Fully assembled kit includes:
- Trove1 enclosure with TM1 Altronix/Mercury backplane
- (1) eFlow4NB - Power Supply/Charger
- (1) VR6 - Voltage Regulator
- (1) ACM4 - Fused Access Power Controller
T1MK1F4S
4 Door Kit with Fused Outputs
Fully assembled kit includes:
- Trove1 enclosure with TM1 Altronix/Mercury backplane
- (1) eFlow4NB - Power Supply/Charger
- (1) VR6 - Voltage Regulator
- (1) ACM4 - Fused Access Power Controller
- (1) PDS8 - Dual Input Power Distribution Module
T1MK1F4D
4 Door Kit with PTC Outputs
Fully assembled kit includes:
- Trove1 enclosure with TM1 Altronix/Mercury backplane
- (1) eFlow4NB - Power Supply/Charger
- (1) VR6 - Voltage Regulator
- (1) ACM4CB - PTC Access Power Controller
T1MK1F4SD
4 Door Kit with PTC Outputs
Fully assembled kit includes:
- Trove1 enclosure with TM1 Altronix/Mercury backplane
- (1) eFlow4NB - Power Supply/Charger
- (1) VR6 - Voltage Regulator
- (1) ACM4CB - PTC Access Power Controller
- (1) PDS8CB - Dual Input Power Distribution Module
Access & Power Integration
Rev. T1MK022719
Installing Company: _____________________ Service Rep. Name: __________________________________________
Address: ________________________________________________________ Phone #: _________________________
All registered trademarks are property of their respective owners. More than just power.™
Installation Guide
All components of these Trove kits are UL Listed sub-assemblies.
Please refer to the included corresponding Sub-Assembly Installation Guides for further information.
- 2 - T1MK Kits
Overview:
Altronix Trove Mercury kits are pre-assembled and consist of Trove1M1 enclosure/backplane with factory installed Altronix power
supply/charger and sub-assemblies. These kits also accommodate various combinations of Mercury boards for up to four (4) doors in a
single enclosure.
Configuration Chart:
Altronix
Model
Number
120VAC 60Hz
Input Current (A)
Power Supply Board
Input Fuse Rating
Power Supply Board
Battery Fuse Rating
Nominal DC
Output Voltage
Maximum
Supply Current
for Main and
Aux. Outputs
on Power
Supply board
and ACM4/
ACM4CB
Access Power
Controller’s
outputs (A)
Fail-Safe/Fail-Secure or
Dry Form “C” Outputs
Fail-Safe/Fail-Secure
Outputs (auto-resettable)
Current Per
ACM4 Output (A)
Current Per
ACM4CB Output (A)
ACM4/ACM4CB Board
Input Fuse Rating
ACM4 Board
Output Fuse Rating
ACM4CB Board
Output PTC Rating
PDS8/PDS8CB Board
Input Fuse Rating
PDS8 Board
Output Fuse Rating
PDS8CB Board
Output PTC Rating
[DC] [Aux]
24VDC Output
Range (V)
24VDC Output
Range (V)
T1MK1F4
3.5
5A/
250V
7.5A/
32V
20.28-
26.4
20.28-
26.4
24VDC @ 3.6A 4 2.5
10A/
250V
3A/
250V
T1MK1F4D
3.5
5A/
250V
7.5A/
32V
20.28-
26.4
20.28-
26.4
24VDC @ 3.6A 4 2.0
10A/
250V
2.0A
T1MK1F4S
3.5
5A/
250V
7.5A/
32V
20.28-
26.4
20.28-
26.4
24VDC @ 3.6A 4 2.5
10A/
250V
3A/
250V
10A/
250V
3A/
250V
T1MK1F4SD
3.5
5A/
250V
7.5A/
32V
20.28-
26.4
20.28-
26.4
24VDC @ 3.6A 4 2.0
10A/
250V
2.0A
10A/
250V
2.0A
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI and with all local codes and authorities having
jurisdiction. Product is intended for indoor use only.
1. Remove backplane from enclosure. Do not discard hardware.
2. Mark and predrill holes in the wall to line up with the top two (2) keyholes in the enclosure. Install two upper fasteners and screws
in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the two upper screws; level and secure.
Mark the position of the lower two holes. Remove the enclosure. Drill the lower holes and install the two fasteners. Place the
enclosure’s upper keyholes over the three upper screws. Install the two lower screws and make sure to tighten all screws.
3. Mount included UL Listed tamper switch (Altronix Model T112 or equivalent) in desired location, opposite hinge.
Slide the tamper switch bracket onto the edge of the enclosure approximately 2” from the right side (Fig. 1, pg. 2).
Connect tamper switch wiring to the Access Control Panel input or the appropriate UL Listed reporting device.
To activate alarm signal open the door of the enclosure.
4. Position Mercury access controller modules over corresponding standoffs and depress onto
snap on standoffs, Fig. 2, pg. 3.
5. Refer to the eFlow Power Supply/Charger Installation Guide for eFlow4NB,
and corresponding Sub-Assembly Installation Guide for ACM4(CB), PDS8(CB)
and VR6 for further installation instructions.
6. Mount backplane to enclosure with hardware.
Fig. 1
Tamper Switch
(provided)
To Access Control Panel or
UL Listed Reporting Device
Edge of
Enclosure
Enclosure
T1MK Kits - 3 -
Altronix
eFlow4NB
– DC +– BAT +
+ IN - +OUT-
ON-5V
OFF-12V
Altronix
VR6
TRG
TRIGGER
INPUT
ACM4
ACCESS POWER
CONTROLLER
LED1 LED2 LED3 LED4
MAIN
OUTPUT 1
NC C NO COM NC C NO COM NC C NO COM NC C NO COM
OUTPUT 2 OUTPUT 3
IN GND
1
IN GND
2
IN GND
3
IN GND
4
OUTPUT 4
-- +
CONTROL
-- +
POWER
+INP- T +RET-
INTERFACE
NO C NC
FACP
Altronix ACM4(CB)
A
B
C
D D
C
B
A
T1MK1F4 and T1MK1F4D: Configuration of Mercury Boards:
1. Fasten snap on standoffs onto metal pems configuration (A), (B), (C) or (D) of backplane depending on the access controller (Fig. 2, pg. 3).
2. Position access controller module over corresponding standoffs and depress onto snap on standoffs (Fig. 2a, pg. 3).
3. Mount backplane to enclosure with hardware.
Access Controller Position Chart for the Following Models:
Mercury Access Controller Pem Mounting
EP1502, LP1502, MR52, MR16IN, MR16OUT
A
EP1501, LP1501, MR51e, MR62e
B
MR50
C
EP2500, LP2500, MUX8
D
Fig. 2
Snap On
Standoff
Mercury Board
Backplane
Pem
Fig. 2a
- 4 - T1MK Kits
Altronix
eFlow4NB
– DC +– BAT +
TRG
TRIGGER
INPUT
ACM4
ACCESS POWER
CONTROLLER
LED1 LED2 LED3 LED4
MAIN
OUTPUT 1
NC C NO COM NC C NO COM NC C NO COM NC C NO COM
OUTPUT 2 OUTPUT 3
IN GND
1
IN GND
2
IN GND
3
IN GND
4
OUTPUT 4
-- +
CONTROL
-- +
POWER
+INP- T +RET-
INTERFACE
NO C NC
FACP
Altronix ACM4(CB)
Altronix PDS8(CB)
+ INP1
--
DM1 +
OFF
IN1
IN2
Out1
<
1 off 2
>
DM1 +
DM2 +
DM2 +
Common (--- )
Common (--- )
+ INP2
--
IN2 Fuse
IN1 Fuse
Common Power Outputs (NEG)
N
P
OUT1 OUT2 OUT3 OUT4 OUT5 OUT6 OUT7 OUT8
1 2 3 4 5 6 7 8
Out2
<
1 off 2
>
Out3
<
1 off 2
>
Out4
<
1 off 2
>
Out5
<
1 off 2
>
Out6
<
1 off 2
>
Out7
<
1 off 2
>
Out8
<
1 off 2
>
A
B
C
D D
C
B
A
T1MK1F4S and T1MK1F4SD: Configuration of Mercury Boards:
1. Fasten snap on standoffs onto metal pems configuration (A), (B), (C) or (D) of backplane depending on the access controller (Fig. 3, pg. 4).
2. Position access controller module over corresponding standoffs and depress onto snap on standoffs (Fig. 3a, pg. 4).
3. Mount backplane to enclosure with hardware.
Access Controller Position Chart for the Following Models:
Mercury Access Controller Pem Mounting
EP1502, LP1502, MR52, MR16IN, MR16OUT
A
EP1501, LP1501, MR51e, MR62e
B
MR50
C
EP2500, LP2500, MUX8
D
Fig. 3
Snap On
Standoff
Mercury Board
Backplane
Pem
Fig. 3a
- 5 - T1MK Kits
eFlow Power Supply/Chargers can be Controlled and Monitored while
Reporting Power/Diagnostics from Anywhere over the Network...
LINQ2 Mounts Inside any Trove Enclosure
LINQ2 - Network Communication Module
LINQ2 provides remote IP access to real-time data from eFlow power supply/chargers to help keep
systems up and running at optimal levels. It facilitates fast and easy installation and set-up, mini-
mizes system downtime, and eliminates unnecessary service calls, which helps reduce Total Cost
of Ownership (TCO) - as well as creating a new source of Recurring Monthly Revenue (RMR).
LINQ2
Features:
- UL Listed in the U.S. and Canada.
- Local or remote control of up to (2) two Altronix eFlow power output(s) via LAN and/or WAN.
- Monitor real time diagnostics: DC output voltage, output current, AC & battery status/service, input trigger state change,
output state change and unit temperature.
- Access control and user managment: Restrict read/write, Restrict users to specific resources
- Two (2) integral network controlled Form “C” Relays.
- Three (3) programmable input triggers: Control relays and power supplies via external hardware sources.
- Email and Windows Dashboard notifications
- Event log tracks history.
- Secure Socket Layer (SSL).
- Programmable via USB or web browser - includes operating software and 6 ft. USB cable.
LINQ2 Module
Altronix eFlow
Power Supply
Network Connection:
Installation, Programming
and Monitoring
- 6 - T1MK Kits
Notes:
- 7 - T1MK Kits
Notes:
- 8 - T1MK Kits
Altronix is not responsible for any typographical errors.
140 58th Street, Brooklyn, New York 11220 USA | phone: 718-567-8181 | fax: 718-567-9056
web site: www.altronix.com | e-mail: [email protected] | Lifetime Warranty | Made in U.S.A.
IITrove1M1 Kit Series A15T
MEMBER
Trove1 Enclosure Dimensions (H x W x D approximate):
18” x 14.5” x 4.625” (457mm x 368mm x 118mm)
13.0”
(330.2mm)
4.5”
(114.3mm)
0.5897”
(14.98mm)
14.5”
(368mm)
1.45”
(36.83mm)
7.25”
(184.15mm)
4.5”
(114.3mm)
4.5”
(114.3mm)
2.75”
(69.85mm)
1.25”
(31.75mm)
1.5”
(38.09mm)
8.5”
(215.9mm)
18.0”
(457.2mm)
1.0958”
(27.83mm)
0.6012”
(15.27mm)
6.5”
(165.1mm)
1.25”
(31.75mm)
1.25”
(31.75mm)
1.5”
(38.09mm)
8.5”
(215.9mm)
6.5”
(165.1mm)
0.569”
(14.52mm)
1.948”
(49.483mm)
1.115”
(28.32mm)
1.362”
(34.59mm)
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8

Altronix TROVE T1MK1F4 Installation guide

Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI