Allen-Bradley ArmorStratix 5700 Ethernet Managed Switches offer robust networking solutions for industrial applications. These switches provide secure and reliable connectivity for critical devices, enabling efficient data transfer and control within industrial automation systems. With advanced features like Layer 3 routing, PoE+, and comprehensive security mechanisms, the ArmorStratix 5700 switches are ideal for building resilient and scalable industrial networks.

Allen-Bradley ArmorStratix 5700 Ethernet Managed Switches offer robust networking solutions for industrial applications. These switches provide secure and reliable connectivity for critical devices, enabling efficient data transfer and control within industrial automation systems. With advanced features like Layer 3 routing, PoE+, and comprehensive security mechanisms, the ArmorStratix 5700 switches are ideal for building resilient and scalable industrial networks.

ATTENTION: Read this document and the documents listed in the Additional Resources section about installation, configuration and operation of this equipment before you install, configure, operate or maintain this product. Users are
required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
⌘᜿˖൘ᆹ㻵ǃ䝽㖞ǃ᫽֌઼㔤ᣔᵜӗ૱ࡽˈ䈧䰵䈫ᵜ᮷ẓԕ৺ Ā ަԆ䍴Ⓚ ā 䜘࠶ࡇࠪⲴᴹޣ䇮༷ᆹ㻵ǃ䝽㖞઼᫽֌Ⲵ⴨ᓄ᮷ẓDŽ䲔Ҷᡰᴹ䘲⭘㿴㤳ǃ⌅ᖻ઼ḷ߶
Ⲵ⴨ޣ㾱≲ѻཆˈ⭘ᡧ䘈ᗵ享⟏ᚹᆹ㻵઼᧕㓯䈤᰾DŽ
ᆹ㻵ǃ䈳ᮤǃᣅ䘀ǃ֯⭘ǃ㓴㻵ǃ᣶ন઼㔤ᣔㅹ਴亩᫽֌ᗵ享⭡㓿䗷䘲ᖃ䇝㓳ⲴуъӪઈ᤹➗䘲⭘Ⲵ᫽֌㿴㤳ᇎᯭDŽ
ྲ᷌ᵚ᤹➗ࡦ䙐୶ᤷᇊⲴᯩᔿ֯⭘䈕䇮༷ˈࡉਟ㜭Պᦏᇣ䇮༷ᨀ׋Ⲵ؍ᣔDŽ
ATENCIÓN: Antes de instalar, configurar, poner en funcionamiento o realizar el mantenimiento de este producto, lea este documento y los documentos listados en la sección Recursos adicionales acerca de la instalación, configuración y
operación de este equipo. Los usuarios deben familiarizarse con las instrucciones de instalación y cableado y con los requisitos de todos los códigos, leyes y estándares vigentes.
El personal debidamente capacitado debe realizar las actividades relacionadas a la instalación, ajustes, puesta en servicio, uso, ensamblaje, desensamblaje y mantenimiento de conformidad con el código de práctica aplicable.
Si este equipo se usa de una manera no especificada por el fabricante, la protección provista por el equipo puede resultar afectada.
ATENÇÃO: Leia este e os demais documentos sobre instalação, configuração e operação do equipamento que estão na seção Recursos adicionais antes de instalar, configurar, operar ou manter este produto. Os usuários devem se familiarizar
com as instruções de instalação e fiação além das especificações para todos os códigos, leis e normas aplicáveis.
É necessário que as atividades, incluindo instalação, ajustes, colocação em serviço, utilização, montagem, desmontagem e manutenção sejam realizadas por pessoal qualificado e especializado, de acordo com o código de prática aplicável.
Caso este equipamento seja utilizado de maneira não estabelecida pelo fabricante, a proteção fornecida pelo equipamento pode ficar prejudicada.
ВНИМАНИЕ: Перед тем как устанавливать, настраивать, эксплуатировать или обслуживать данное оборудование, прочитайте этот документ и документы, перечисленные в разделе «Дополнительные ресурсы». В этих
документах изложены сведения об установке, настройке и эксплуатации данного оборудования. Пользователи обязаны ознакомиться с инструкциями по установке и прокладке соединений, а также с требованиями всех
применимых норм, законов и стандартов.
Все действия, включая установку, наладку, ввод в эксплуатацию, использование, сборку, разборку и техническое обслуживание, должны выполняться обученным персоналом в соответствии с применимыми нормами и
правилами.
Если оборудование используется не предусмотренным производителем образом, защита оборудования может быть нарушена.
ὀព ᮏ〇ရࢆタ⨨ࠊᵓᡂࠊ✌ືࡲࡓࡣಖᏲࡍࡿ๓࡟ࠊᮏ᭩࠾ࡼࡧᮏᶵჾࡢタ⨨ࠊタᐃࠊ᧯స࡟ࡘ࠸࡚ࡢཧ⪃㈨ᩱࡢヱᙜ⟠ᡤ࡟グ㍕ࡉࢀ࡚࠸ࡿᩥ᭩࡟┠ࢆ㏻ࡋ࡚
ࡃࡔࡉ࠸ࠋ࣮ࣘࢨࡣࠊࡍ࡭࡚ࡢヱᙜࡍࡿ᮲౛ࠊἲᚊࠊつ᱁ࡢせ௳࡟ຍ࠼࡚ࠊタ⨨࠾ࡼࡧ㓄⥺ࡢᡭ㡰࡟⩦⇍ࡋ࡚࠸ࡿᚲせࡀ࠶ࡾࡲࡍࠋ
タ⨨ㄪᩚࠊ㐠㌿ࡢ㛤ጞࠊ౑⏝ࠊ⤌❧࡚ࠊゎయࠊಖᏲࢆྵࡴㅖసᴗࡣࠊヱᙜࡍࡿᐇ᪋つ๎࡟ᚑࡗ࡚カ⦎ࢆཷࡅࡓ㐺ษ࡞సᴗဨࡀᐇ⾜ࡍࡿᚲせࡀ࠶ࡾࡲࡍࠋ
ᮏᶵჾࡀ〇㐀࣓࣮࢝࡟ࡼࡾᣦᐃࡉࢀ࡚࠸࡞࠸᪉ἲ࡛౑⏝ࡉࢀ࡚࠸ࡿሙྜࠊᶵჾ࡟ࡼࡾᥦ౪ࡉࢀ࡚࠸ࡿಖㆤࡀᦆ࡞ࢃࢀࡿᜍࢀࡀ࠶ࡾࡲࡍࠋ
ACHTUNG: Lesen Sie dieses Dokument und die im Abschnitt „Literaturverweise“ genannten Dokumente zur Installation, Konfiguration und Bedienung dieser Ausrüstung sorgfältig durch, bevor Sie dieses Produkt installieren, konfigurieren,
bedienen oder instandsetzen. Benutzer müssen sich mit den Anweisungen zur Installation und Verdrahtung vertraut machen und müssen die Anforderungen aller geltenden Vorschriften, Gesetze und Normen kennen.
Aktivitäten wie Installation, Einstellung, Inbetriebnahme, Verwendung, Montage, Demontage und Instandsetzung müssen durch ausreichend geschultes Personal in Übereinstimmung mit den geltenden Durchführungsvorschriften
ausgeführt werden.
Wenn diese Ausrüstung in einer Weise verwendet wird, die nicht vom Hersteller angegeben wurde, kann der von der Ausrüstung bereitgestellte Schutz beeinträchtigt sein..
ATTENTION : Lisez ce document et les documents listés dans la section Ressources complémentaires relatifs à l’installation, la configuration et le fonctionnement de cet équipement avant d’installer, configurer, utiliser ou entretenir ce
produit. Les utilisateurs doivent se familiariser avec les instructions d’installation et de câblage en plus des exigences relatives aux codes, lois et normes en vigueur.
Les activités relatives à l’installation, le réglage, la mise en service, l’utilisation, l’assemblage, le démontage et l’entretien doivent être réalisées par des personnes formées selon le code de pratique en vigueur.
