TheadvancedheatingapplicationA314.7isveryflexible.These
arethebasicprinciples:
Heating/coolingwithroomtemperatureandairquality
control
Typically,theheatingtemperatureisadjustedaccordingtoyour
requirements.TheairducttemperaturesensorS3isthemost
importantsensor.ThedesiredtemperatureatS3issetintheECL
Comfortcontrollerasthe'Desiredinlettemperature'.
Therecoverycircuit,controlledbyM2,isconsideredasthemain
circuit,whereastheheatingcircuit(controlledbyM1)andthe
coolingcircuit(controlledbyM3)arethesupplementarycircuits.
ThemotorizedcontrolvalveM1(controllingtheheating
temperature)isopenedgraduallywhentheS3temperatureis
lowerthanthedesiredS3temperatureandviceversa.
Atcooling,themotorizedcontrolvalveM3controlsthecooling
temperature.
Roomtemperature:
Iftheroomtemperature(S4orECA30)doesnotequalthedesired
roomtemperature,thedesiredtemperatureatS3canbeadjusted.
AtoolowtemperatureatS4willactivatetheheatingcircuit(M1),
whereasatoohighairducttemperaturewillactivatethecooling
circuit(M3).A"Deadzone"(=numberofdegrees)canbeset
inordertoavoidunstableshiftsbetweenheatingandcooling
operation.
Bymeansofaweekschedule(upto3‘Comfort’periods/day),the
heatingcircuitcanbein‘Comfort’or‘Saving’mode(twodifferent
temperaturevaluesfordesiredinlettemperatureandtwodifferent
temperaturevaluesfordesiredroomtemperature).
ThefanF1isON/OFFcontrolledaccordingtotheschedule
andheatingdemand.AdamperP2canbeON/OFFcontrolled
accordingtoschedule.ThecirculationpumpX3isON/OFF
controlledaccordingtoheatingdemand.
Airqualitycontrol(CO
2
measuredin"ppm"):
ThefansV2andV3areincreasedinspeedwhentheppmvalue(0-
10voltsignalmeasuredbyS11)exceedsaselectablelimit.Speed
relationbetweenV2andV3canbeset.Asanalternative,theS11
signalcanexpressanRHsignal(RelativeHumidity).
Heatrecovery:
Inordertoutilizeheatfromtheexitairduct,arotating
heat-exchanger,acrossheat-exchangerorafluidbatterycan
becontrolledbyM2.BasedontheoutdoortemperatureS1,the
entryducttemperatureS13andtheexitducttemperatureS14the
recoveryefficiency(in%)canbeindicated.
Nightcooling:
DuringSavingmodeapassivecoolingcanbearranged,mainly
underthefollowingconditions:
•roomtemperatureishigherthandesiredsavingroom
temperature
•outdoortemperatureislowerthantheroomtemperature
•schedule3isinComfortmode
TypicalA314.7application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
ElectroniccontrollerECLComfort310
ECA32
Built-inextensionmodule
S1
Outdoortemperaturesensor
S2
(Optional)Compensationtemperaturesensor
S3
Ducttemperaturesensor
S4Roomtemperaturesensor*
S5
(Optional)Returntemperaturesensor
S6
(Optional)Frosttemperaturesensor
S7
(Optional)Frostthermostat
S8
(Optional)Firethermostat
S9
Fanmonitor
S10
Filtermonitor
S11
Airquality(CO
2
)signal(ppm).Alternative:Relative
Humiditysignal
S13
Entryducttemperaturesensor
S14
Exitducttemperaturesensor
F1
Fan(ON/OFF)
P2
Damper(ON/OFF)
X3
Circulationpump,heating(ON/OFF)
X4
Schedule3
X5
Circulationpump,cooling(ON/OFF)
P7
RecoverycircuitpumpON/OFF,(notillustrated)
M1
Motorizedcontrolvalve,heating(3-pointcontrolled)
M2
Rotatingheat-exchanger(0-10voltcontrolled)
M3
Motorizedcontrolvalve,cooling(3-pointcontrolled)
V2
Fanspeed(0-10voltcontrolled)
V3
Fanspeed(0-10voltcontrolled)
A1
Alarm
*Alternative:ECA30
20|©Danfoss|2017.03
VI.GU.A3.02