Johnson Controls Mercury P2000 CKM-MR16IN Hardware Installation

Type
Hardware Installation
24-10707-74 Revision D
December 2017
P2000
Security Management System
CKM-MR16IN
authentic Mercury™ terminal module
hardware
installation
Copyright 2017
Johnson Controls
All Rights Reserved
No part of this document may be reproduced without the prior permission of Johnson Controls.
If this document is translated from the original English version by Johnson Controls, all reasonable
endeavors will be used to ensure the accuracy of translation. Johnson Controls shall not be liable
for any translation errors contained herein or for incidental or consequential damages in connection
with the furnishing or use of this translated material.
Due to continuous development of our products, the information in this document is subject to
change without notice. Johnson Controls shall not be liable for errors contained herein or for
incidental or consequential damages in connection with furnishing or use of this material. Contents
of this publication may be preliminary and/or may be changed at any time without any obligation to
notify anyone of such revision or change, and shall not be regarded as a warranty.
Other Manufacturers’ Documentation
Johnson Controls does not duplicate documentation of other equipment manufacturers. When
necessary, Johnson Controls provides documentation that supplements that of other manufacturers.
When unpacking your equipment, keep all original manufacturer documentation for reference.
Technical Support
For factory technical support, Johnson Controls authorized field technicians or authorized dealer
representatives can contact Global Security Solutions Technical Support by phone at
(866) 893-0423 or (414) 524-1214, or by email at [email protected]
. They
can also call the Field Support Center at (800) 524-1330 or (414) 524-5000 and use options 6, 1, 7.
End users and customers should contact their local Johnson Controls branch or authorized dealer
for any of their support needs (technical support, maintenance contracts, on-site field support,
P2000 Software Service Agreements, Service Partnerships, and so on). Visit
http://www.johnsoncontrols.com/location-finder
to find your local Johnson Controls office.
For material returns contact the branch if the material was purchased through a Johnson Controls
branch or through the Product Sales Operations Team, if ordered through the Advanced Order
Management System (AOMS) and follow the RMA process; or contact the authorized dealer
representative where the material was purchased directly.
Single Point of Contact by Region
Acknowledgments
Metasys® and Johnson Controls® are trademarks of Johnson Controls. All other company and
product names are trademarks or registered trademarks of their respective owners.
European Single Point of Contact
JOHNSON CONTROLS
WESTENDHOF 3
45143 ESSEN
GERMANY
NA/SA Single Point of Contact
JOHNSON CONTROLS
507 E MICHIGAN ST
MILWAUKEE WI 53202
USA
APAC Single Point of Contact
JOHNSON CONTROLS
C/O CONTROLS PRODUCT
MANAGEMENT
NO. 22 BLOCK D NEW DISTRICT
WUXI JIANGSU PROVINCE 214142
CHINA
Declarations of Conformity
United States: This equipment has been tested and found to comply with the limits for a Class A
digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference when the equipment is operated in a commercial
environment. This equipment generates, uses, and can radiate radio frequency energy and, if not
installed and used in accordance with the instruction manual, may cause harmful interference to
radio communications. Operation of this equipment in a residential area is likely to cause harmful
interference in which case the user will be required to correct the interference at his own expense.
Canada: CAN ICES-3 (A)/NMB-3(A)
European Union: This product complies with the requirements of the EMC Directive.
This equipment must not be modified for any reason and it must be installed as stated in the
Manufacturer’s instruction. If this shipment (or any part thereof) is supplied as second-hand
equipment, equipment for sale outside the European Economic Area or as spare parts for either a
single unit or system, it is not covered by the Directives.
UNDERWRITERS LABORATORIES COMPLIANCE VERIFICATION SHEET
The following model number is listed under Underwriters Laboratories® (UL) 1076 for Proprietary
Burglar Alarm Units and Systems, UL 294 for Access Control Systems Units and Underwriters
Laboratories of Canada ULC/ORD-C1076-86.
CKM-MR16IN
When installed at the site the following requirements must be met to comply with these standards.
1. The CKM-MR16IN shall be mounted in Listed Enclosures CKM-CE75-E2M, CKM-CE150-
E4M, and Listed Burglar Alarm and Access Control System Units SPF10000-1I00, SPF1I100-
1I00 or SPF1I300-1J00.
2. A CKM-MR16IN mounted in Listed Enclosures CKM-CE75-E2M, CKM-CE150-E4M, and
Listed Burglar Alarm and Access Control System Units SPF10000-1I00, SPF1I100-1I00 or
SPF1I300-1J00 shall be powered through the CKM-F8P power distribution module.
3. Transient protection devices that are installed must not be removed or defeated.
4. Do not connect equipment to an AC power source that is controlled by a switch.
5. Power for devices connected through relay/control output wiring must be provided by a UL
Listed power limited power source.
6. A 1.5Kohm/750ohm custom end-of-line resistance supervised circuit was investigated by
Underwriter Laboratories.
7. Encrypted communication has not investigated by Underwriters Laboratories.
8. Suitable for use with the model P2K-nnn-UL-x Security Management System, where n can be
any number 0 through 9 and where x can be any three letters A through Z.
9. UL 294 Performance Levels
Destructive Attack Level I
Endurance Level IV
Line Security Level I
Standby Power Level I
CKM-MR16IN Hardware Installation Manual
24-10707-74 Rev. D
1
CKM-MR16IN INPUT TERMINAL MODULE
This document provides hardware installation and setup instructions for
CKM-MR16IN, the authentic Mercury™ terminal module. This document is
divided into the following sections:
General Information on page 1
Mounting Information on page 2
Wiring Information on page 2
Setup Information on page 6
Status LEDs on page 8
Specifications on page 10
Maintenance on page 11
G
ENERAL INFORMATION
The CKM-MR16IN terminal module provides a solution to the OEM system
integrator for sensor monitoring and output control. The CKM-MR16IN has 16
supervised inputs and 2 form-C contact relays for load switching. In addition, 2
digital inputs are used for cabinet tamper and power fault status monitoring.
The CKM-MR16IN requires 12 to 24 VDC for power.
CKM-MR16IN Hardware Installation Manual
24-10707-74 Rev. D
2
MOUNTING INFORMATION
Figure 1: CKM-MR16IN Hardware
WIRING INFORMATION
This sections covers the following:
Cable Routing
Supplying Power
Communications Wiring
CKM-MR16IN Communications Wiring.
Relay Outputs Wiring
2.00 [50.80] 3.00 [76.20] 2.00 [50.80]
8.00 [203.20]
0.25 [6.35] 5.50 [139.70]
6.00 [152.40]
OUTPUTS
TB11
VIN
GND
TR-
R+
R-
GND
TR+
TB10
4W
2W
RS-485
TB1
TB2
TB3
TB4
TB9
I1
I1
I2
I2
I3
I3
I4
I4
I5
I5
I6
I6
I7
I7
I8
I8
CT
GND
BA
GND
2W
4W
J3
J6
J5
12345678
S1
N
C
C
N
O
N
C
C
N
O
O
U
T
1
O
U
T
2
TB12
K1K2
J8
TB5
I9
I9
I10
I10
TB6
I11
I11
I12
I12
TB7
I13
I13
I14
I14
TB8
I15
I15
I16
I16
A
B
K
1
K
2
J9
J7
J4
MR-16IN
J1
J2
RS-485
TERM
U1
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
CT
BA
INPUT STATUS LEDs
INPUTS
DIP SWITCHES
STATUS LEDs
Ø0.16 [Ø3.96]
8 PLACES
INPUTS
SIO COMMUNICATION
PORT, RS-485
POWER IN
12-24Vdc
CKM-MR16IN Hardware Installation Manual
24-10707-74 Rev. D
3
Cable Routing
The cables should run in grounded conduit or at least two feet from AC
power, fluorescent lights, or other high energy sources.
IMPORTANT: All data cables should be physically separated from power lines. If
conduit is used, do not run data cables in the same conduit as power cables or
certain door strike cables, e.g. strike voltage greater that 42V or Magnetic door
locks without EMI suppression.
All cables must conform with the following regulations:
National Electrical Code
•NFPA 70
Local electrical codes
Canadian Electric Code C22.1 (installations in Canada)
BSI Standard BS7671, latest edition (installations in Great Britain)
Cabling should be made using good wiring practices and should be long
enough to allow service loops at their terminations in the enclosure.
Supplying Power
The CKM-MR16IN accepts 12 to 24 VDC for power. Locate power
source as close to the unit as possible. Connect power with minimum of
18 AWG wires.
IMPORTANT: Observe polarity on VIN.
Figure 2: CKM-MR16IN Supplying Power
12 TO 24Vdc
GND
VIN
+
-
TB11
CKM-MR16IN Hardware Installation Manual
24-10707-74 Rev. D
4
Communications Wiring
The CKM-MR16IN communicates to an intelligent controller (EP2500
for example) via a two-wire RS-485 interface. The interface allows
multidrop communication on a single bus of up to 4,000 feet (1,200 m).
Shielded cable of 24 AWG with characteristic impedance of 120 ohm is
specified for the RS-485 interface. The last devices on each end of the
cable should have the terminator installed (set jumper J1 on).
Install the following jumpers for the RS-485 interface according to the
selected configuration.
Figure 3: CKM-MR16IN Communications Wiring.
Alarm Inputs Wiring
Inputs 1 to 16 may be configured to use or not use End Of Line (EOL)
resistors and to use normally open or normally closed contacts. Input CT
and input BA are used for monitoring cabinet tamper and power failure,
respectively. These two inputs are for contact closure monitoring only,
and do not use EOL resistors. Input configuration is set via host software.
CKM-MR16IN Hardware Installation Manual
24-10707-74 Rev. D
5
Figure 4: Alarm Contact Wiring
Relay Outputs Wiring
Two form-C contact relays are provided for controlling door strikes or
other devices. Load switching can cause abnormal contact wear and
premature contact failure. Switching of inductive loads (strike) also
causes EMI (electromagnetic interference) which may interfere with
normal operation of other equipment. To minimize premature contact
failure and to increase system reliability, contact protection circuit must
be used. The following two circuits are recommended. Locate the
protection circuit as close to the load as possible, but within 12 inches
(30 cm), as the effectiveness of the circuit decreases if it is located further
away.
Figure 5: CKM-MR16IN Relay Outputs Wiring
NC
NO
NO
NC
1K,1%
1K,1%
1K,1%
1K,1%
TB6 TB5
I9
I9
I10
I10
I11
I11
I12
I12
CKM-MR16IN Hardware Installation Manual
24-10707-74 Rev. D
6
SETUP INFORMATION
Use the Jumpers for RS-485 termination and two-wire/four-wire select.
Use the Jumpers to select the device address, communication baud rate, and to
enable or disable encrypted communication. All other configuration settings
are set via host software.
Table 1: Jumpers
Jumper Description
J1 RS-485 termination, install in first and last units only
J2 Factory Use Only
J3 Two-wire/four-wire select, install in 2W position only
J4 - J9 Factory Use Only
Table 2: Switches
S8 S7 S6 S5 S4 S3 S2 S1 Selection
OFF OFF OFF OFF OFF Address 0
OFF OFF OFF OFF ON Address 1
OFF OFF OFF ON OFF Address 2
OFF OFF OFF ON ON Address 3
OFF OFF ON OFF OFF Address 4
OFF OFF ON OFF ON Address 5
OFF OFF ON ON OFF Address 6
OFF OFF ON ON ON Address 7
OFF ON OFF OFF OFF Address 8
OFF ON OFF OFF ON Address 9
OFF ON OFF ON OFF Address 10
OFF ON OFF ON ON Address 11
OFF ON ON OFF OFF Address 12
OFF ON ON OFF ON Address 13
OFF ON ON ON OFF Address 14
OFF ON ON ON ON Address 15
ON OFF OFF OFF OFF Address 16
CKM-MR16IN Hardware Installation Manual
24-10707-74 Rev. D
7
ON OFF OFF OFF ON Address 17
ON OFF OFF ON OFF Address 18
ON OFF OFF ON ON Address 19
ON OFF ON OFF OFF Address 20
ON OFF ON OFF ON Address 21
ON OFF ON ON OFF Address 22
ON OFF ON ON ON Address 23
ON ON OFF OFF OFF Address 24
ON ON OFF OFF ON Address 25
ON ON OFF ON OFF Address 26
ON ON OFF ON ON Address 27
ON ON ON OFF OFF Address 28
ON ON ON OFF ON Address 29
ON ON ON ON OFF Address 30
ON ON ON ON ON Address 31
OFF OFF 115,200 BPS
1
OFF ON 9,600 BPS
ON OFF 19200 BPS
ON ON 38,400 BPS
OFF
Encrypted communication not
required
2
ON Encrypted communication
required
2
1. Firmware revisions prior to 1.38.1, this setting is 2,400 BPS.
2. Firmware revisions prior to 1.38.1, SW8 is not defined. Set to the OFF position.
Table 2: Switches
S8 S7 S6 S5 S4 S3 S2 S1 Selection
CKM-MR16IN Hardware Installation Manual
24-10707-74 Rev. D
8
STATUS LEDS
Table 3: LED Information
Process LED Information
Power-up All LEDs OFF
Initialization Once you apply power, initialization of the module begins.