Si cet équipement est utilisé d’une façon qui n’a pas été définie par le fabricant, la protection fournie par l’équipement peut être compromise.
늱넍 뇑븽 ꫙렍 ꫙뇊 녆鶎 鿅鱉 냕덵 ꚩꯍ뼍韥 놹꾅 ꓭ꫑ꌱ 붡뼝뼍꾡 ꫙렍 ꫙뇊 녆鶎꾅 隵뼑 뗭隕 녅ꊁ ꫮꬍ넍 ꓭ꫑麙냹 ꗍ麑겑 넲隕 ꯎ덵뼍겢겑꿙 ꩡ끞녅鱉
ꑝ麕隵ꇝ鞑뇊 Ꙋ鞑ꗄ븑늵꾅꫑끉霡뼍鱉ꩡ뼢꾅鲵뼩ꗍ麑겑꫙렍ꗄꗥ꫕덵렝냹ꯎ덵뼩꼱뼞鱽鲙
꫙렍 눥뇊 閵鶎 ꩡ끞 눥ꍲ ꜹ뼩 냕덵ꚩꯍ麦ꑝ麕녆꽺냵隵ꇝ鞑뇊꾅黥ꄱ놶놽뼑霅냖냹ꗐ냵ꩡ끞녅ꌱ뭪뼩꫑ꎁꯍ뼾뼩꼱뼞鱽鲙 .
ꚭ녚ꟹꌱ뇑눥ꩡ閵ꐺ겑뼍덵껿냵ꗞꙊ냱ꈑꩡ끞뼍ꐩ녚ꟹ넍ꚩ뿭韥鱚넩ꭅꩶ鷕ꯍ넽걪鱽鲙 .
ATTENZIONE Prima di installare, configurare ed utilizzare il prodotto, o effettuare interventi di manutenzione su di esso, leggere il presente documento ed i documenti elencati nella sezione “Altre risorse”, riguardanti l’installazione, la
configurazione ed il funzionamento dell’apparecchiatura. Gli utenti devono leggere e comprendere le istruzioni di installazione e cablaggio, oltre ai requisiti previsti dalle leggi, codici e standard applicabili.
Le attività come installazione, regolazioni, utilizzo, assemblaggio, disassemblaggio e manutenzione devono essere svolte da personale adeguatamente addestrato, nel rispetto delle procedure previste.
Qualora l’apparecchio venga utilizzato con modalità diverse da quanto previsto dal produttore, la sua funzione di protezione potrebbe venire compromessa.
DİKKAT: Bu ürünün kurulumu, yapılandırılması, işletilmesi veya bakımı öncesinde bu dokümanı ve bu ekipmanın kurulumu, yapılandırılması ve işletimi ile ilgili İlave Kaynaklar bölümünde yer listelenmiş dokümanları okuyun. Kullanıcılar
yürürlükteki tüm yönetmelikler, yasalar ve standartların gereksinimlerine ek olarak kurulum ve kablolama talimatlarını da öğrenmek zorundadır.
Kurulum, ayarlama, hizmete alma, kullanma, parçaları birleştirme, parçaları sökme ve bakım gibi aktiviteler sadece uygun eğitimleri almış kişiler tarafından yürürlükteki uygulama yönetmeliklerine uygun şekilde yapılabilir.
Bu ekipman üretici tarafından belirlenmiş amacın dışında kullanılırsa, ekipman tarafından sağlanan koruma bozulabilir.
⌘᜿һ丵˖൘ᆹ㼍ǃ䁝ᇊǃ᫽֌ᡆ㏝䆧ᵜ⭒૱ࡽˈ䃻ݸ䯡䆰↔᮷Ԧԕ৺ࡇᯬ NjަԆ䋷Ⓚnjㄐㇰѝᴹ䰌ᆹ㼍ǃ䁝ᇊ㠷᫽֌↔䁝ۉⲴ᮷ԦDŽ֯⭘㘵ᗵ丸⟏ᚹᆹ㼍઼䝽㐊ᤷ
⽪ˈіㅖਸᡰᴹ⌅㾿ǃ⌅ᖻ઼⁉Ⓠ㾱≲DŽ
वᤜᆹ㼍ǃ䃯ᮤǃӔԈ֯⭘ǃ֯⭘ǃ㍴㼍ǃ᣶ন઼㏝䆧ㅹअ֌䜭ᗵ丸Ӕ⭡ᐢ㏃䙾䚙⮦䁃㐤ⲴӪ଑䙢㹼ˈԕㅖਸ䚙⭘Ⲵሖ֌⌅㾿DŽ
ྲ᷌ሷ䁝ۉ⭘ᯬ䶎㼭䙐୶ᤷᇊⲴ⭘䙄ᱲˈਟ㜭ᴳ䙐ᡀ䁝ۉᡰᨀ׋Ⲵ؍䆧࣏㜭ਇᨽDŽ
POZOR: Než začnete instalovat, konfigurovat či provozovat tento výrobek nebo provádět jeho údržbu, přečtěte si tento dokument a dokumenty uvedené v části Dodatečné zdroje ohledně instalace, konfigurace a provozu tohoto zařízení.
Uživatelé se musejí vedle požadavků všech relevantních vyhlášek, zákonů a norem nutně seznámit také s pokyny pro instalaci a el
ektrické zapojení.
Činnosti zahrnující instalaci, nastavení, uvedení do provozu, užívání, montáž, demontáž a údržbu musí vykonávat vhodně proškolený personál v souladu s příslušnými prováděcími předpisy.
Pokud se toto zařízení používá způsobem neodpovídajícím specifikaci výrobce, může být narušena ochrana, kterou toto zařízení poskytuje.
UWAGA: Przed instalacją, konfiguracją, użytkowaniem lub konserwacją tego produktu należy przeczytać niniejszy dokument oraz wszystkie dokumenty wymienione w sekcji Dodatkowe źródła omawiające instalację, konfigurację i
procedury użytkowania tego urządzenia. Użytkownicy mają obowiązek zapoznać się z instrukcjami dotyczącymi instalacji oraz oprzewodowania, jak również z obowiązującymi kodeksami, prawem i normami.
Działania obejmujące instalację, regulację, przekazanie do użytkowania, użytkowanie, montaż, demontaż oraz konserwację muszą być wykonywane przez odpowiednio przeszkolony personel zgodnie z obowiązującym kodeksem
postępowania.
Jeśli urządzenie jest użytkowane w sposób inny niż określony przez producenta, zabezpieczenie zapewniane przez urządzenie może zostać ograniczone.
OBS! Läs detta dokument samt dokumentet, som står listat i avsnittet Övriga resurser, om installation, konfigurering och drift av denna utrustning innan du installerar, konfigurerar eller börjar använda eller utföra underhållsarbete på
produkten. Användare måste bekanta sig med instruktioner för installation och kabeldragning, förutom krav enligt gällande koder, lagar och standarder.
Åtgärder som installation, justering, service, användning, montering, demontering och underhållsarbete måste utföras av personal med lämplig utbildning enligt lämpligt bruk.
Om denna utrustning används på ett sätt som inte anges av tillverkaren kan det hända att utrustningens skyddsanordningar försätts ur funktion.
LET OP: Lees dit document en de documenten die genoemd worden in de paragraaf Aanvullende informatie over de installatie, configuratie en bediening van deze apparatuur voordat u dit product installeert, configureert, bediend of
onderhoudt. Gebruikers moeten zich vertrouwd maken met de installatie en de bedradingsinstructies, naast de vereisten van alle toepasselijke regels, wetten en normen.
Activiteiten zoals het installeren, afstellen, in gebruik stellen, gebruiken, monteren, demonteren en het uitvoeren van onderhoud mogen uitsluitend worden uitgevoerd door hiervoor opgeleid personeel en in overeenstemming met de
geldende praktijkregels.
Indien de apparatuur wordt gebruikt op een wijze die niet is gespecificeerd door de fabrikant, dan bestaat het gevaar dat de beveiliging van de apparatuur niet goed werkt.
