Alarm SAF CPS240D-UL/CSA Installation guide

Type
Installation guide
J. Visual Indicators
1. Green AC LED (D5) Low Voltage AC Presence
2. Green DC OK LED (D17) Regulator Output Voltage in tolerance
3. Red DC1 LED (D11) DC1 Output Voltage Present
4. Red DC2 LED (D10) DC2 Output Voltage Present
I. AC and DC fault conditions are reported via Form 'C' relay contacts
1. 'AC' fault relay - Max Contact Rating: 30VDC/5A
2. 'DC' fault relay - Max Contact Rating: 30VDC/2A
Emergency Standby battery capacity for a minimum of four hours must be provided when using
optional batteries.
H. FAI (Fire Alarm Interface) Controlled Output operation (DC2)
1. For power presence with a normally open (n/o) circuit connected to the FAI
terminals, set S1 to 1 & 3 (default setting).
2. For power presence with a normally closed (n/c) circuit connected to the FAI
terminals, set S1 to 1 & 2.
G. Connect user system to 'DC1 and/or FAI controlled 'DC2' terminals. Caution: Observe
Polarity! Incorrect polarity may damage user system. refer to section 1. for maximum
allowable current.
F. if optional batteries are present, connect battery set to 'battery' terminals. (See Fig
4.)Caution: Observe Polarity! Incorrect polarity may damage battery set.
Recommended battery type - PowerSonic PS Series or Yuasa NP Series, sealed lead
acid/gel cell.
E. Verify output voltage by measuring output present at 'DC1' output and 'Battery'
terminals
12 Volt Battery 12 Volt Battery
12 Volt Configuration
+
-
12 Volt Battery 12 Volt Battery
24 Volt Configuration
+
-
Parallel Hook-Up Series Hook-up
OFFONJ3
OFFONJ1
24 V12 V (Default)
Output Voltage
IV. Optional Battery Configuration
D. Configure power supply output by positioning the following jumpers:
C. Low Voltage AC Input -Verify that both PCB’s LVAC terminal connections are wired
together. Connect CPS200 PCB to secondary winding of the transformer.
Transformer output voltage is approximately 28VAC.
B. Connect 120 VAC, 60 Hz, Single Phase to the Black and White leads of the
transformer in accordance with Article 725 of the National Electrical Code, Article 16
of the Canadian Electrical Code or other applicable codes.
A. Mount Cabinet per mechanical dimensions and knockouts given in Section 7.
II. Installation Instructions
12/24 VDC (field selectable), 2 and 4 amp dual power supplies for systems integration.
Common access control and system applications include powering door strikes, mag locks,
card readers, and other accessory devices.
Reserved
Standard Battery
Connection
FAI Connection
J3 and J4
"DC1" System DC
"DC1" System DC
S1
AC Fault Output
DC Fault Output
4.25
3.20
J1
5.75
5.00
Connect to Low
Voltage Transformer
7/14Ah2.0A2.5/4ACPS240DX-UL/CSA02902
7/14Ah2.0A2.5/4ACPS240D-UL/CSA02901
Max Battery
Capacity
Max AC Input
Current
Max System
Current
Model NumberOrder
Number
III. PCB Hookup Information (Typical both boards)I. Model Numbers
CPS240D-UL/CSA
CPS240DX-UL/CSA
Installation Instructions
AlarmSaf
65A Industrial Way, Wilmington MA 01887
-
3499, U
S
A
,Vo
i
c
e 978
-
658
-
6717, Fax 978
-
658 8638,
www.alarmsaf.com
2, Rev
A
52
-
2
14
,
0
8
/
14
/01
V. Troubleshooting
Wiring Requirements
Power limited and non power-limited circuit wiring must remain separated by at least 0.25” within the
cabinet. All power limited and non power limited circuit wiring must enter and exit the cabinet through
different knockouts.
CPS240D-UL/CSA
CPS240DX-UL/CSA
Installation Instructions
AlarmSaf
65A Industrial Way, Wilmington MA 01887
-
3499, U
S
A
,Vo
i
c
e 978
-
658
-
6717, Fax 978
-
658 8638,
www.alarmsaf.com
2, Rev
A
52
-
2
14
,
0
8
/
14
/01
DC OUTPUT
POWER LIMITED
WHEN CONNECTED
TO POWER
LIMITED CIRCUITS
120VAC
4A POWER SUPPLY
2A POWER SUPPLY
TB3
F1
C5
C10
C4
C8
R9
R1 5
D8
D15
C11
TB4
C1
Q2
K3
J1
R26
R8
S1
R27
J4
J3
R25
U1
D20
D3
REV A
FAI
+
+
+
DC2DC1
+
DC
AC
LVAC
~
NC
NO C CNC NO
AC FAULT
DC FAULT
SB
BATTERY
+
-
DC1 OUT
+
-
DC2 OUT
+
-
CPS-600
AlarmSaf
1
2
3
LVAC NON POWER LIMITED
VI. Wiring Diagram
VII. Mounting and Knockout positions
Remove system load on
affected board. Verify Red
LED is illuminated, check
system wiring.
Verify setting per Section II line
8
Verify setting per Section II ,
line 8. Verify circuit driving FAI
connector.
Replace power supply
Short circuit in system wiring
S1 improperly set
FAI not driven correctly
Defective power supply
Red DS2 LED not illuminated
on 2A or 4A power supply.
Remove system load on
affected board. Verify Red
LED illuminated. If it does,
verify system wiring.
Replace unit
Short circuit in system wiring
Defective power supply
Red DS1 LED not illuminated
on 2A or 4A power supply
Check LVAC connection
Replace affected board
Loss of input to switcher
Loss of switcher voltage
Green AC LED not illuminated
on 4A power supply only
Wire not properly connected
to 2A PCB
Loss of low VACGreen AC LED not illuminated
on 2A power supply only
Restore 120VAC
Replace Transformer
Loss of 120VAC
Loss of low VAC
Green AC LED not illuminated
on 2A & 4A power supplies
CorrectionPossible CauseSymptoms
15.38
1.16
0
9.94
1.81
0
13.56
4.34
1.94 TYP
15.00
12.06
3.00
KEY LOCK
0
2.12
0
0
0
0
0
CPS240D-UL/CSA
1.50
0
13.94
1.00
0
9.0
17.00
0
12.00
2 PLCS
4.34
1.94 TYP
18.00
12.00
2 PLCS
3.00
2 PLCS
KEY LOCK
15.21
18.21
CPS240DX-UL/CSA
  • Page 1 1
  • Page 2 2

Alarm SAF CPS240D-UL/CSA Installation guide

Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI