Johnson Controls CKM-MR16OUT Hardware Installation

Type
Hardware Installation

This manual is also suitable for

Johnson Controls CKM-MR16OUT is a terminal module designed to provide output control for OEM system integrators. It features 16 form-C contact relays for load switching, allowing you to control various devices or systems. The module also includes 2 digital inputs for tamper and power fault status monitoring, enhancing the security of your installation. CKM-MR16OUT supports RS-485 communication, enabling seamless integration with other devices and systems. Its compact design and versatile mounting options make it suitable for various applications and environments.

Johnson Controls CKM-MR16OUT is a terminal module designed to provide output control for OEM system integrators. It features 16 form-C contact relays for load switching, allowing you to control various devices or systems. The module also includes 2 digital inputs for tamper and power fault status monitoring, enhancing the security of your installation. CKM-MR16OUT supports RS-485 communication, enabling seamless integration with other devices and systems. Its compact design and versatile mounting options make it suitable for various applications and environments.

24-10707-82 Revision D
December 2017
P2000
Security Management System
CKM-MR16OUT
authentic Mercury™ terminal module
hardware
installation
Copyright 2017
Johnson Controls
All Rights Reserved
No part of this document may be reproduced without the prior permission of Johnson Controls.
If this document is translated from the original English version by Johnson Controls, all reasonable
endeavors will be used to ensure the accuracy of translation. Johnson Controls shall not be liable
for any translation errors contained herein or for incidental or consequential damages in connection
with the furnishing or use of this translated material.
Due to continuous development of our products, the information in this document is subject to
change without notice. Johnson Controls shall not be liable for errors contained herein or for
incidental or consequential damages in connection with furnishing or use of this material. Contents
of this publication may be preliminary and/or may be changed at any time without any obligation to
notify anyone of such revision or change, and shall not be regarded as a warranty.
Other Manufacturers’ Documentation
Johnson Controls does not duplicate documentation of other equipment manufacturers. When
necessary, Johnson Controls provides documentation that supplements that of other manufacturers.
When unpacking your equipment, keep all original manufacturer documentation for reference.
Technical Support
For factory technical support, Johnson Controls authorized field technicians or authorized dealer
representatives can contact Global Security Solutions Technical Support by phone at
(866) 893-0423 or (414) 524-1214, or by email at [email protected]
. They
can also call the Field Support Center at (800) 524-1330 or (414) 524-5000 and use options 6, 1, 7.
End users and customers should contact their local Johnson Controls branch or authorized dealer
for any of their support needs (technical support, maintenance contracts, on-site field support,
P2000 Software Service Agreements, Service Partnerships, and so on). Visit
http://www.johnsoncontrols.com/location-finder
to find your local Johnson Controls office.
For material returns contact the branch if the material was purchased through a Johnson Controls
branch or through the Product Sales Operations Team, if ordered through the Advanced Order
Management System (AOMS) and follow the RMA process; or contact the authorized dealer
representative where the material was purchased directly.
Single Point of Contact by Region
Acknowledgments
Metasys® and Johnson Controls® are trademarks of Johnson Controls. All other company and
product names are trademarks or registered trademarks of their respective owners.
European Single Point of Contact
JOHNSON CONTROLS
WESTENDHOF 3
45143 ESSEN
GERMANY
NA/SA Single Point of Contact
JOHNSON CONTROLS
507 E MICHIGAN ST
MILWAUKEE WI 53202
USA
APAC Single Point of Contact
JOHNSON CONTROLS
C/O CONTROLS PRODUCT
MANAGEMENT
NO. 22 BLOCK D NEW DISTRICT
WUXI JIANGSU PROVINCE 214142
CHINA
Declarations of Conformity
United States: This equipment has been tested and found to comply with the limits for a Class A
digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference when the equipment is operated in a commercial
environment. This equipment generates, uses, and can radiate radio frequency energy and, if not
installed and used in accordance with the instruction manual, may cause harmful interference to
radio communications. Operation of this equipment in a residential area is likely to cause harmful
interference in which case the user will be required to correct the interference at his own expense.
Canada: CAN ICES-3 (A)/NMB-3(A)
European Union: This product complies with the requirements of the EMC Directive.
This equipment must not be modified for any reason and it must be installed as stated in the
Manufacturer’s instruction. If this shipment (or any part thereof) is supplied as second-hand
equipment, equipment for sale outside the European Economic Area or as spare parts for either a
single unit or system, it is not covered by the Directives.
UNDERWRITERS LABORATORIES COMPLIANCE VERIFICATION SHEET
The following model number is listed under Underwriters Laboratories® (UL) 1076 for Proprietary
Burglar Alarm Units and Systems, UL 294 for Access Control Systems Units and Underwriters
Laboratories of Canada ULC/ORD-C1076-86.
CKM-MR16OUT
When installed at the site the following requirements must be met to comply with these standards.
1. The CKM-MR16OUT shall be mounted in Listed Enclosures CCKM-CE75-E2M, CKM-
CE150-E4M, and Listed Burglar Alarm and Access Control System Units SPF10000-1I00,
SPF1I100-1I00 or SPF1I300-1J00.
2. A CKM-MR16OUT mounted in Listed Enclosures CKM-CE75-E2M, CKM-CE150-E4M, and
Listed Burglar Alarm and Access Control System Units SPF10000-1I00, SPF1I100-1I00 or
SPF1I300-1J00 shall be powered through the CKM-F8P power distribution module.
3. Transient protection devices that are installed must not be removed or defeated.
4. Do not connect equipment to an AC power source that is controlled by a switch.
5. Power for devices connected through relay/control output wiring must be provided by a UL
Listed power limited power source.
6. Encrypted communication has not investigated by Underwriters Laboratories.
7. Suitable for use with the model P2K-nnn-UL-x Security Management System, where n can be
any number 0 through 9 and where x can be any three letters A through Z.
8. UL 294 Performance Levels
Destructive Attack Level I
Endurance Level IV
Line Security Level I
Standby Power Level I
CKM-MR16OUT Hardware Installation Manual
24-10707-82 Rev. D
1
CKM-MR16OUT TERMINAL MODULE
This document provides hardware installation and setup instructions for
CKM-MR16OUT, the authentic Mercury™ terminal module. This document is
divided into the following sections:
General Information on page 1
Mounting Information on page 2
Wiring Information on page 2
Setup Information on page 5
Status LEDs on page 7
Specifications on page 8
Maintenance on page 9
G
ENERAL INFORMATION
The CKM-MR16OUT output terminal module provides a solution to the OEM
system integrator for output control. The controller has 16 form-C contact
relays for load switching. Additionally, 2 digital inputs are provided for tamper
and power fault status monitoring. The CKM-MR16OUT requires 12 to 24
VDC for power.
CKM-MR16OUT Hardware Installation Manual
24-10707-82 Rev. D
2
MOUNTING INFORMATION
Figure 1: CKM-MR16OUT Hardware
WIRING INFORMATION
This sections covers the following:
Cable Routing
Supplying Power
Communications Wiring
Inputs for Cabinet Tamper/Power Fault
Relay Outputs Wiring
6.00 [152.40]
5.50 [139.70].25 [6.35]
2.00 [50.80]3.00 [76.20]2.00 [50.80]
8.00 [203.20]
S1
1
12 435 12976 8 13 1410 11 15 16
TB10
TR+
GND
R+
4W
R-
2W
TR-
RS-485
GND
VIN
GND
BA
CT
GND
TB9