When initialization is completed, LEDs 1 through 16, CT, BA, A, and B are
briefly sequenced ON then OFF.
Running A LED Heartbeat and On-Line Status:
Offline
1-second rate, 20% ON
Online
Non-encrypted communication: 1-second rate, 80% ON
Encrypted communication:
0.1 second ON
0.1 second OFF
0.1 second ON
0.1 second OFF
0.1 second ON
0.1 second OFF
0.1 second ON
0.3 second OFF
Running
(continued)
A LED Error Indication:
Waiting for application firmware to be downloaded:
1 second ON
1 second OFF
Running
(continued)
B LED SIO Communication Port Status:
Indicates communication activity on the SIO communication port.
CKM-MR16IN Hardware Installation Manual
24-10707-74 Rev. D
9
Running
(continued)
1 LED: Input Status: 1
2 LED: Input Status: 2
3 LED: Input Status: 3
4 LED: Input Status: 4
5 LED: Input Status: 5
6 LED: Input Status: 6
7 LED: Input Status: 7
8 LED: Input Status: 8 CKM-MR
9 LED: Input Status: 9
10 LED: Input Status: 10
11 LED: Input Status: 11
12 LED: Input Status: 12
13 LED: Input Status: 13
14 LED: Input Status: 14
15 LED: Input Status: 15
16 LED: Input Status: 16
CT: Cabinet Tamper
BA: Power Fault
Input in the inactive state: OFF (briefly flashes ON every 3 seconds)
Input in the active state: ON (briefly flashes OFF every 3 seconds)
Input in a trouble state: Rapid Flash
Running
(continued)
K1 through K2 LEDs: Illuminates when output relay RLY 1 (K1) or RLY 2
(K2) is energized.
Table 3: LED Information
Process LED Information
CKM-MR16IN Hardware Installation Manual
24-10707-74 Rev. D
10
SPECIFICATIONS
Use this interface in low voltage, Class 2 circuits only.
Table 4: CKM-MR16IN Specifications
Category Description
Primary Power 12 to 24 VDC ±10%, 350 mA maximum (plus reader current)
12 VDC at 300 mA (plus reader current) nominal
24 VDC at 220 mA (plus reader current) nominal
Outputs 2 outputs, Form-C, 5A at 28 VDC, resistive
Inputs 16 unsupervised/supervised, standard EOL: 1k/1k ohm, 1%, 1/4 watt
2 unsupervised, dedicated for cabinet tamper and UPS fault
monitoring
Communication RS-485, two-wire. 9600, 19200, 38400, or 115200 bps
Cable Requirements
Power 1 twisted pair, 18 AWG.
RS-485 24 AWG, 120 ohm impedance, twisted pair with shield, 4,000 ft
(1,219 m) maximum
Alarm Inputs 1 twisted pair, 30 ohms maximum
Outputs As required for the load.
Environmental
Temperature 32 to 120°F (0 to 49 °C) operating
-67 to 185°F (-55 to 85°C) storage
Humidity 10 to 93% RHNC
Mechanical
Dimensions
(W x L x H)
6 in x 8 in x 1in (152mm x 203 mm x 25 mm)
Weight 9 oz. (250 g) nominal
CKM-MR16IN Hardware Installation Manual
24-10707-74 Rev. D
11
MAINTENANCE
Impaired Performance
The following is a list of the impaired performance conditions:
Unit environment not as specified
Unit power not as specified
Cable type and length not as specified
Test Procedure
To check for proper operation of the device:
1. Verify LED status indicates device is online.
2. Change the state of any input and verify change of state.
3. Change the state of any output and verify change of state.
CKM-MR16IN Hardware Installation Manual
24-10707-74 Rev. D
12
We welcome your comments at [email protected].
Security Solutions
(805) 522-5555
www.johnsoncontrols.com
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17