided could result in death or serious injury.
CAUTION! Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
NOTICE: Used to address practices not related to personal injury.
Installation Standard Work Checklist ....................3

A. Appliance Certication ............................4
B. Glass Specications ..............................4
C. BTU Specications ...............................4
D. High Altitude Installations ..........................4
E. Non-Combustible Materials Specication. . . . . . . . . . . . . . 4
F. Combustible Materials Specication .................4
G. Electrical Codes .................................4
H. California Safety Warning ..........................4
I. Requirements for the Commonwealth of Massachusetts . . 5
2 Getting Started
A. Design and Installation Considerations ...............6
B. Tools and Supplies Needed ........................6
C. Inspect Appliance and Components ..................6
3 Framing and Clearances
A. Appliance Dimension Diagram ......................7
B. Clearances to Combustibles .......................8
C. Hearth Extension/Floor Protection ...................8
4 Termination Location and Vent Information
A. Vent Termination Minimum Clearances ...............9
B. Chimney Diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
C. Approved Pipe ................................. 11
D. Use of Elbows .................................12
E. Measuring Standards ............................12
F. Venting Guidelines for Horizontal Runs .............. 13
G. Vent Diagrams .................................13
5 Vent Clearances and Framing
A. Pipe Clearances to Combustibles ..................30
B. Wall Penetration Framing/Firestops .................30
C. Ceiling Firestop/Floor Penetration Framing ...........31
D. Install Attic Insulation Shield .......................31
6 Appliance Preparation
A. Top to Rear Vent Conversion ......................32
B. Securing and Leveling the Appliance ................35
7 Venting and Chimneys
A. Assemble Vent Sections. . . . . . . . . . . . . . . . . . . . . . . . . . 36
B. Assemble Slip Sections ..........................37
C. Secure the Vent Sections .........................38
D. Disassemble Vent Sections .......................38
E. Vertical Termination Requirements .................. 40
F. Horizontal Termination Requirements ...............42
8 Electrical Information
A. General Information .............................44
B. Wiring Requirements ............................ 45
9 Gas Information
A. Fuel Conversion ................................48
B. Gas Pressure ..................................48
C. Gas Connection ................................48
D. High Altitude Installations .........................48
E. Air Shutter Setting ..............................49
10 Appliance Setup
A. Remove Fixed Glass Assembly .................... 50
B. Remove Shipping Materials and Install Knob. . . . . . . . . . 50
C. Clean the Appliance .............................50
D. Install Top Bae ................................50
E. Install the Log Assembly. . . . . . . . . . . . . . . . . . . . . . . . . . 51
F. Install Fixed Glass Assembly ...................... 52
11 Reference Materials
A. Vent Components Diagrams ...................... 53
B. Accessories ...................................58
= Contains updated information.
Table of Contents
Heat & Glo • TIARAI-IPI Installation Manual • 2342-980_R29 • 06/223
Installation Standard Work Checklist
Customer:
Lot/Address:
Model (circle one): TIARAI-BK-IPI TIARAI-BK-IPIL
TIARAI-BR-IPI TIARAI-BR-IPIL
TIARAI-CES-IPI TIARAI-CES-IPIL
Date Installed:
Location of Stove:
Installer:
Dealer/Distributor Phone #
Serial #:
Comments: Further description of the issues, who is responsible (Installer/ Builder/ Other Trades, etc) and corrective
action needed _____________________________________________________________________________________
_________________________________________________________________________________________________
_________________________________________________________________________________________________
Comments Communicated to party responsible ____________________ by ______________________on ___________
(Builder / Gen. Contractor/) (Installer) (Date)
Appliance Install YES IF NO, WHY?
Veri ed combustible or non-combustible clearances to walls. (Pg. 8) ___________________________
Stove is installed level. (Pg. 35) ___________________________
Venting/Chimney Section 7 (Pg 36-43)
Venting con guration complies with allowable vent requirements. ___________________________
Venting installed, locked and secured in place with proper clearance. ___________________________
Interior/Exterior restops installed and sealed. ___________________________
Attic insulation shield installed. ___________________________
Exterior wall/Roof ashing installed and sealed. ___________________________
Terminations/Roof ashing installed and sealed. ___________________________
Electrical Section 8 (Pg 44-47)
Unswitched power (110-120 VAC) provided for the appliance. ___________________________
Switch wires properly installed. ___________________________
Gas Section 9 (Pg 48-49)
Appliance con guration matches fuel type. ___________________________
Was a conversion performed? ___________________________
Leak check performed and inlet/outlet pressure veri ed. ___________________________
Set air shutter for optimal ame appearance. ___________________________
Appliance Setup Section 10 (Pg 50-52)
All packaging and protective materials are from removed inside/under/on
the appliance). ___________________________
Refractories, logs, and embers installed correctly. ___________________________
Glass assembly installed and secured. ___________________________
Accessories installed properly. ___________________________
Mesh, doors, or decorative front properly installed. ___________________________
Manual bag and all of its contents are removed from inside/under
the appliance and given to party responsible for use and operation. ___________________________
Started appliance and veri ed no gas leaks exist. ___________________________
2342-982 Rev. B 2/14
= Contains updated information.