Product Information
ArmorStratix™ 5700 Ethernet Managed Switches
2 ArmorStratix™ 5700 Ethernet Managed Switches
Rockwell Automation Publication 1783-PC012C-EN-P - April 2015
Environment and Enclosure
Before You Begin
Observe these guidelines before installing ArmorStratix™ 5700 switches:
For 10/100 ports and 10/100/1000 ports, the cable length from a switch to an attached device
cannot exceed 100 m (328 ft).
Clearance to front and rear panels meets these conditions:
Front-panel status indicators can be easily read.
Access to ports is sufficient for unrestricted cabling.
Front-panel direct current (DC) power connectors and the alarm relay connector are within reach of the
connection to the DC power source.
To prevent the switch from overheating, observe the following minimum clearances:
Top and bottom: 50.8 mm (2.0 in.)
Sides: 50.8 mm (2.0 in.)
Front: 50.8 mm (2.0 in.)
Temperature surrounding the unit does not exceed 60 °C (140 °F).
ATTENTION:
Installation, adjustments, putting into service, use, assembly, disassembly, and maintenance shall be
carried out by suitably trained personnel in accordance with applicable code of practice. In case of
malfunction or damage, no attempts at repair should be made. The module should be returned to the
manufacturer for repair. Do not dismantle the module.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the
equipment may be impaired.
This equipment is certified for use only within the surrounding air temperature range of -40…60 °C
(-40…140 °F). The equipment must not be used outside of this range.
Solid-state equipment has operational characteristics differing from those of electromechanical
equipment. Safety Guidelines for the Application, Installation, and Maintenance of Solid-state Controls,
publication SGI-1.1, available from your local Rockwell Automation sales office or online at
http://www.rockwellautomation.com/literature, describes some important differences between
solid-state equipment and hard-wired electromechanical devices.
IMPORTANT
Any illustrations, charts, sample programs, and layout examples shown in this publication are intended
solely for the purposes of example. Since there are many variables and requirements associated with any
particular installation, Rockwell Automation does not assume responsibility or liability for actual use
based upon the examples shown in this publication.
WARNING: This is a Class A Information Product, when used in residential environment, it may cause radio
frequency interference, under such circumstances, the user may be requested to take appropriate
countermeasures.
ATTENTION: This equipment is intended for use in a Pollution Degree 2 industrial environment, in
overvoltage Category II applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without
derating.
This equipment is not intended for use in residential environments and may not provide adequate
protection to radio communication services in such environments.
This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is
suitably designed for those specific environmental conditions that will be present and appropriately
designed to prevent personal injury resulting from accessibility to live parts. The enclosure must have
suitable flame-retardant properties to prevent or minimize the spread of flame, complying with a flame
spread rating of 5VA or be approved for the application if non-metallic. The interior of the enclosure must be
accessible only by the use of a tool. Subsequent sections of this publication may contain additional
information regarding specific enclosure type ratings that are required to comply with certain product safety
certifications.
In addition to this publication, see the following:
Industrial Automation Wiring and Grounding Guidelines, publication
1770-4.1, for additional installation
requirements
NEMA 250 and IEC 60529, as applicable, for explanations of the degrees of protection provided by
different types of enclosure
ATTENTION: To meet IP67 compliance, all cables, dust caps, or the SD card cover’s captive screws must
be torqued to the recommended specification before operating the unit.
ArmorStratix™ 5700 Ethernet Managed Switches 3
Rockwell Automation Publication 1783-PC012C-EN-P - April 2015
Mount the Switch on the Wall
1. Position the rear panel of the switch against the wall or a panel in the desired location.
2. Place a number-10 screw that you provide through each mounting ear, and screw them into the wall.
Ground the Switch
Use at least a 4 mm
2
conductor to connect to the external grounding screws.
The ground lug is not supplied with the switch.
You can use one of these options:
• Single-ring terminal
Two single-ring terminals
1. Use a Phillips screwdriver or a ratcheting torque screwdriver with a Phillips head to remove the ground screw from the
switch.
Store the ground screw for later use.
2. Determine the wire length to be stripped by using the manufacturer guidelines.
3. Insert the ground wire into the ring terminal lug, and using a crimping tool, crimp the terminal to the wire.
If two ring terminals are being used, repeat this action for a second ring terminal.
4. Slide the ground screw through the terminal.
5. Insert the ground screw into the ground screw opening.
6. Use a ratcheting-torque screwdriver to tighten the ground screws and ring terminal to the switch front panel to
0.4 N•m (3.5 lb•in).
Do not exceed the recommended torque.
7. Attach the other end of the ground wire to a grounded, bare metal surface, such as a ground bus, a grounded DIN rail, or
a grounded bare rack.
Connect the Earth Ground Wire
1. Measure a single length of stranded copper wire long enough to connect the power converter to the earth ground.
2. For connections from the power converter to earth ground, use shielded 18-AWG stranded copper wire.
3. Connect one end of the stranded copper wire to a grounded bare metal surface, such as a ground bus, a grounded DIN
rail, or a grounded bare rack.
4. Insert the other end of the exposed ground wire lead into the earth-ground wire connection on the power converter
terminal block. Only wire with insulation should extend from the connection.
5. Tighten the earth-ground wire connection terminal block screw.
Torque to 0.9 N•m (8 lb•in). Do not exceed 1.13 N•m (10 lb•in).
Connect the DC Power to the Switch
You must supply a power solution for the device. An IP67-rated cordset or patchcord with a female-end, 4-pin mini
connector is required to provide power to the switch. Rockwell Automation offers a Bulletin 1607 IP67-rated power supply
to provide 24V DC power to the switch. Ethernet communication and control power cables are available separately.
Power over Ethernet
For switches with Power over Ethernet (PoE) capability, PoE power is drawn from the single power connection. There is no
separate power input for PoE.
Cordsets
Patchcords
Connect the DC power to the switch through the front panel connector.
WARNING:
To prevent bodily injury when mounting or servicing this unit in a rack, you must take
special precautions to ensure that the system remains stable. The following guidelines are provided to
ensure your safety:
Mount the unit at the bottom of the rack if it is the only unit in the rack.
When mounting the unit in a partially filled rack, load the rack from the bottom to the top with the
heaviest component at the bottom of the rack.
If the rack is provided with stabilizing devices, install the stabilizers before mounting or servicing the unit in
the rack.
ATTENTION: For proper grounding, you must always connect the power supply functional-ground screw
when connecting the power supply. You must provide an acceptable grounding path for each device in your
application. For more information on proper grounding guidelines, refer to publication 1770-4.1, Industrial
Automation Wiring and Grounding Guidelines.
WARNING: This equipment is intended to be grounded to comply with emission and immunity
requirements. Ensure that the switch functional ground lug is connected to earth ground during normal
use.
32477
Switch Configuration Required Power Input
Power Supplied per Port
PoE 44-57V 15.4 W, max
PoE+ 50-57V 30 W, max
Non-PoE 9.6…60V Not applicable
No. of Pins Assembly Rating Straight Male Right Angle Male
4 600V, 10 A
889N-F4AFC-
(1)
6F series B
(1) Replace (1) with 6 (6 ft), 12 (12 ft), or 20 (20 ft) for standard cable lengths.
889N-E4AFC
(1)
F
No. of
Pins
Assembly
Rating
Straight Female,
Straight Male
Straight Female,
Right Angle Male
Right Angle
Female, Straight
Male
Right Angle
Female,
Right Angle
Male
4 600V, 10 A
889N-F4AFNM-
(1)
(1) Replace (1) with 1 (1 m), 2 (2 m), 5 (5 m), and 10 (10 m) for standard cable lengths.
889N-F4AFNE-
(1)
889N-R4AFNM-
(1)
889N-R4AFNE-
(1)
32475
32476
32478
Publication 1783-PC012C-EN-P - April 2015 PN-311057
Copyright © 2015 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.
Allen-Bradley, ArmorStratix, Rockwell Automation, and Stratix are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400
Rockwell Automation maintains current product environmental information on its website at http://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.page.
Switch Specifications
Additional Resources
These documents contain additional information concerning related products from Rockwell Automation.
You can view or download publications at
http://www.rockwellautomation.com/literature/. To order paper copies of technical documentation, contact your local Allen-Bradley distributor or Rockwell Automation sales representative.
Attribute 1783-ZMS8TA 1783-ZMS16TA 1783-ZMS24TA 1783-ZMS4T4E2TGP,
1783-ZMS4T4E2TGN
1783-ZMS8T8E2TGP,
1783-ZMS8T8E2TGN
Power and alarm relay
Switch power input ratings 12…48V DC, 1.5 A 12…48V DC, 1.8 A 12…48V DC, 2.0 A PoE/PoE +: 48…54V DC, 2.9 A
Non-PoE: 9.6…60V DC, 2.9 A
PoE/PoE+: 48…54V DC, 3.3 A
Non-PoE: 9.6…60V DC, 3.3 A
Alarm relay ratings Not applicable 30V DC, 1.0 A or 48V DC, 0.5 A
Wire size and temp
Power connector for IP67 cable 600V 16 AWG, 105 °C (221 °F)
Alarm connector for IP67 cable 300V, 22 AWG,105 °C (221 °F)
Screw torque
Ground ports 0.4 N•m (3.5 lb•in)
Power ports 0.23 N•m (2.0 lb•in)
Alarm, console, Ethernet ports
(M12 connectors)
0.5…0.8 N•m (4.43…7.08 lb•in)
For mating cables or dust caps
Power supply connector
(mini-change)
1.13 N•m (10 lb•in)
SD card access door captive screws 1.8…2.2 N•m (15.93…19.47 lb•in)
Environmental ranges
Storage temperature -40…85 °C (-40…185°F)
Storage altitude Up to 4570 m (15,000 ft)
Operating temperature -40…60 °C (-40…140 °F)
Operating humidity 5…95% noncondensing
Operating altitude Up to 4570 m (15,000 ft)
IP/type rating IP67 rated for protection against dust and submersion in water
NEMA Type 4
ATTENTION: The switch is IP67- and NEMA Type 4-compliant only when all IP67 cables are mated and torqued appropriately or with the supplied dust caps attached.
Physical attributes
Dimensions (H x W x D), approx 243.8 x 237.49 x 86.3 mm
9.6 x 9.35 x 3.4 in.
243.8 x 300.99 x 68.07 mm
9.6 x 11.85 x 2.68 in.
243.8 x 374.65 x 68.07 mm
9.6 x 14.75 x 2.68 in.
243.8 x 237.49 x 86.3 mm
9.6 x 9.35 x 3.4 in.
243.8 x 300.99 x 68.07 mm
9.6 x 11.85 x 2.68 in.
Weight 3.26 kg (7.19 lb) 3.30 kg (7.28 lb) 4.02 kg (8.86 lb) 3.26 kg (7.19 lb) 3.30 kg (7.28 lb)
Resource Description
Stratix™ 5700 Ethernet Managed Switches Technical Data, publication
1783-TD001 Provides specification information for the switches.
Stratix™ Managed Switches User Manual, publication
1783-UM007 Provides detailed information on about installing and using switch hardware and software.
Ethernet Network Media page,
http://ab.rockwellautomation.com/Connection-Devices/EtherNet-Media Provides information about industrial Ethernet media.
Industrial Automation Wiring and Grounding Guidelines, publication
1770-4.1 Provides general guidelines for installing a Rockwell Automation® industrial system.
Product Certifications website,
http://www.rockwellautomation.com/products/certification Provides declarations of conformity, certificates, and other certification details.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

Allen-Bradley armorstratix 5700 Product information

Type
Product information

Allen-Bradley ArmorStratix 5700 Ethernet Managed Switches offer robust networking solutions for industrial applications. These switches provide secure and reliable connectivity for critical devices, enabling efficient data transfer and control within industrial automation systems. With advanced features like Layer 3 routing, PoE+, and comprehensive security mechanisms, the ArmorStratix 5700 switches are ideal for building resilient and scalable industrial networks.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI