Alarm SAF CPS100 Installation guide

Category
Electrical relays
Type
Installation guide
I.
Model Numbers
N/A4.0A28V360Transformer00634
17AH2.8A8ACPS100C - Cabinet00867
17AH2.8A8ACPS100-PCB00866
Max. Battery
Capacity
Max. AC Input
Current
Max. System
CurrentModel Number
Order
Number
12/24 VDC (field selectable), 8 power supplies for systems integration. Common access control and
security system applications include powering door strikes, mag locks, card readers and other
accessory devices.
II
.
Installation Instructions
1.
Mount cabinet/board per mechanical dimensions and knockouts given in section III / VII.
2.
Connect 120VAC,60 HZ., single phase to the black and white leads of the transformer in
accordance with Article 725 of the National Electrical Code , Article 16 of the Canadian Electrical
Code or other applicable codes.
3. Low Voltage AC Input - Connect to Secondary winding of the transformer. Transformer output
voltage is approximately 28VAC
4. Configure power supply output by positioning the appropriate jumpers
OFFONJ3
OFFONJ1
24V12V (Factory Default)
Output Voltage
5.
Verify Output voltage by measuring output present at “DC1” output and “Battery “ terminals.
6.
If optional batteries are present, connect battery set to “Battery” terminals (see Fig. IV). CAUTION:
Observe polarity; incorrect polarity may damage batteries. Recommended battery type -
PowerSonic (PS Series) or YUASA (NP - Series) sealed lead acid/gel cell.
7.
Connect user system to “DC1” and/or FAI controlled “DC2” terminals. Caution: Observe polarity;
incorrect polarity may damage user system. Refer to Section 1 for Maximum Allowable Current.
8.
FAI controlled Output (DC2) operation:
a. For power presence with a n/o circuit to FAI connector, set S1 to 1 & 3. (Default setting)
b. For power present on a n/c circuit to FAI, connector, set S1 to 2 & 3
9. AC and DC fault outputs are reported via Form “C” relays;
a. “AC” fault relay maximum contact switching : 30VDC/5A
b. ‘DC’ fault relay maximum contact switching : 30VDC/5A
10.
Visual Indicators:
a.
Green AC LED (D5) Low Voltage AC Presence
b.
Green DC OK LED (D17) Regulator Voltage Output Presence
c.
Red DC1 LED (D11) DC1 Output Voltage Presence
III. PCB Hookup Information
IV. Optional Battery Configuration
V.
Troubleshooting
CPS100
CPS100C
Installation Instructions
AlarmSaf
65A Industrial Way, Wilmington MA 01887-3499, USA, Voice 978-658-6717, Fax 978-658 8638, www.alarmsaf.com Page 1 of 2, Rev A 52-227, 02/12/02
12 Volt B a tte ry 12 Volt B a tte ry
12 Volt Config u ra tion
+
-
12 Volt B a tte ry 12 Volt B a tte ry
24 Volt Config u ra tion
+
-
Parallel Hook-Up Series Hook-up
Remove system load. Verify
red LED is illuminated, check
system wiring
Replace unit
Short circuit in system wiring
Defective power supply
Red DS2 LED not illuminated
Remove system load. Verify
red LED is illuminated, check
system wiring
Replace unit
Short circuit in system wiring
Defective power supply
Red DS1 LED not illuminated
Replace Board
Check transformer connection
Loss of switcher voltage
Loss of input to switcher
Green DC LED not illuminated
Restore 120VAC
Replace Transformer
Loss of 120VAC
Loss of Low VAC
Green AC LED not Illuminated
CorrectionPossible CauseSymptoms
VI. WIRING DIAGRAM
VII. CABINET MOUNTING AND KNOCKOUT POSITIONS
CPS100
CPS100C
Installation Instructions
AlarmSaf
65A Industrial Way, Wilmington MA 01887-3499, USA, Voice 978-658-6717, Fax 978-658 8638, www.alarmsaf.com Page 2 of 2, Rev A 52-227, 02/12/02
18.21
1.16
0
9.94
1.81
0
13.56
4.34
1.94 TY P
15.00
12.06
3.00
KEY LO C K
15.21
0
12.1
2
0
0
0
0
0
CPS100C
120VAC
LVA C
DC OUT
TYPICAL WIRING LA YO U T
CPS100-UL/CSA
DC1 DC2
AC
LVAC
SB + BAT -
DC1 OUT
DC2 OUT
+
--
+