5
Installation and maintenance instructions
FläktGroup DC_8678GB 20180228_R0 Specifications are subject to alteration without notice
AIR HEATER, STEAM
STRAINER
A strainer should be installed ahead of the control valve and condensate
trap, to collect foreign matter such as scales and rust flakes. If they are
not removed, these impurities will prevent the various accessories from
work ing properly and may even cause a stoppage in the throttling discs
of the air heater – thus reducing the heating efficiency and at the same
time increasing the risk of freezing-up.
VACUUM BREAKER
If the supply of steam to the air heater is reduced or shut off, there will be
a vacuum in the air heater, with the result that it will wholly or partly fill
with conden sate. If the temperature of the outside air is so low that the
coil may freeze up, the water must be emptied and the air heater filled
with air instead. This is the function of the vacuum breaker. In air heaters
where there is no danger of freezing up, a vacuum breaker need not be
used; the risk of corrosion will be reduced accordingly.
DIRT TRAP AND DRAIN COCK
It is recommended that a dirt trap be installed before the condensate
trap. Thus it will not be necessary to clean the strainer so often.
PETCOCK
Air which has entered the system through the vacuum breaker, and
likewise non-condensible gases from the steam, must be eliminated.
This is done by means of the petcock, which should be installed ahead of
the condensate trap.
STEAM COIL
Check that there is steam pressure up to the heating coil (the boiler must
have correct steam pressure and all the valves must be open) and that
the condensation discharge pipe and provision for venting work properly
throughout the system. A fault in the steam trap may adversely affect all
the discharge pipes.
CONDENSATE TRAP
Each air heater (or tube row) should be provided with a condensate trap.
A single condensate trap should not be connected to more than one air
heater, regardless of its operation.
The condensate trap also prevents a return flow of steam to the coil via
the return line.
The condensate trap should be sized according to the amount of
condensation when the air heater is cold. Its capacity in litres/h should
be three to five times the calculated steam flow in kg/h.
The trap may be of such a type that a separate strainer and venting valve
will not be required.
Important!
The strainers should be controlled at short
intervalls right after start-up.
To ensure that the condensate is emptied completely, the trap should be
installed at least 500 mm below the pipe connection of the air heater.
In the case of a thermostatic condensate trap, a cool ing length of piping
is required between the air heater and the trap.
If the air heaters are connected in series (see Fig. 4, page 3) the maximal
heat is produced by the first air heater. Its condensate trap must
therefore be selected with this in mind.
NON-RETURN VALVE
To prevent water hammer from other units connected to the system, the
installation should be fitted with a non-return valve or a condensate trap.
When two air heaters are installed, each of them must be provided with a
non-return valve, to prevent an overflow of steam.
CONDENSATE PUMP
If an overhead return main is installed, the pump should be located before
the rise; this reduces the risk of cavitation in the pump, and ensures that
the condensate is emptied completely.