Hearth & Home Technologies recommends the following:
• Photographing the installation and copying this checklist for your le.
• That this checklist remain visible at all times on the appliance until the installation is complete.
This standard work checklist is to be used by the installer in conjunction with, not instead of, the instructions contained in
this
installation manual.
WARNING! Risk of Fire or Explosion! Failure to install appliance according to these instructions can
lead to a re or explosion.
ATTENTION INSTALLER:
Follow this Standard Work Checklist
Heat & Glo • TIARAI-IPI Installation Manual • 2342-980_R29 • 06/224
 
This appliance is equipped with 5 mm ceramic glass.
Replace glass only with 5 mm ceramic glass. Please contact
your dealer for replacement glass.
 
This product is listed to ANSI standards for “Vented Gas
Fireplace Heaters” and applicable sections of “Gas
Burning Heating Appliances for Manufactured Homes and
Recreational Vehicles”, and “Gas Fired Appliances for Use
at High Altitudes”.
NOTICE: This installation must conform with local codes. In
the absence of local codes you must comply with the National
Fuel Gas Code, ANSI Z223.1-latest edition in the U.S.A. and
the CAN/CGA B149 Installation Codes in Canada.
 
NOT INTENDED FOR USE AS A PRIMARY HEAT SOURCE.
This appliance is tested and approved as either supplemental
room heat or as a decorative appliance. It should not be
factored as primary heat in residential heating calculations.
1 1  
MODELS: TIARAI-BK-IPI, TIARAI-BR-IPI, TIARAI-CES-IPI
LABORATORY: Underwriters Laboratories, Inc. (UL)
TYPE: Direct Vent Heater
STANDARD: ANSI Z21.88-2019/CSA 2.33-2019
 
Material which will not ignite and burn. Such materials are
those consisting entirely of steel, iron, brick, tile, concrete,
slate, glass or plasters, or any combination thereof.
Materials that are reported as passing ASTM E 136,
Standard Test Method for Behavior of Materials in a
Vertical Tube Furnace at 750 ºC shall be considered non-
combustible materials.
 
Materials made of or surfaced with wood, compressed paper,
plant bers, plastics, or other material that can ignite and burn,
whether ame proofed or not, or plastered or unplastered
shall be considered combustible materials.
G. Electrical Codes
NOTICE: This appliance must be electrically wired and
grounded in accordance with local codes or, in the absence
of local codes, with National Electric Code ANSI/NFPA
70-latest edition or the Canadian Electric Code CSA
C22.1.
A 110-120 VAC circuit for this product must be protected
with ground-fault circuit-interrupter protection, in
compliance with the applicable electrical codes, when
it is installed in locations such as in bathrooms or near
sinks.
H. California Safety Warning
Models
(U.S. or Canada)
Maximum
Input
BTU/h
Minimum
Input
BTU/h

Size
(DMS)
AFUE
State
Steady


TIARAI-BK-IPI
TIARAI-BR-IPI
TIARAI-CES-IPI
(Natrural Gas)
(0-2000 FT) 25,000 19,500 42 67.4% 69.6% 74.3%
TIARAI-BK-IPIL
TIARAI-BR-IPIL
TIARAI-CES-IPIL
(Propane)
(0-2000 FT) 22,500 16,500 54 72.1% 74.5% 78.1%
!WARNING
This product and the fuels used to operate this product
(liquid propane or natural gas), and the products of
combustion of such fuels, can expose you to chemicals
including benzene, which is known to the State of
California to cause cancer and reproductive harm. For
more information go to: www.P65Warnings.ca.gov.
D. High Altitude Installations
NOTICE: If the heating value of the gas has been reduced,
these rules do not apply. Check with your local gas utility or
authorities having jurisdiction.
When installing above 2000 feet elevation:
• In the USA: Reduce input rate 4% for each 1000 feet above
2000 feet.
In CANADA: Input ratings are certied without a reduction
of input rate for elevations up to 4500 feet (1370 m)above
sea level. Please consult provincial and/or local authorities
having jurisdiction for installations at elevations above
4500 feet (1370 m).
Check with your local gas utility to determine proper orice
size.
Heat & Glo • TIARAI-IPI Installation Manual • 2342-980_R29 • 06/225
I. Requirements for the Commonwealth of
Massachusetts
For all side wall horizontally vented gas fueled equipment
installed in every dwelling, building or structure used in
whole or in part for residential purposes, including those
owned or operated by the Commonwealth and where
the side wall exhaust vent termination is less than seven
(7) feet above nished grade in the area of the venting,
including but not limited to decks and porches, the following
requirements shall be satised:
Installation of Carbon Monoxide Detectors
At the time of installation of the side wall horizontal vented
gas fueled equipment, the installing plumber or gas tter
shall observe that a hard wired carbon monoxide detector
with an alarm and battery back-up is installed on the
oor level where the gas equipment is to be installed. In
addition, the installing plumber or gas tter shall observe
that a battery operated or hard wired carbon monoxide
detector with an alarm is installed on each additional level
of the dwelling, building or structure served by the side
wall horizontal vented gas fueled equipment. It shall be the
responsibility of the property owner to secure the services
of qualied licensed professionals for the installation of hard
wired carbon monoxide detectors.
In the event that the side wall horizontally vented gas fueled
equipment is installed in a crawl space or an attic, the hard
wired carbon monoxide detector with alarm and battery
back-up may be installed on the next adjacent oor level.
In the event that the requirements of this subdivision can not
be met at the time of completion of installation, the owner
shall have a period of thirty (30) days to comply with the
above requirements; provided, however, that during said
thirty (30) day period, a battery operated carbon monoxide
detector with an alarm shall be installed.
Approved Carbon Monoxide Detectors
Each carbon monoxide detector as required in accordance
with the above provisions shall comply with NFPA 720 and
be ANSI/UL 2034 listed and IAS certied.
Signage
A metal or plastic identication plate shall be permanently
mounted to the exterior of the building at a minimum height
of eight (8) feet above grade directly in line with the exhaust
vent terminal for the horizontally vented gas fueled heating
appliance or equipment. The sign shall read, in print size no
less than one-half (1/2) in. in size, “GAS VENT DIRECTLY
BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.
Note: The following requirements reference various
Massachusetts and national codes not contained in this
document.
Inspection
The state or local gas inspector of the side wall horizontally
vented gas fueled equipment shall not approve the
installation unless, upon inspection, the inspector observes
carbon monoxide detectors and signage installed in
accordance with the provisions of 248 CMR 5.08(2)(a)1
through 4.
Exemptions
The following equipment is exempt from 248 CMR 5.08(2)
(a)1 through 4:
• The equipment listed in Chapter 10 entitled “Equipment
Not Required To Be Vented” in the most current edition of
NFPA 54 as adopted by the Board; and
• Product Approved side wall horizontally vented gas fueled
equipment installed in a room or structure separate from
the dwelling, building or structure used in whole or in part
for residential purposes.
MANUFACTURER REQUIREMENTS
Gas Equipment Venting System Provided
When the manufacturer of Product Approved side wall
horizontally vented gas equipment provides a venting
system design or venting system components with the
equipment, the instructions provided by the manufacturer
for installation of the equipment and the venting system
shall include:
• Detailed instructions for the installation of the venting
system design or the venting system components; and
A complete parts list for the venting system design or
venting system.
Gas Equipment Venting System NOT Provided
When the manufacturer of a Product Approved side wall
horizontally vented gas fueled equipment does not provide
the parts for venting the ue gases, but identies “special
venting systems”, the following requirements shall be
satised by the manufacturer:
• The referenced “special venting system” instructions shall
be included with the appliance or equipment installation
instructions; and
• The “special venting systems” shall be Product Approved
by the Board, and the instructions for that system shall
include a parts list and detailed installation instructions.
A copy of all installation instructions for all Product Approved
side wall horizontally vented gas fueled equipment, all
venting instructions, all parts lists for venting instructions,
and/or all venting design instructions shall remain with the
appliance or equipment at the completion of the installation.
See Gas Connection section for additional Commonwealth
of Massachusetts requirements.
Heat & Glo • TIARAI-IPI Installation Manual • 2342-980_R29 • 06/226
2 2 Getting Started
A. Design and Installation Considerations
Heat & Glo direct vent gas appliances are designed to
operate with all combustion air siphoned from outside of the
building and all exhaust gases expelled to the outside. No
additional outside air source is required.
Installation MUST comply with local, regional, state and
national codes and regulations. Consult insurance carrier,
local building inspector, re ocials or authorities having
jurisdiction over restrictions, installation inspection and
permits.
Before installing, determine the following:
• Where the appliance is to be installed.
• The vent system conguration to be used.
• Gas supply piping requirements.
• Electrical wiring requirements.
• Whether optional accessories—devices such as a fan or
remote control—are desired.
C. Inspect Appliance and Components
Carefully remove the appliance and components from the
packaging.
The vent system components and optional accessories
may be shipped in separate packages.
• If packaged separately, the log set must be installed.
• Report to your dealer any parts damaged in shipment,
particularly the condition of the glass.
Read all of the instructions before starting the
installation. Follow these instructions carefully during

WARNING! Risk of Fire or Explosion! Damaged parts
could impair safe operation. DO NOT install damaged,
incomplete or substitute components. Keep appliance dry.
B. Tools and Supplies Needed
Before beginning the installation be sure that the following
tools and building supplies are available.
Tape measure Framing material
Pliers Hammer
Phillips screwdriver Manometer
Gloves Framing square
Voltmeter Electric drill and bits (1/4 in.)
Plumb line Safety glasses
Level Reciprocating saw
Flat blade screwdriver
Non-corrosive leak check solution
1/2 - 3/4 in. length, #6 or #8 Self-drilling screws
Caulking material (300º F minimum continuous exposure
rating)
One 1/4 in. female connection (for optional fan).
Hearth & Home Technologies disclaims any responsibility for,
and the warranty will be voided by, the following actions:
Installation and use of any damaged appliance or vent system
component.
Modication of the appliance or vent system.
Installation other than as instructed by Hearth & Home
Technologies.
Improper positioning of the gas logs or the glass door.
Installation and/or use of any component part not approved
by Hearth & Home Technologies.

WARNING! Risk of Fire, Explosion or Electric Shock! DO
NOT use this appliance if any part has been under water.
Call a qualied service technician to inspect the appliance
and to replace any part of the control system and/or gas
control which has been under water.
Improper installation, adjustment, alteration, service or
maintenance can cause injury or property damage. For
assistance or additional information, consult a qualied service
technician, service agency or your dealer.
Installation and service of this appliance should be
performed by qualied personnel. Hearth & Home
Technologies suggests NFI certied or factory trained
professionals, or technicians supervised by an NFI
certied professional (www.ncertied.org).
Heat & Glo • TIARAI-IPI Installation Manual • 2342-980_R29 • 06/227
3 3 Framing and Clearances
A. Appliance Dimension Diagram
Dimensions are actual appliance dimensions. Use for reference only.
Figure 3.1 - Appliance Dimensions
Location Inches Millimeter Location Inches Millimeter
A23-1/4 590 F20 506
B9-3/8 237 G 17-1/2 445
C 27 686 H 13-7/8 352
D20-1/4 514 I 12-3/8 314
E11-3/4 298
NOTE: Diagrams show gas appliance equipped without optional Blower, Part #GFK-160A.
Installation of optional blower does not effect overall dimensions
FRONT SIDE
A
B
C
D
E
F
BACK
GAS LINE
ELECTRICAL
CORD
H
G
C
LC
L
I I
Heat & Glo • TIARAI-IPI Installation Manual • 2342-980_R29 • 06/228
B. Clearances to Combustibles
When selecting a location for the appliance it is important to
consider the required clearances to walls, Figure 3.2.
WARNING! Risk of Fire or Burns! Provide adequate
clearance around air openings and for service access. Due
to high temperatures, the appliance should be located out of
trac and away from furniture and draperies.
NOTICE: Illustrations reect typical installations and are FOR
DESIGN PURPOSES ONLY. Illustrations/diagrams are not
drawn to scale. Actual installation may vary due to individual
design preference.
NOTICE: Some carpet materials may be sensitive to radiant
heat from the appliance causing discoloration or odor.
Figure 3.2 - Appliance Locations
Model A B *B C *C D E F G
H
Top of
pipe
Side of
pipe
TIARAI-IPI
Inches 8-1/2 1/4 53/8 4 54 36 40-1/4 27 3 1
Millimeters 216 6 127 10 102 1372 914 1022 686 76 25
A
B
E
A
"A"
measurement is from
stove top, not side
or *B
F
G
H
D
C or *C
C
or *C
A
G
A
C. Hearth Extension/Floor Protection
CAUTION! Risk of Fire or Injury! Install appliance on
a stable, level, platform or oor strong enough to support
appliance without tipping.
A non-combustible hearth pad is not required. However,
the floor beneath the appliance must be stable, level, and
strong enough to support the appliance without a tipping
hazard. It is permissible to place the appliance on carpet.
NOTE: Flooring beneath appliance may reach 90 degrees
plus room ambient temperature. Check with flooring
manufacturer for maximum temperature allowed on flooring
surfaces.
Alcove Installation
Note: Dimensions are minimums as shown and may not be typical for all applications. An alcove installation is
shown above on left.
*Installation of optional blower does not eect minimum clearance dimensions, however, if frequent blower removal
service is desired, clearance to the wall should be increased to *B and *C Dimensions.
Heat & Glo • TIARAI-IPI Installation Manual • 2342-980_R29 • 06/229
A. Vent Termination Minimum Clearances
Roof Pitch H (Min.) Ft.
Flat to 6/12.............................................................1.0*
Over 6/12 to 7/12 ..................................................1.25*
Over 7/12 to 8/12 ...................................................1.5*
Over 8/12 to 9/12 ...................................................2.0*
Over 9/12 to 10/12 .................................................2.5*
Over 10/12 to 11/12 .............................................. 3.25
Over 11/12 to 12/12 ............................................... 4.0
Over 12/12 to 14/12 ............................................... 5.0
* 3 foot minimum in snow regions
Figure 4.1 - Minimum Height From Roof To Lowest Discharge Opening
HORIZONTAL
OVERHANG
VERTICAL
WALL
GAS DIRECT VENT
TERMINATION CAP
12
X
ROOF PITCH
IS X/ 12
LOWEST
DISCHARGE
OPENING
2 FT.
MIN.
20 INCHES MIN.
H (MIN.) - MINIMUM HEIGHT FROM ROOF
TO LOWEST DISCHARGE OPENING
4 4 Termination Location and Vent Information
Fire Risk.
Maintain vent clearance to combustibles as
specied.
DO NOT pack air space with insulation or other
materials.
Failure to keep insulation or other materials away
from vent pipe may cause overheating and re.
Figure 4.2 - Staggered Termination Caps
Gas, Wood or Fuel Oil
Termination Cap
B
Gas
Termination
Cap **
A *
*If using decorative cap cover(s), this distance may need to be
increased. Refer to the installation instructions supplied with the
decorative cap cover.
**
A B
6 in. (minimum) up to 20 in.
152 mm/508 mm
18 in. minimum
457 mm
20 in. and over 0 in. minimum
In a staggered installation with both gas and wood or fuel oil
terminations, the wood or fuel oil termination cap must be
higher than the gas termination cap.
WARNING
!
Heat & Glo • TIARAI-IPI Installation Manual • 2342-980_R29 • 06/2210
B. Chimney Diagram
Figure 4.3 - Minimum Clearances for Termination
A = 12 inches.................clearances above grade, veranda,
porch, deck or balcony
B = 12 inches.................clearance to window or door that may
be opened, or to permanently closed
window
C = 18 inches.................clearance below unventilated sot
18 inches.................clearance below ventilated sot
30 inches .................clearance below vinyl soffits and
electrical service
D = 9 inches...................clearance to outside corner
E = 6 inches...................clearance to inside corner
F = 3 ft. (Canada) ..........not to be installed above a gas
meter/regulator assembly within 3 feet
horizontally from the center-line of the
regulator
G = 3 ft ...........................clearance to gas service regulator vent
outlet
H = 12 inches.................clearance to non-mechanical
(unpowered) air supply inlet,
combustion air inlet or direct-vent
termination
i = 3 ft. (U.S.A.)
6 ft. (Canada) ...........clearance to a mechanical (powered)
air supply inlet
All mechanical air intakes within 10 feet of a termination cap must
be a minimum of 3 feet below termination.
J = 7 ft. ......................... On public property: clearance above
paved sidewalk or a paved driveway.
A vent shall not terminate directly above a sidewalk or paved
driveway which is located between two single family dwellings and
serves both dwellings.
C
JB
D
B
F
B
A
E
V
V
V
V
V
V
M
H or i
V
G
X
VH
A
VV
H
X= AIR SUPPLY INLET
V= VENT TERMINAL
= AREA WHERE TERMINAL IS NOT PERMITTED
O
N
P
R
Q
Electrical
Service
V
K
V K
V
L
C
V
QMIN RMAX
1 cap 3 feet 2 x Q ACTUAL
2 caps 6 feet 1 x Q ACTUAL
3 caps 9 feet 2/3 x Q ACTUAL
4 caps 12 feet 1/2 x Q ACTUAL
QMIN = # termination caps x 3 RMAX = (2 / # termination caps) x QACTUAL
Covered Alcove Applications
(Spaces open only on one side and with an overhang)
N = 6 inches ........... non-vinyl sidewalls
12 inches ......... vinyl sidewalls
O = 18 inches ......... non-vinyl sot and overhang
42 inches ......... vinyl sot and overhang
P = 8 ft.
Measure horizontal clearances from this surface.
Measure vertical clearances from this surface.
CAUTION! Risk of Burns! Termination caps are HOT, consider
proximity to doors, trac areas or where people may pass or
gather (sidewalk, deck, patio, etc.). Listed cap shields available.
Contact your dealer.
Local codes or regulations may require dierent clearances.
Vent system termination is NOT permitted in screened porches.
Vent system termination is permitted in porch areas with two or
more sides open.
Hearth & Home Technologies assumes no responsibility for the
improper performance of the appliance when the venting system
does not meet these requirements.
Vinyl protection kits are suggested for use with vinyl siding.
M = 18 inches .................... clearance under veranda, porch, deck,
balcony or overhang
42 inches ................vinyl or composite overhang
Permitted when veranda, porch, deck or balcony is fully open on a
minimum of 2 sides beneath the oor.
K = 6 inches................. clearance from sides of electrical
service
L = 12 inches................ clearance above electrical service
Location of the vent termination must not interfere with access to the
electrical service.
Heat & Glo • TIARAI-IPI Installation Manual • 2342-980_R29 • 06/2211
C. Approved Pipe
This appliance is approved for use with Hearth & Home
Technologies SLP, Simpson Duravent and ICC venting
systems. Refer to Section 11.A for vent component
information and dimensions.
DO NOT mix pipe, ttings or joining methods from dierent
manufacturers.
The pipe is tested to be run inside an enclosed wall. There
is no requirement for inspection openings at each joint
within the wall.
WARNING! Risk of Fire or Asphyxiation. This appliance
requires a separate vent. DO NOT vent to a pipe serving a
separate solid fuel burning appliance.
DO NOT USE FIELD-FABRICATED VENTING
COMPONENTS.
This product is approved to be vented either horizontally,
through the side wall or vertically through the roof. You may
vent through a Class A or masonry chimney if an approved
adapter is used.
This appliance is a direct vent heater. All combustion air must
come directly from the outside of the building. The vent pipe
for this unit consists of an inner and an outer pipe. The inner
pipe carries the appliance exhaust out of the system, and
the outer pipe brings fresh combustion air into the appliance.
A round support box/wall thimble or heat shield is required
when the venting passes through a combustible wall.
A support box or ceiling restop is required when the
venting passes through a ceiling.
• Roof ashing and a storm collar are required when venting
passes through the roof.
• Follow instructions provided with the venting for installation
of these items.
Heat & Glo • TIARAI-IPI Installation Manual • 2342-980_R29 • 06/2212
D. Use of Elbows
Diagonal runs have both vertical and horizontal vent aspects
when calculating the eects. Use the rise for the vertical
aspect and the run for the horizontal aspect. See Figure 4.4.
Two 45º elbows may be used in place of one 90º elbow. On
45º runs, one foot of diagonal is equal to 8-1/2 in. (216 mm)
horizontal run and 8-1/2 in. (216 mm) vertical run. A length of
straight pipe is allowed between two 45º elbows, Figure 4.4.
Figure 4.5 shows the vertical and horizontal osets for SLP
elbows.
Y
X
X
X
Vent Type X
Inches Millimeters
SLP 11-1/4 286
Vent
Type
X Y
Inches Millimeters Inches Millimeters
SLP 5 127 11-3/4 298
Figure 4.4
HORIZONTAL
VERTICAL
RUN
RISE
EFFECTIVE
LENGTH
SLP
Pipe
 Rise/Run
Inches Millimeters Inches Millimeters
SLP4 4 102 2-3/4 70
SLP6 6 152 4-1/4 108
SLP12 12 305 8-1/2 216
SLP24 24 610 17 432
SLP36 36 914 25-1/2 648
SLP48 48 1219 34 864
SLP6A 3 to 6 76 to 152 2-1/8-4-1/4 54-108
SLP12A 3 to 12 76 to 305 2-1/8-8-1/2 54-216
Figure 4.5 - Vertical and Horizontal Oset for SLP Elbows
E. Measuring Standards
Vertical and horizontal measurements listed in the vent
diagrams were made using the following standards:
• Pipe measurements are shown using the eective length of
pipe. See Figure 11.1 for SLP for information on eective
length of pipe components.
Horizontal terminations are measured to the outside
mounting surface (ange of termination cap), Figure 4.3.
Vertical terminations are measured to bottom of
termination cap.
• Horizontal pipe installed level with 1/4 inch rise per foot.
Y
X
X
X
Heat & Glo • TIARAI-IPI Installation Manual • 2342-980_R29 • 06/2213
G. Vent Diagrams
To replace the rst 90º starter elbow with two 45º elbows,
refer to Figure 4.7. All other 90º elbows can be replaced
with two 45º elbows.
General Rules:
• SUBTRACT 3 ft. from the total H measurement for each
90º elbow installed horizontally.
• SUBTRACT 1 ft. from the total H measurement for each
45º elbow installed horizontally.
• A maximum of three 90º elbows (or six 45º elbows) may
be used in any vent conguration. Some elbows may be
installed horizontally. See specic vent diagrams.
• When penetrating a combustible wall, a wall shield restop
must be installed.
• When penetrating a combustible ceiling, a ceiling restop
must be installed.
Top Vent—Horizontal Termination—Two 45º Elbows
Installation requirements to replace the rst 90º elbow
with two 45º elbows:
4 ft min.
(1.22 m)
Figure 4.7
Figure 4.6
F. Venting Guidelines for Horizontal Runs
C
L
Snorkel Kit
Max Horizontal Run,
Rear Vent (No Rise)
14 in. (356 mm)
Snorkel kit and derating orice
must be used. See Figure 4.6.
Max Horizontal Run 14 ft (4.3 m) when vertical rise
is 10 ft (3m)
Max Horizontal Run
Rear Vent with 45o
Elbow (No Rise)
14 in. (356 mm)
Snorkel kit and derating orice
must be used. See Figure 4.6.
Rear Vent with Vertical
Rise
Min of 2 ft vertical (610 mm)
must be used prior to any
horizontal run. Derating orice
must be used.
Horizontal Run requires a 1/4 in. (6mm) rise for every 1
ft toward the termination.
Horizontal Run requires a non-combustible support
every 3 ft (914 mm), i.e., plumbing tape
A vent run o the top of the appliance with more than
one 90º elbow or two 45º elbows must have a minimum
vertical of 2 feet.
All rear vent applications will require the use of a derating
orice, included in the RV Kit
Heat & Glo • TIARAI-IPI Installation Manual • 2342-980_R29 • 06/2214
Figure 4.8
One Elbow
Top Vent - Horizontal Termination
V1H1 Maximum
1 ft. 305 mm 14 in. 356 mm
2 ft. 610 mm 9 ft. 2.7 m
4 ft. 1.2 m 10 ft., 3 in. 3.1 m
6 ft. 1.8 m 11 ft., 6 in. 3.5 m
8 ft. 2.4m 12 ft., 9 in. 3.9 m
10 ft. 3.0 m 14 ft. 4.3 m
12 ft. 3.7 m 13 ft., 2 in. 4.0 m
16 ft. 4.9 m 11 ft., 3 in. 3.4 m
20 ft. 6.1 m 9 ft., 4 in. 2.7 m
24 ft. 7.3 m 7 ft., 6 in. 2.3 m
28 ft. 8.5 m 5 ft., 7 in. 1.7 m
30 ft. 9.1 m 4 ft., 7 in. 1.4 m
H1
V1
12-3/4” 3/8”
Corner Installation - Measurement

Heat & Glo • TIARAI-IPI Installation Manual • 2342-980_R29 • 06/2215
Two Elbows
INSTALLED
HORIZONTALLY
H1
H2
V1
2 Elbows to Max. Horizontal
V1 Minimum H1 + H2 Maximum
2 ft. 610 mm 6 ft. 1.8 m
4 ft. 1.2 m 7 ft., 3 in. 2.2 m
6 ft. 1.8 m 8 ft., 6 in. 2.6 m
8 ft. 2.4 m 9 ft., 9 in. 3.0 m
10 ft. 3.1 m 11 ft. 3.4 m
12 ft. 3.7 m 10 ft., 2 in. 3.1 m
16 ft. 4.9 m 8 ft., 3 in. 2.5 m
20 ft. 6.1 m 6 ft., 4 in. 1.9 m
24 ft. 7.3 m 4 ft., 6 in. 1.4 m
28 ft. 8.5 m 2 ft., 7 in. 787 mm
30 ft. 9.1 m 1 ft. 9 in. 533 mm
Figure 4.9
Heat & Glo • TIARAI-IPI Installation Manual • 2342-980_R29 • 06/2216
H2
H1
V2
V1
Figure 4.10
Top Vent - Horizontal Termination - (continued)
Three Elbows
3 Elbows to Max. Horizontal
V1 Minimum H1 + H2 Maximum
2 ft. 610 mm 3 ft. 914 mm
4 ft. 1.2 m 4 ft., 3 in. 1.3 m
6 ft. 1.8 m 5 ft., 6 in. 1.7 m
8 ft. 2.4 m 6 ft., 9 in. 2.1 m
10 ft. 3.1 m 8 ft. 2.4 m
12 ft. 3.7 m 7 ft., 2 in. 2.2 m
16 ft. 4.9 m 5 ft., 3 in. 1.6 m
20 ft. 6.1 m 3 ft., 4 in. 1.0 m
24 ft. 7.3 m 1 ft., 6 in. 457 mm
28 ft. 8.5 m 11 in. 279 mm
30 ft. 9.1 m 11 in. 279 mm
Heat & Glo • TIARAI-IPI Installation Manual • 2342-980_R29 • 06/2217
Top Vent - Vertical Termination
No Elbow
Figure 4.11
V1
V1 = 30 ft. Max. (9.1 m)
V1 = 6 ft. Min. (1.8 m)
Heat & Glo • TIARAI-IPI Installation Manual • 2342-980_R29 • 06/2218
Figure 4.12
Two Elbows
H1
V1
V2
2 Elbows to Max. Horizontal
V1 Minimum V1 + V2 Maximum H1 Maximum
2 ft. 610 mm 27 ft. 4 in. 8.3 m 6 ft. 1.8 m
4 ft. 1.2 m 24 ft., 8 in. 7.5 m 7 ft., 3 in. 2.2 m
6 ft. 1.8 m 22 ft. 6.7 m 8 ft., 6 in. 2.6 m
8 ft. 2.4 m 19 ft., 4 in. 5.9 m 9 ft., 9 in. 3.0 m
10 ft. 3.1 m 16 ft., 8 in. 5.1 m 11 ft. 3.4 m
12 ft. 3.7 m 18 ft., 8 in. 5.7 m 10 ft., 2 in. 3.1 m
16 ft. 4.9 m 22 ft., 8 in. 6.9 m 8 ft., 3 in. 2.5 m
20 ft. 6.1 m 26 ft.,8 in. 8.1 m 6 ft., 4 in. 1.9 m
24 ft. 7.3 m 30 ft. 9.1 m 4 ft., 6 in. 1.4 m
28 ft. 8.5 m 34 ft. 9.1 m 2 ft., 7 in. 787 mm
Heat & Glo • TIARAI-IPI Installation Manual • 2342-980_R29 • 06/2219
Figure 4.13
Top Vent - Vertical Termination - (continued)
Three Elbows
INSTALLED
HORIZONTALLY
H1
H2V1
V2
3 Elbows to Max. Horizontal
V1 Minimum V1 + V2 Maximum H1 + H2 Maximum
2 ft. 610 mm 30 ft. 9.1 m 6 ft. 1.8 m
4 ft. 1.2 m 30 ft. 9.1 m 7 ft., 3 in. 2.2 m
6 ft. 1.8 m 28 ft., 2 in. 8.6 m 8ft., 6 in. 2.6 m
8 ft. 2.4 m 25 ft., 6 in. 7.8 m 9 ft., 9 in. 3.0 m
10 ft. 3.1 m 21 ft. 6.4 m 11 ft. 3.4 m
12 ft. 3.7 m 24 ft., 8 in. 7.5 m 11.2 m 2.2 m
16 ft. 4.9 m 29 ft. 8.8 m 5 ft., 3 in. 1.6 m
20 ft. 6.1 m 30 ft. 9.1 m 3 ft., 4 in. 1.0 m
24 ft. 7.3 m 30 ft. 9.1 m 1 ft., 6 in. 457 mm
Heat & Glo • TIARAI-IPI Installation Manual • 2342-980_R29 • 06/2220
Rear Vent - Horizontal Termination
Figure 4.14
Figure 4.15
No Elbow
H1 = 14 in. (356 mm) Maximum
H1 = 14 in. (356 mm) Maximum
Note: A derating orice is required with this
application and is included in the Rear Vent Kit.
Note: All horizontal vent pipe runs must have
1/4 inch rise per foot.
NOTICE: An SLK-SNKD is required for this
vent conguration.
H1
H1
One 45º Elbow
Note: A derating orice is required with this
application and is included in the Rear Vent Kit.
Note: All horizontal vent pipe runs must have
1/4 inch rise per foot.
NOTICE: An SLK-SNKD is required for this
vent conguration.
Rear Vent - Horizontal Termination
/