LQES Air heater, steam - Installation instruction
3
FläktGroup DC_9148GB 20180412_R0
Specifications are subject to alteration without notice
Control and piping (Contd.)
The steam and condensate pipes should be sized accord ing to the
recommended load and not according to the connection size of the air
heater.
STRAINER
A strainer should be installed ahead of the control valve and conden-
sate trap, to collect foreign matter such as scales and rust flakes. If
they are not removed, these impurities will prevent the various acces-
sories from work ing properly and may even cause a stoppage in the
throttling discs of the air heater – thus reducing the heating efficiency
and at the same time increasing the risk of freezing-up.
3154 EUES Tryckförhållanden
S
P1
2
hm
Fig. 5. Pressure conditions with overhead return line.
MEASUREMENT OUTLET
If possible, the system should be fitted with an outlet to permit meas-
urement of the pressure, flow and temperature, both ahead of and af-
ter the air heater.
FLEXIBLE FITTINGS
Flexible fittings should be provided in all piping connections so as to
absorb expansion and contraction strains. Rigid piping connections
can cause serious physical damage to the air heater coil.
FIXING POINTS
All fixing points should be as close to the air heater as possible, so
as to protect it from the weight of the pip ing, valves etc., and from the
expansion strain.
GATE VALVES
Gate valves should be mounted ahead of, and after, other accessories.
This will facilitate cleaning of the strainer and replacement of trapping,
valves, etc.
CONTROL VALVES
The control valve should be sized according to the manu facturer’s
recommendations and not according to the size of the air heater con-
nections.
An electric regulating motor should not be mounted under the valve,
as water leakage from the valve will cause damage. The control valve
should be mounted as close to the air heater as possible and should
be installed according to the manufacturer’s instructions.
hm < p1 – p2 kp/cm2
10,3
VACUUM BREAKER
If the supply of steam to the air heater is reduced or shut off, there
will be a vacuum in the air heater, with the result that it will wholly or
partly fill with conden sate. If the temperature of the outside air is so
low that the coil may freeze up, the water must be emptied and the
air heater filled with air instead. This is the function of the vacuum
breaker. In air heaters where there is no danger of freezing up, a vac-
uum breaker need not be used; the risk of corrosion will be reduced
accordingly.
DIRT TRAP AND DRAIN COCK
It is recommended that a dirt trap be installed before the condensate
trap. Thus it will not be necessary to clean the strainer so often.
PETCOCK
Air which has entered the system through the vacuum
breaker, and likewise non-condensible gases from the steam, must be
eliminated. This is done by means of the petcock, which should be in-
stalled ahead of the condensate trap.
CONDENSATE TRAP
Each air heater (or tube row) should be provided with a condensate
trap. A single condensate trap should not be connected to more than
one air heater, regardless of its operation. The condensate trap also
prevents a return flow of steam to the coil via the return line.
The condensate trap should be sized according to the amount of con-
densation when the air heater is cold. Its capacity in litres/h should be
three to five times the calculated steam flow in kg/h.
The trap may be of such a type that a separate strainer and venting
valve will not be required.
To ensure that the condensate is emptied completely, the trap should
be installed at least 500 mm below the pipe connection of the air
heater.
In the case of a thermostatic condensate trap, a cool ing length of pip-
ing is required between the air heater and the trap. If the air heaters
are connected in series (see Fig. 4) the maximal heat is produced by
the first air heater. Its condensate trap must therefore be selected with
this in mind.
IMPORTANT!
When starting up, check the strainers at regular
intervals.