TB11
J2 J1
J1, J2
RS-485
TERM
NC
C
NO
NC
C
NO
OUT 8
OUT 7
TB4 K8
NO
C
NC
NO
C
NC
OUT 6
OUT 5
NO
C
NC
NO
C
NC
OUT 4
OUT 3
NO
C
NC
NO
C
NC
OUT 2
OUT 1
TB3K7 TB2 TB1
2W
4W
J3
U1
J6
J5
J7
J8
J4
A
B
CT
BA
2
3
4
5
6
7
8
K2
K4
K3
K1
K9
K11
K12
K10
K5
K13
K14
K15
K16
TB5
TB6
TB7
TB8
NO
C
NC
NO
C
NC
OUT 9
OUT 10
C
NO
NC
C
NO
NC
OUT 11
OUT 12
NC
C
OUT 13
NO
NC
OUT 14
NO
C
OUT 16
NO
C
OUT 115
NC
C
NO
NC
K6
POWER IN
12-24Vdc
SIO COMMUNICATION
PORT, RS-485
TAMPER AND POWER
MONIOTR INPUTS
DIP SWITCHES
STATUS LEDs
Ø.156 [Ø4.0]
8 PLACES
OUTPUTS
OUTPUTS
RELAY STATUS LEDs
.50 [12.70]
CKM-MR16OUT Hardware Installation Manual
24-10707-82 Rev. D
3
Cable Routing
The cables should run in grounded conduit or at least two feet from AC
power, fluorescent lights, or other high energy sources.
IMPORTANT: All data cables should be physically separated from power lines. If
conduit is used, do not run data cables in the same conduit as power cables or
certain door strike cables, e.g. strike voltage greater that 42V or Magnetic door
locks without EMI suppression.
All cables must conform with the following regulations:
National Electrical Code
•NFPA 70
Local electrical codes
Canadian Electric Code C22.1 (installations in Canada)
BSI Standard BS7671, latest edition (installations in Great Britain)
Cabling should be made using good wiring practices and should be long
enough to allow service loops at their terminations in the enclosure.
Supplying Power
The CKM-MR16OUT requires 12 to 24 VDC for power on TB11. Locate
power source as close to the unit as possible. Connect power with
minimum of 18 AWG wires.
Figure 2: CKM-MR16OUT Supplying Power
IMPORTANT: Observe polarity on VIN.
12 TO 24Vdc
GND
VIN
+
-
TB11
CKM-MR16OUT Hardware Installation Manual
24-10707-82 Rev. D
4
Communications Wiring
The CKM-MR16OUT communicates to a controller via a two-wire RS-
485 interface. The interface allows multidrop communication on a single
bus of up to 4,000 feet (1,200 m). Use twisted pair (minimum 24 AWG)
with shield for the communication line.
Install the following jumpers for the RS-485 interface according to the
selected configuration.
Figure 3: CKM-MR16OUT Communications Wiring
Inputs for Cabinet Tamper/Power Fault
Input CT and input BA are used for monitoring cabinet tamper and power
failure with normally closed contacts. These two inputs are for contact
closure monitoring only, and do not use EOL resistors. If you are not
using these inputs, install a short piece of wire at the input to indicate a
safe condition.
Figure 4: CKM-MR16OUT Cabinet Tamper and Power Fault Wiring
CT
GND
BA
GND
CABINET
TAMPER
POWER
FAULT
TB9
CKM-MR16OUT Hardware Installation Manual
24-10707-82 Rev. D
5
Relay Outputs Wiring
The following diagrams show typical use of the relay. A DC power
source is recommended whenever possible. Transient clamping must be
provided to protect the contacts and to reduce EMI emission. Use
sufficiently large wires for the load current to avoid voltage loss.
Figure 5: CKM-MR16OUT Relay Outputs Wiring
SETUP INFORMATION
Table 1: Jumpers
Jumper Description
J1 RS-485 termination, install in first and last units only
J2 Factory Use Only
J3 Two-wire/four-wire select, install in 2W position only
J4 - J9 Factory Use Only
CKM-MR16OUT Hardware Installation Manual
24-10707-82 Rev. D
6
Table 2: Switches
S8 S7 S6 S5 S4 S3 S2 S1 Selection
OFF OFF OFF OFF OFF Address 0
OFF OFF OFF OFF ON Address 1
OFF OFF OFF ON OFF Address 2
OFF OFF OFF ON ON Address 3
OFF OFF ON OFF OFF Address 4
OFF OFF ON OFF ON Address 5
OFF OFF ON ON OFF Address 6
OFF OFF ON ON ON Address 7
OFF ON OFF OFF OFF Address 8
OFF ON OFF OFF ON Address 9
OFF ON OFF ON OFF Address 10
OFF ON OFF ON ON Address 11
OFF ON ON OFF OFF Address 12
OFF ON ON OFF ON Address 13
OFF ON ON ON OFF Address 14
OFF ON ON ON ON Address 15
ON OFF OFF OFF OFF Address 16
ON OFF OFF OFF ON Address 17
ON OFF OFF ON OFF Address 18
ON OFF OFF ON ON Address 19
ON OFF ON OFF OFF Address 20
ON OFF ON OFF ON Address 21
ON OFF ON ON OFF Address 22
ON OFF ON ON ON Address 23
ON ON OFF OFF OFF Address 24
ON ON OFF OFF ON Address 25
ON ON OFF ON OFF Address 26
ON ON OFF ON ON Address 27
ON ON ON OFF OFF Address 28
CKM-MR16OUT Hardware Installation Manual
24-10707-82 Rev. D
7
STATUS LEDS
ON ON ON OFF ON Address 29
ON ON ON ON OFF Address 30
ON ON ON ON ON Address 31
OFF OFF 115,200 BPS
1
OFF ON 9,600 BPS
ON OFF 19200 BPS
ON ON 38,400 BPS
OFF
Encrypted communication not
required
2
ON Encrypted communication
required
2
1. Firmware revisions prior to 1.38.1, this setting is 2,400 BPS.
2. Firmware revisions prior to 1.38.1, SW8 is not defined. Set to the OFF position.
Table 3: LED Information
Process LED Information
Power-up All LEDs OFF
Initialization Once you apply power, initialization of the module begins.
When initialization is completed, LEDs A, B, CT, and BA are briefly
sequenced ON then OFF.
Running A LED Heartbeat and On-Line Status:
Offline
1-second rate, 20% ON
Online
Non-encrypted communication: 1-second rate, 80% ON
Encrypted communication:
0.1 second ON
0.1 second OFF
0.1 second ON
0.1 second OFF
0.1 second ON
0.1 second OFF
0.1 second ON
0.3 second OFF
Table 2: Switches
S8 S7 S6 S5 S4 S3 S2 S1 Selection
CKM-MR16OUT Hardware Installation Manual
24-10707-82 Rev. D
8
SPECIFICATIONS
Use this interface in low voltage, Class 2 circuits only.
Running
(continued)
A LED Error Indication:
Waiting for application firmware to be downloaded:
1 second ON
1 second OFF
Running
(continued)
B LED SIO Communication Port Status:
Indicates communication activity on the SIO communication port.
Running
(continued)
CT: Cabinet Tamper
BA: Power Fault
Running
(continued)
LED 1 through 16: Illuminates when output relay OUT 1 (K1), OUT 2 (K2)
is energized, and so on.
Table 4: CKM-MR16OUT Specifications
Category Description
Primary Power 12 to 24 VDC ±10%, 1100 mA maximum (plus reader current)
12 VDC at 850 mA nominal
24 VDC at 450 mA nominal
Relay Contacts 16 Form-C, 5A at 30 VDC, resistive
Inputs 2 unsupervised, dedicated for cabinet tamper and UPS fault
monitoring
Communication RS-485, two-wire. 9600, 19200, 38400, or 115200 bps
Cable Requirements
Power 1 twisted pair, 18 AWG.
RS-485 24 AWG, 120 ohm impedance, twisted pair with shield, 4,000 ft
(1,219 m) maximum
Inputs 1 twisted pair, 30 ohms maximum
Outputs As required for the load.
Environmental
Temperature 32 to 120°F (0 to 49 °C) operating
-67 to 185°F (-55 to 85°C) storage
Humidity 10 to 93% RHNC
Table 3: LED Information
Process LED Information
CKM-MR16OUT Hardware Installation Manual
24-10707-82 Rev. D
9
MAINTENANCE
Impaired Performance
The following is a list of the impaired performance conditions:
Unit environment not as specified
Unit power not as specified
Cable type and length not as specified
Test Procedure
To check for proper operation of the device:
1. Verify LED status indicates device is online.
2. Change the state of any input and verify change of state.
3. Change the state of any output and verify change of state.
Mechanical
Dimensions
(W x L x H)
6 in x 8 in x 1in (152mm x 203 mm x 25 mm)
Weight 14 oz. (400 g) nominal
Table 4: CKM-MR16OUT Specifications
Category Description
CKM-MR16OUT Hardware Installation Manual
24-10707-82 Rev. D
10
We welcome your comments at [email protected].
Security Solutions
(805) 522-5555
www.johnsoncontrols.com
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15

Johnson Controls CKM-MR16OUT Hardware Installation

Type
Hardware Installation
This manual is also suitable for

Johnson Controls CKM-MR16OUT is a terminal module designed to provide output control for OEM system integrators. It features 16 form-C contact relays for load switching, allowing you to control various devices or systems. The module also includes 2 digital inputs for tamper and power fault status monitoring, enhancing the security of your installation. CKM-MR16OUT supports RS-485 communication, enabling seamless integration with other devices and systems. Its compact design and versatile mounting options make it suitable for various applications and environments.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI