Alarm SAF BP-001 Quick start guide

  • Hello! I am an AI chatbot trained to assist you with the Alarm SAF BP-001 Quick start guide. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
For Use With PS-5, NPL, or CPS Power Supplies
PS5 intructions( see side two for additional instructions)
Mechanical Installation Instructions
Remove the two mounting screws from the PS-5 on the terminal strip end.
Replace mounting screws with male-female (m-f) standoffs supplied.
Use two supplied ¼” screws to connect the 1” standoffs to the indicated points on the BP-001. these standoffs are used
for mechanical support only and do not tie to the cabinet
Place the empty BP-001 mounting holes over the m-f standoffs and screw together using two ¼” screws.
Wiring
Connect Battery (+) on the PS-5 to Battery (+) on the BP-001
Connect DC (+) on the PS-5 to PS-5 (+) on the BP-001.
Connect DC (-) on the PS-5 to PS5 (-) on the BP-001.
Connect the System DC Load to the PS-5 (+) and PS-5 (-) terminals of the BP-001
Verify the battery set wires are not connected to the battery
Connect Battery Set (+), red, wire to the BAT (+) terminal of the BP-001
Connect Battery Set (-), black, wire to the BAT (-) terminal of the BP-001
Power-Up
For 24 VDC usage, CUT the BLUE jumper
Power the system and observe the BP-001 System OK LED is OFF after approximately two minutes.
Connect the battery set wires to the battery set.
Observe the BP-001 System OK LED is ON after one minute
Fault Relay
The fault relay provides a failsafe Form ‘C’ contact set. The relay is powered under a normal condition and drops out on
fault. This operation allows for an automatic fault indication to the system in the event of loss of primary AC and a
simultaneous lack of battery power.
Visual Indicators
Yellow L Indicates low charge voltage, can temporarily occur during high charge
Yellow H Indicates high charge voltage
Green OK Indicates system OK
Note: The Yellow L may illuminate if the battery set is only partially charged.
Mechanical Stackup
BATTERY +
BATTERY -
SYSTEM DC +
SYSTEM DC -
BP-001
PS-5
To
Battery Set
To
System Load
H
L
OK
NO
NC
C
Fault Relay
BLUE
Note: Battery (-) on PS-5
board not used with BP-001
7/16" m-f standoff
½" nylon standoff
½" nylon standoff
1" nylon standoff
¼" Screw
BP-001
PS-5
Transformer
BATTERY PRESENCE MONITOR (BP-001)
65A Industrial Way, Wilmington, MA 01887-3499 (978) 658-6717, Fax. (978) 658-8638 www.alarmsaf.com
52-024 05/17/01
For Use With Other AlarmSaf Power Supplys
Power-Up
For 24 VDC useage, CUT the BLUE jumper
Power the system and observe the BP-001 System OK LED
is OFF after two minutes.
Connect the battery set wires to the battery set.
Observe the BP-001 System OK LED is ON after one
minute
Fault Relay
The fault relay provides a failsafe Form ‘C’ contact set. The
relay is powered under a normal condition and drops out
on fault. This operation allows for an automatic fault
indication to the system in the event of loss of primary AC
and a simultaneous lack of battery power.
Visual Indicators
Yellow L Indicates low charge voltage, can
temporarily occur during high charge
Yellow H Indicates high charge voltage
Green OK Indicates system OK
Note: The Yellow LED may illuminate if the battery set is only
partially charged.
Mechanical Installation Instructions
Mount BP-001 board into cabinet with:
A. Four Mounting standoffs
Drill four
1
/
8
” holes in cabinet at mounting location
Install four nylon standoffs with supplied ¼” screws
Mount board to standoffs with four supplied ¼”
screws
B. SnapTrak
Drill two
1
/
8
” holes in cabinet at mounting location
Install Snaptrack
TM
with two ¼” screws and nuts
supplied
Snap board into position such that board is centered in
SnapTrack
TM
TM- Augat Corporation
Wiring
Verify the battery set wires are not connected to the
battery
Connect Battery (+) on the Power Supply to Battery (+) on
the BP-001
Connect DC (+) on the Power Supply to PS-5 (+) on the
BP-001.
Connect DC (-) on the Power Supply to PS5 (-) on the
BP-001.
Connect the System DC Load to the PS-5 (+) and PS-5 (-)
terminals of the BP-001
Connect Battery Set (+), red, wire to the BAT (+) terminal
of the BP-001
Connect Battery Set (-), black, wire to the BAT (-) terminal
of the BP-001
Mechanical Mounting
2"
3.4"
~ 3"
SnapTrack
4.7"
3.25"
BP-001
BATTERY +
BATTERY -
SYSTEM DC +
SYSTEM DC -
BP-001
Power Supply
To
Battery Set
To
System Load
H
L
OK
NO
NC
C
Fault Relay
BLUE
Note: Battery (-) on PS-5
board not used with BP-001
BATTERY PRESENCE MONITOR (BP-001)
65A Industrial Way, Wilmington, MA 01887-3499 (978) 658-6717, Fax. (978) 658-8638 www.alarmsaf.com
52-024 05/17/01
/