FläktGroup EQES Air heater steam Installation and Maintenance Manual

Type
Installation and Maintenance Manual

FläktGroup EQES Air heater steam lets you control temperature and pressure with the use of reducing valves and regulation functions. The device should be positioned horizontally and connected with piping and trapping installed in a way that does not cause extra weight or pressure on the coil. Accessories like flanges, strainers, and vacuum beakers can be added to facilitate installation and maintenance. FläktGroup EQES is equipped with a condensate trap and a non-return valve to prevent overflows and water hammer.

FläktGroup EQES Air heater steam lets you control temperature and pressure with the use of reducing valves and regulation functions. The device should be positioned horizontally and connected with piping and trapping installed in a way that does not cause extra weight or pressure on the coil. Accessories like flanges, strainers, and vacuum beakers can be added to facilitate installation and maintenance. FläktGroup EQES is equipped with a condensate trap and a non-return valve to prevent overflows and water hammer.

FläktGroup DC_8678GB 20180228_R0 Specifications are subject to alteration without notice
TEMPERATURE
The temperature of the steam should not exceed the maximum operating
temperature prescribed for the air heater.
PRESSURE
If the steam pressure is in excess of maximum operating pressure
prescribed for the air heater a reducing valve should be mounted.
REGULATION
In the case of air heaters connected in series (as viewed in the air flow
direction) and where the temperature of the entering air may be sub
zero, the first air heater should operate at full steam while the second air
heater is regulated (see Fig. 4, page 3). Regulation of the first air heater
will only increase the risk of the coils freezing up and should be avoided.
POSITIONING
The air heater is designed for horizontal air flow.
CONNECTIONS
The piping and trapping etc. should be installed in such a way that
its weight will not bear upon the coil, nor press against it through
mechanical expansion.
ACCESSORIES
To facilitate the installation or replacement of traps, valves etc., the air
heater connections may be fitted with flanges.
EQES AIR HEATER, STEAM
AIR HEATER, STEAM
INSTALLATION AND MAINTENANCE INSTRUCTIONS
2
Installation and maintenance instructions
FläktGroup DC_8678GB 20180228_R0 Specifications are subject to alteration without notice
AIR HEATER, STEAM
SYMBOLS
Steam main
Return main
Flexible fitting
Fixing point
Gate valve
Shut-off valve
Control valve
Strainer
Vacuum breaker
Dirt pocket and valve
Petcock
Condensate trap
Non-return valve
Condensate pump
Steam
Condensate
Air
Direction of flow
Direction of air flow
Pitch (arrow indicates direction of flow)
To overhead return main
3154 EUES SYMBOL ÅNGLEDNING
3154 EUES SYMBOL KONDENSATLEDNING
3154 EUES SYMBOL KOMPENSATOR
3154 EUES SYMBOL FIXPUNKT
3154 EUES SYMBOL STOR AVSTÄNGNINGSVENTIL
3154 EUES SYMBOL REGLERVENTIL
3154 EUES SYMBOL SIL
3154 EUES SYMBOL VAKUUMVENTIL
3154 EUES SYMBOL AVÖUFTARE
C
3154 EUES SYMBOL KONDENSAT
S
3154 EUES SYMBOL ÅNGA
3154 EUES SYMBOL BACKVENTIL
3154 EUES SYMBOL KONDENSATAVLEDARE
3154 EUES SYMBOL FLÖDESRIKTNING
3154 EUES SYMBOL LUFTRIKTNING
1:100
3154 EUES SYMBOL LEDNINGSLUTNING
3154 EUES SYMBOL TILL ÖVERLIGGANDE KONDENSATLEDNING
3154 EUES SYMBOL KONDENSATPUMP
3154 EUES SYMBOL SMUTSFICKA MED AVTAPPNINGSVENTIL
3154 EUES SYMBOL AVSTÄNGNINGSVENTIL
3
Installation and maintenance instructions
FläktGroup DC_8678GB 20180228_R0 Specifications are subject to alteration without notice
AIR HEATER, STEAM
3154 EUES schema
öppet system
S
S
C
C
A
A
Min.500
1 : 100
Fig. 2. Open System
3154 EUES schema
slutet system
S
S
C
C
A
A
Min.500
1 : 100
Fig. 3. Closed System
CONNECTING-UP
To ensure that the system functions properly, the air heater and trapping,
etc. should be installed as shown in Figs. 2–4.
The steam main should always be connected at the top of the air heater
whereas the return main should be at the bottom. See symbols page 2.
3154 EUES schema
två seriekopplade
C
A
AA
Min.500
S
1 : 100
Fig. 4. Two air heaters connected in series on the
air side, b = 2.
4
Installation and maintenance instructions
FläktGroup DC_8678GB 20180228_R0 Specifications are subject to alteration without notice
AIR HEATER, STEAM
3154 EUES Tryckförhållanden
S
P1
P2
C
hm
Fig. 5. Pressure conditions with overhead return line.
hm < p1 – p2 kp/cm2
10,3
CONTROL AND PIPING
The piping should be pitched to ensure that the condensate build-up is
drained off, and not admitted into the coil.
The return main should be pitched downward from the air heater.
All the accessories which are part of the system must be designed
for steam or for condensate respectively. They should be sized for the
pressure, temperature and flow for the installation concerned, and be
connected according to the recommendations of the manufacturer.
STEAM AND RETURN MAINS
As a rule, steam mains should be sized for high vel oci ties. The steam
should be dry and preferably super heat ed. Humid steam leads to corro-
sion in the piping and may damage the air heaters and accessories
through water hammer.
The steam main should be drained of condensate upsteam of the air
heater and accessories by means of a shunt valve. The take-off should
be mounted as near to the air heater as possible and be designed to
separate the steam from the condensate in the pipe.
If the return main is pitched higher than the condensate trap, the coil will
operate at a static overpressure resulting from the w.g. height ”h” (see
Fig. 5) and the pres sure drop (i.e. resistance) in the condensate trap and/
or other accessories. Consequently this form of over head return main
should be avoided.
The steam and condensate pipes should be sized accord ing to the
recommended load and not according to the connection size of the air
heater.
MEASUREMENT OUTLET
If possible, the system should be fitted with an outlet to permit
measurement of the pressure, flow and temperature, both ahead of and
after the air heater.
FLEXIBLE FITTINGS
Flexible fittings should be provided in all piping connections so as to
absorb expansion and contraction strains. Rigid piping connections can
cause serious physical damage to the air heater coil.
FIXING POINTS
All fixing points should be as close to the air heater as possible, so
as to protect it from the weight of the pip ing, valves etc., and from the
expansion strain.
GATE VALVES
Gate valves should be mounted ahead of, and after, other accessories.
This will facilitate cleaning of the strainer and replacement of trapping,
valves, etc.
CONTROL VALVES
The control valve should be sized according to the manu facturer’s
recommendations and not according to the size of the air heater
connections.
An electric regulating motor should not be mounted under the valve, as
water leakage from the valve will cause damage.
The control valve should be mounted as close to the air heater as
possible and should be installed according to the manufacturer’s
instructions.
See symbols page 2.
5
Installation and maintenance instructions
FläktGroup DC_8678GB 20180228_R0 Specifications are subject to alteration without notice
AIR HEATER, STEAM
STRAINER
A strainer should be installed ahead of the control valve and condensate
trap, to collect foreign matter such as scales and rust flakes. If they are
not removed, these impurities will prevent the various accessories from
work ing properly and may even cause a stoppage in the throttling discs
of the air heater – thus reducing the heating efficiency and at the same
time increasing the risk of freezing-up.
VACUUM BREAKER
If the supply of steam to the air heater is reduced or shut off, there will be
a vacuum in the air heater, with the result that it will wholly or partly fill
with conden sate. If the temperature of the outside air is so low that the
coil may freeze up, the water must be emptied and the air heater filled
with air instead. This is the function of the vacuum breaker. In air heaters
where there is no danger of freezing up, a vacuum breaker need not be
used; the risk of corrosion will be reduced accordingly.
DIRT TRAP AND DRAIN COCK
It is recommended that a dirt trap be installed before the condensate
trap. Thus it will not be necessary to clean the strainer so often.
PETCOCK
Air which has entered the system through the vacuum breaker, and
likewise non-condensible gases from the steam, must be eliminated.
This is done by means of the petcock, which should be installed ahead of
the condensate trap.
STEAM COIL
Check that there is steam pressure up to the heating coil (the boiler must
have correct steam pressure and all the valves must be open) and that
the condensation discharge pipe and provision for venting work properly
throughout the system. A fault in the steam trap may adversely affect all
the discharge pipes.
CONDENSATE TRAP
Each air heater (or tube row) should be provided with a condensate trap.
A single condensate trap should not be connected to more than one air
heater, regardless of its operation.
The condensate trap also prevents a return flow of steam to the coil via
the return line.
The condensate trap should be sized according to the amount of
condensation when the air heater is cold. Its capacity in litres/h should
be three to five times the calculated steam flow in kg/h.
The trap may be of such a type that a separate strainer and venting valve
will not be required.
Important!
The strainers should be controlled at short
intervalls right after start-up.
To ensure that the condensate is emptied completely, the trap should be
installed at least 500 mm below the pipe connection of the air heater.
In the case of a thermostatic condensate trap, a cool ing length of piping
is required between the air heater and the trap.
If the air heaters are connected in series (see Fig. 4, page 3) the maximal
heat is produced by the first air heater. Its condensate trap must
therefore be selected with this in mind.
NON-RETURN VALVE
To prevent water hammer from other units connected to the system, the
installation should be fitted with a non-return valve or a condensate trap.
When two air heaters are installed, each of them must be provided with a
non-return valve, to prevent an overflow of steam.
CONDENSATE PUMP
If an overhead return main is installed, the pump should be located before
the rise; this reduces the risk of cavitation in the pump, and ensures that
the condensate is emptied completely.
6
Installation and maintenance instructions
FläktGroup DC_8678GB 20180228_R0 Specifications are subject to alteration without notice
AIR HEATER, STEAM
Fig. 6. By-pass
FREEZE GUARD THERMOSTAT
Steam air heaters supplied with outside air should be protected by
means of a freeze guard thermostat, to be selected and mounted
according to the instruction. However, its sensing element should be
mounted so that it does not come in contact with un heated air.
With capillary tube thermostats, the element should be located at the
bottom of the air heater coil, on the condensate side, and not over the
entire face area. If the thermostat is of the bulb type, it should likewise be
mounted in the lower part of the coil, and parallel with the finned tubes.
If the thermostat is not temperature-compensated, its cubicle should
be mounted in a location where the temperature is higher than that
required to trip the circuit breaker. If the cubicle of a thermostat which
is not compensated, is mounted on the casing of an air heater, or a duct
upsteam of the air heater, it should be insulated by means of a wood-
fibre board or the like.
BY-PASS
Replacement of the regulating valve or condensate trap will be facilitated
if a by-pass is installed as shown in Fig. 6.
See symbols page 2.
STARTING-UP
Open the steam valve until the entire air heater is warm, then start the fan
motor.
If the temperature if the outside air is below 0°C, there is risk of the air
heater coil freezing, see “vacum breaker”.
Important!
When installing air heaters which use steam
as a heating medium, great care should be
exercized when opening air vents and gate
valves. Failure to do this may result in serious
damage through water hammer or a discharge
of steam.
FläktGroup assumes no responsibility for the
connection of air heaters to the heating system,
or for any damage which may arise through
faulty planning, installation or maintenance of
such system. Piping, valves, etc. should be
sized according to pressure drop and function
and not according to the size of the air heater
coil connections. The pipes should be installed
in such a way that the air heater does not bear
their weight or is not subjected to expansion
and contraction strain from the heating system.
The guarantee does not cover air heaters which
have been damaged through water hammer or
freezing.
7
Installation and maintenance instructions
FläktGroup DC_8678GB 20180228_R0 Specifications are subject to alteration without notice
AIR HEATER, STEAM
TO CLEAN
Even a very efficient air filter cannot remove all dust from the air. Dust
deposited on the heat transfer surfaces restricts the air flow and impairs
the heat transfer.
The finned unit must therefore be kept clean, for which one of the
methods described below or a suitable combination of these methods
can be employed.
A. Blow clean with compressed air.
B. Blow clean with steam.
CHECK
Check that there is steam pressure all the way to the heating coils (the
boiler must have the correct steam pressure and all the valves must be
open) and that the condensate trap and venting valves are in working
order throughout the system. One faulty condensate trap can give rise to
repercussions on all the traps.
After cleaning but before starting the fan, remove all dust that has fallen
down.
Caution!
The heating elements are still hot after you have
switched off the unit. You risk getting burned
if you touch them. Switch off the unit well in
advance before cleaning.
A
B
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7

FläktGroup EQES Air heater steam Installation and Maintenance Manual

Type
Installation and Maintenance Manual

FläktGroup EQES Air heater steam lets you control temperature and pressure with the use of reducing valves and regulation functions. The device should be positioned horizontally and connected with piping and trapping installed in a way that does not cause extra weight or pressure on the coil. Accessories like flanges, strainers, and vacuum beakers can be added to facilitate installation and maintenance. FläktGroup EQES is equipped with a condensate trap and a non-return valve to prevent overflows and water hammer.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI