Danfoss ECA 30 / 31 Operating instructions

Type
Operating instructions

Danfoss ECA 30 / 31 is a remote control unit for room temperature control and override of ECL Comfort controllers. It features a built-in temperature sensor and supports connection of an external one. ECA 31 additionally has a built-in relative humidity sensor. The device can be connected to up to 10 ECL Comfort controllers and monitor their status. It allows for setting desired room temperature, switching between comfort, saving and holiday modes, and setting optimized start or stop times for heating or cooling.

Danfoss ECA 30 / 31 is a remote control unit for room temperature control and override of ECL Comfort controllers. It features a built-in temperature sensor and supports connection of an external one. ECA 31 additionally has a built-in relative humidity sensor. The device can be connected to up to 10 ECL Comfort controllers and monitor their status. It allows for setting desired room temperature, switching between comfort, saving and holiday modes, and setting optimized start or stop times for heating or cooling.

InstallationGuide
ECA30/31forECLComfort210/210B/310/310B
1.0TableofContents
1.0TableofContents.............................................1
2.0UserGuide.......................................................2
2.1Symboloverview..................................................2
2.2Introduction........................................................3
2.3DisplayinformationECA30/31.................................4
2.4OverridefunctionsECA30/31..................................9
3.0Installation......................................................10
3.1Importantsafetyandproductinformation....................10
3.2Mounting...........................................................14
3.3Placingthetemperaturesensors................................15
3.4Electricalconnections.............................................16
3.5ECA30/31setupprocedures...................................18
4.0Settings...........................................................26
4.1Roomtemperature................................................26
4.2Optimization........................................................27
4.3Holiday..............................................................28
DanfossDistrictEnergy
VI.GU.V1.02
DEN-SMT/DK1
InstallationGuideECA30/31forECLComfort210/210B/310/310B
2.0UserGuide
2.1Symboloverview
2.1.1Ageneraloverview:Whatdothesymbolsmean?
Symbol
Description
Outdoortemp.
Relativehumidityindoor
Roomtemp.
DHWtemp.
Temperature
Positionindicator
Scheduledmode
Comfortmode
Savingmode
Frostprotectionmode
Manualmode
Standby
Coolingmode
!
Activeoutputoverride
Optimizedstartorstoptime
Mode
Heating
Cooling
DHW
Commoncontrollersettings
Circuit
PumpON
PumpOFF
Actuatoropens
Actuatorcloses
42
Actuator,analoguecontrol
signal
Controlled
component
Symbol
Description
Alarm
Monitoringtemperaturesensor
connection
Displayselector
Max.andmin.value
Trendinoutdoortemperature
Windspeedsensor
Sensornotconnectedornotused
Sensorconnectionshort-circuited
7-23
Fixedcomfortday(holiday)
Activeinuence
Heatingactive
Coolingactive
Additionalsymbols,ECA30/31:
Symbol
Description
ECARemoteControlUnit
15
Connectionaddress(master:15,slaves:1-9)
Dayoff
Holiday
Relaxing(extendedcomfortperiod)
Goingout(extendedsavingperiod)
InECA30/31onlythesymbolsthatarerelevanttotheapplicationin
thecontrolleraredisplayed.
2
DEN-SMT/DK
VI.GU.V1.02
DanfossDistrictEnergy
InstallationGuideECA30/31forECLComfort210/210B/310/310B
2.2Introduction
TheRemoteControlUnits(RCU)ECA30andECA31areusedfor
roomtemperaturecontrolandoverrideoftheECLComfort210/
210BandECLComfort310/310Bcontrollers.
UptotworemotecontrolunitscanbeconnectedtooneECL
controllerinordertocontroltheECLcontrollerremotely.
Thedisplayhasbacklight.
TheRCUsareconnectedtotheECLComfortcontrollersbymeans
of2×twistedpaircablesforcommunicationandpowersupply
(ECL485communicationbus).
TheECA30/31hasabuilt-inroomtemperaturesensor.An
externalroomtemperaturesensorcanbeconnectedsubstituting
thebuilt-intemperaturesensor.
Furthermore,theECA31hasabuilt-inrelativehumiditysensorand
thesignalisusedinrelevantapplications.
Itispossibletoconnectupto2RCUsontheECL485
communicationbus.
OneRCUcanmonitormax.10ECLComfortcontrollers(master/
slavesystem).
Pleaseconsulttheuserguidethatisenclosedwithyourproductfor
moreinformationontheECLComfortcontroller.
ECA30
(codeno.087H3200)
Remotecontrolunitwithroom
temperaturesensor
ECA31
(codeno.087H3201)
Remotecontrolunitwithroom
temperaturesensorandrelative
humiditysensor
SafetyNote
Toavoidinjuryofpersonsanddamagestothedevice,itisabsolutely
necessarytoreadandobservetheseinstructionscarefully.
Necessaryassembly,start-up,andmaintenanceworkmustbe
performedbyqualiedandauthorizedpersonnelonly.
Thewarningsignisusedtoemphasizespecialconditionsthatshould
betakenintoconsideration.
Thissymbolindicatesthatthisparticularpieceofinformationshould
bereadwithspecialattention.
DanfossDistrictEnergy
VI.GU.V1.02
DEN-SMT/DK3
InstallationGuideECA30/31forECLComfort210/210B/310/310B
2.3DisplayinformationECA30/31
2.3.1Howtonavigate
ThedisplayandthedialareusedinthesamewayasintheECL
ComfortController.
Younavigateinthecontrollerbyturningthedialleftorrightto
thedesiredposition().
Thedialhasabuilt-inaccellerator.Thefasteryouturnthedial,the
fasteritreachesthelimitsofanywidesettingrange.
Thepositionindicatorinthedisplay()willalwaysshowyouwhere
youare.
Pushthedialtoconrmyourchoices().
ThedisplayexamplesarefromanECA30andanECA31.
Theexamplesmightdifferfromyourapplication.
ECA30:ECA31:
2.3.2ECA30/31,displayinformation
ThecontrollericonhasanaddressindicationoftheconnectedECL
Comfortcontroller.
Tochangeconnectionaddress:
1.ChooseECApicture
2.Movethepositionindicatortothecontrollericon
3.Pushthedialtoselectthecontrollericon
4.Turnthedialtoselectdesiredaddress
5.Pushthedialtoconrmyourchoice
ExampleshowingconnectedECLComfortControlleraddress.
2.3.3Pop-up:Copynewapplication,YES/NO
ThersttimeanECA30/31connectstoanECLComfort
controllerwithanewapplicationoraknownapplicationwitha
newlanguage,theECA30/31askstocopytheapplicationand
languagetotheECA30/31.
Propercommunicationisnotpossiblebeforetheapplicationhas
beencopied.
NO:TheapplicationwillnotbecopiedtotheECA30/31.
YES:TheapplicationwillbecopiedtotheECA30/31.
Typically,theselectionis"YES".
"NO"isselectedwhensomeofseveralECLComfortcontrollersin
anECL485bussystemshouldnotbecopiedtotheECA30/31.
WhenstartingtheECA30/31forthersttime,thereactiontime
seemsslow.
Normalreactiontimeisachievedwhentheapplicationhasbeen
copiedtotheECA30/31.
4DEN-SMT/DK
VI.GU.V1.02
DanfossDistrictEnergy
InstallationGuideECA30/31forECLComfort210/210B/310/310B
2.3.4Situation:Copying
Theapplication,forexampleA266.1,iscopiedtotheECA30/31.
ThecopiedapplicationissavedintheECA30/31.Herebythe
applicationdoesnotneedtobecopiedagainthenexttimetheECA
30/31connectstothesameECLComfortcontroller.
Upto10applicationscanbesaved.
2.3.5Pop-up:ApplicationrequiresnewerECA
Thispop-upmessageindicatesthattheapplicationcannotrunin
theECA30/31becausenewimprovementshavebeenmade.
AnECA30/31musthavetheversion1.39asaminimuminorder
tobeupdatedfromanapplicationkey.
Inthisexample1.30iscurrentversionand1.40ornewerisdesired
version.
Situation:
TheECA30/31willdisplaythisinformation(anXontheECA30/
31symbol)iftheapplicationintheECLcontrollerdoesnotcomply
withtheECA30/31.
Inthisexample1.10iscurrentversionand1.42isdesiredversion.
DanfossDistrictEnergy
VI.GU.V1.02
DEN-SMT/DK
5
InstallationGuideECA30/31forECLComfort210/210B/310/310B
2.3.6Situation:ECAMENUpointonly
Thisdisplayindicatesthatanapplicationhasnotbeenuploadedor
thecommunicationtotheconnectedECLcontrollerisnotworking
properly.
AnXontheECLcontrollersymbolindicatesthatthereisno
communicationwithamasterontheECL485busnetwork.
Helpprocedure:
1.CheckwiringconnectionsbetweenECA30/31andECL
Comfortcontroller
2.Checkcommunicationaddress:
InECLComfort:MENU>Commoncontrollersettings>System
>Communication>ECL485addr.:
Asstandard"15"isselected.
InECA30/31:ECAMENU>ECASystem>ECACommunication
>Connectionaddr.:
Asstandard"15"isselected.
DisplaypartofECA30/31:
InasystemwithECA30/31andECLComfortcontroller(s)oneofthe
ECLComfortcontrollersmustbemaster(address15).
6DEN-SMT/DK
VI.GU.V1.02
DanfossDistrictEnergy
InstallationGuideECA30/31forECLComfort210/210B/310/310B
2.3.7Situation:ECApicture-Dateandroomtemperature
IntheECApicturethedateisshown.Someapplicationsshowthe
roomtemperaturetoo.
Modeselectoranddesiredroomtemperaturearenotshown.
TheECA30/31isnotsetuptocommunicatewithaheatingcircuit
intheconnectedECLcontroller.
Seetheexampleforestablishingthedesiredcommunication.
2.3.8Override
TheECA30/31isnotfactorysetuptocommunicatewithaheating
circuitintheconnectedECLcontroller.
Inordertoarrangetemporarilyoverride,theECA30/31mustbe
setuptocommunicatewiththedesiredheatingcircuitintheECL
Comfortcontroller.
Seethefollowingexamplesforestablishingthedesired
communication.
Example:
ECLComfort:
Circuit1>MENU>Settings>Application:
ECAaddr.:SettoA
DanfossDistrictEnergy
VI.GU.V1.02
DEN-SMT/DK7
InstallationGuideECA30/31forECLComfort210/210B/310/310B
Example,continued:
ECA30/31:
ECAMENU>ECASystem>ECAcommunication:
Connectionaddr.:
Setto15(onlyonecontroller,themaster,inthesystem)
Setto1...9or15(whenmasterandslave(s)controllersinthe
system)
Alternativesettingofaddress:
1.ChooseECApicture
2.Movethepositionindicatortothecontrollericon
3.Pushthedialtoselectthecontrollericon
4.Turnthedialtoselectdesiredaddress
5.Pushthedialtoconrmyourchoice
ExampleshowingconnectedECLComfortControlleraddress.
Example,continued:
ECA30/31:
ECAMENU>ECASystem>ECAoverride:
Overrideaddr.:
Setto15(onlyonecontroller,themaster,inthesystem)
Setto1...9or15(whenmasterandslave(s)controllersinthe
system)
Overridecircuit:
Setthedesiredcircuitnumber(1-4).
Note:
Onlyheatingcircuitscanbeoverridden.
IntheECLComfortcontrollertheheatingcircuitinquestion
mustbesettoAorB.
8DEN-SMT/DK
VI.GU.V1.02
DanfossDistrictEnergy
InstallationGuideECA30/31forECLComfort210/210B/310/310B
2.4OverridefunctionsECA30/31
Thetabletotherightshowstheoverridefunctions.
Theoverridefunctionsareenabledwhencommunicationhasbeen
established(seeECAMENU>ECAsystem>ECAoverride).
Furthermore,thefunctionselectoroftheheatingcircuitmustbein
scheduledmode.
Ifholidaymodeisactivatedthenholidaymodetakespriorityand
cancelstheoverridemode.
Extendedsavingmode:
Extendedcomfortmode:
Holidayawayfromhome:
Overridefunctions:
Holidayathome:
DHWcircuitscannotbetemporarilyoverridden.
Exampleonoverride:
GotoECAMENU
Placecursoratclocksymbol(Functionselector)
Push/turndialtoselectoverrideform
Ifscheduledmodeisnotselected,thecursorcannotbeplacedatthe
functionselector.
Extendedsavingmode:
Whenselected,theoverridestoptimecanbeset(max.23hours
ahead).
Inaddition,thedesiredroomtemperatureintheoverrideperiod
canbeset.
Extendedcomfortmode
:
Whenselected,theoverridestoptimecanbeset(max.23hours
ahead).
Inaddition,thedesiredroomtemperatureintheoverrideperiod
canbeset.
Holidayawayfromhome
:
Whenselected,theoverridestopdatecanbeset(max.365days
ahead).
Inaddition,thedesiredroomtemperatureintheoverrideperiod
canbeset.
Holidayathome:
Whenselected,theoverridestopdatecanbeset(max.365days
ahead).
Inaddition,thedesiredroomtemperatureintheoverrideperiod
canbeset.
When“holidayoverrideisselected,thestopdateisthelastholiday
date.
Example:
Stopdateissetto"15.11"(15thofNovember),meaningthatfrom
midnightbetweenthe15thofNovemberandthe16thofNovember,
theoverrideisdisabled.
DanfossDistrictEnergy
VI.GU.V1.02
DEN-SMT/DK9
InstallationGuideECA30/31forECLComfort210/210B/310/310B
3.0Installation
3.1Importantsafetyandproductinformation
3.1.1Importantsafetyandproductinformation
ThisInstallationGuideisassociatedwiththeRemoteControlUnits
ECA30(codeno.087H3200)andECA31(codeno.087H3201).
ECA30isaremotecontrolunitwithroomtemperaturesensor.
ECA31isaremotecontrolunitwithroomtemperaturesensorand
relativehumiditysensor.
ECA30andECA31canbeusedwithECLComfort210/210Band
ECLComfort310/310Bcontrollers.
Forinformationongeneralfunctionspleaseconsulttheinstallation
guidefortheapplicationkeyinquestion.
AdditionaldocumentationforECLComfort210and310,modules
andaccessoriesisavailableonwww.ecl.doc.danfoss.com.
SafetyNote
Toavoidinjuryofpersonsanddamagestothedevice,itisabsolutely
necessarytoreadandobservetheseinstructionscarefully.
Necessaryassembly,start-up,andmaintenanceworkmustbe
performedbyqualiedandauthorizedpersonnelonly.
Thewarningsignisusedtoemphasizespecialconditionsthatshould
betakenintoconsideration.
Thissymbolindicatesthatthisparticularpieceofinformationshould
bereadwithspecialattention.
AsthisInstallationGuidecoversseveralsystemtypes,specialsystem
settingswillbemarkedwithasystemtype.Allsystemtypesareshown
inthechapter:'Identifyingyoursystemtype'.
°C(degreesCelsius)isameasuredtemperaturevaluewhereasK
(Kelvin)oftenisusedfortemperaturedifferences.
10DEN-SMT/DK
VI.GU.V1.02
DanfossDistrictEnergy
InstallationGuideECA30/31forECLComfort210/210B/310/310B
TheIDno.isuniquefortheselectedparameter.
ExampleFirstdigitSeconddigitLastthreedigits
1117411174
-
Circuit1
Parameterno.
12174
1
2
174
-
Circuit2
Parameterno.
IfanIDdescriptionismentionedmorethanonce,itmeansthatthere
arespecialsettingsforoneormoresystemtypes.Itwillbemarked
withthesystemtypeinquestion(e.g.12174-A266.9).
ParametersindicatedwithanIDno.like"1x607"meanauniversal
parameter.
DisposalNote
Thisproductshouldbedismantledanditscomponents
sorted,ifpossible,invariousgroupsbeforerecycling
ordisposal.
Alwaysfollowthelocaldisposalregulations.
DanfossDistrictEnergy
VI.GU.V1.02
DEN-SMT/DK11
InstallationGuideECA30/31forECLComfort210/210B/310/310B
3.1.2UpdateofECA30/31software
ThermwareoftheECA30/31canbeautomaticallyupdated
whenakeycontainingnewECA30/31rmwareisinsertedin
theECLComfortcontrollerandthecontrollerhasnotyetgotan
applicationinstalled.
BoththeECLComfortcontrollerandtheECA30/31musthave
softwareversion1.39orhigher.
TheECA30/31rmwareupdatecanalsobestartedmanuallyby
usingtheupdatermwaremenuintheECA30/31duringnormal
operation.
ThenewrmwaremustbecopiedtotheECA30/31unitbefore
itcanbeapplied.
Duringthecopyprocessananimationshowingtheprogresswill
beshown.
WhenthenewrmwarehasbeencopiedtotheECA30/31the
copyprocesswillendwiththispicture.
AfterthenewrmwarehasbeencopiedtotheECA30/31unit
itwillupdatethedeviceitselfwhileshowinganhour-glassand
aprogressbar.
12
DEN-SMT/DK
VI.GU.V1.02
DanfossDistrictEnergy
InstallationGuideECA30/31forECLComfort210/210B/310/310B
Duringupdate:
DonotremovetheKEY
Ifthekeyisremovedbeforethehour-glassisshown,youhave
tostartafresh.
Donotdisconnectthepower
Ifthepowerisinterruptedwhenthehour-glassisshown,the
controllerwillnotwork.
DanfossDistrictEnergy
VI.GU.V1.02
DEN-SMT/DK13
InstallationGuideECA30/31forECLComfort210/210B/310/310B
3.2Mounting
3.2.1MountingtheRemoteControlUnitsECA30/31
Selectoneofthefollowingmethods:
Mountingonawall,ECA30/31
Mountinginapanel,ECA30
Screwsandrawlplugsarenotsupplied.
Mountingonawall
MountthebasepartoftheECA30/31onawallwithasmooth
surface.Establishtheelectricalconnections.PlacetheECA30/
31inthebasepart.
Mountinginapanel
MounttheECA30inapanelusingtheECA30framekit(ordercode
no.087H3236).Establishtheelectricalconnections.Securethe
framewiththeclamp.PlacetheECA30inthebasepart.TheECA
30canbeconnectedtoanexternalroomtemperaturesensor.
TheECA31mustnotbemountedinapanelifthehumidity
functionistobeused.
14DEN-SMT/DK
VI.GU.V1.02
DanfossDistrictEnergy
InstallationGuideECA30/31forECLComfort210/210B/310/310B
3.3Placingthetemperaturesensors
Roomtemperaturesensor
(ESM-10,ECA30/31RemoteControlUnit)
Placetheroomsensorintheroomwherethetemperatureistobe
controlled.Donotplaceitonoutsidewallsorclosetoradiators,
windowsordoors.
DanfossDistrictEnergy
VI.GU.V1.02
DEN-SMT/DK
15
InstallationGuideECA30/31forECLComfort210/210B/310/310B
3.4Electricalconnections
3.4.1Electricalconnections,ECA30/31
Terminal
ECL
Terminal
ECA30/31
Description
Type
(recomm.)
30
4
31
1
Twistedpair
322
333
Twistedpair
Cable2x
twistedpair
4
5
Ext.roomtemperature
sensor*
ESM-10
*
Afteranexternalroomtemperaturesensorhasbeenconnected,
ECA30/31mustberepowered.
ThecommunicationtotheECA30/31mustbesetupintheECL
Comfortcontrollerin'ECAaddr.'
TheECA30/31mustbesetupaccordingly.
AfterapplicationsetuptheECA30/31isreadyafter2–5min.A
progressbarintheECA30/31isdisplayed.
ECL 210 / 310
ECA 30 / 31
A
A
B
B
Da n fos s
87 H2 0 51.1 0
ESM-10
Iftheactualapplicationcontainstwoheatingcircuits,itispossible
toconnectanECA30/31toeachcircuit.Theelectricalconnections
aredoneinparallel.
Max.2ECA30/31canbeconnectedtoanECLComfort310controller
ortoECLComfort310controllersinamaster-slavesystem.
16DEN-SMT/DK
VI.GU.V1.02
DanfossDistrictEnergy
InstallationGuideECA30/31forECLComfort210/210B/310/310B
ECAinformationmessage:
Applicationreq.newerECA’:
ThesoftwareofyourECAdoesnotcomplywiththesoftwareofyour
ECLComfortcontroller.PleasecontactyourDanfosssalesofce.
Someapplicationsdonotcontainfunctionsrelatedtoactualroom
temperature.TheconnectedECA30/31willonlyfunctionasremote
control.
Totalcablelength:Max.200m(allsensorsincl.internalECL485
communicationbus).
Cablelengthsofmorethan200mmaycausenoisesensibility(EMC).
DanfossDistrictEnergy
VI.GU.V1.02
DEN-SMT/DK17
InstallationGuideECA30/31forECLComfort210/210B/310/310B
3.5ECA30/31setupprocedures
ECA30(codeno.087H3200)isaremotecontrolunitwithbuilt-in
roomtemperaturesensor.
ECA31(codeno.087H3201)isaremotecontrolunitwithbuilt-in
roomtemperaturesensorandhumiditysensor(relativehumidity).
Anexternalroomtemperaturesensorcanbeconnectedtoboth
typestosubstitutethebuilt-insensor.
AnexternalroomtemperaturesensorwillberecognizedatECA
30/31power-up.
Connections:Seethesection'Electricalconnections'.
Max.twoECA30/31canbeconnectedtooneECLcontroller
orasystem(master-slave)consistingofseveralECLcontrollers
connectedonthesameECL485bus.Inthemaster-slavesystem
onlyoneoftheECLcontrollersismaster.TheECA30/31can,
amongothers,besetto:
monitorandsettheECLcontrollerremotely
measuretheroomtemperatureand(ECA31)humidity
extendcomfort/savingperiodtemporarily
AfterapplicationuploadintheECLComfortcontroller,theremote
controlunitECA30/31willafterapprox.oneminuteaskto'Copy
application'.
ConrmthisinordertouploadtheapplicationtotheECA30/31.
Menustructure
ThemenustructureofECA30/31isan"ECAMENU"andtheECL
menu,copiedfromtheECLComfortcontroller.
TheECAMENUcontains:
ECAsettings
ECAsystem
ECAfactory
ECAsettings:Offsetadjustmentofthemeasuredroom
temperature.
Offsetadjustmentofrelativehumidity(ECA31only).
ECAsystem:Display,communication,overridesettingsandversion
info.
ECAfactory:EraseofallapplicationsintheECA30/31,restoreto
factorysettings,resetofECLaddressandrmwareupdate.
PartoftheECA30/31displayinECLmode:
PartoftheECA30/31displayinECAmode:
Ifonlythe"ECAMENU"isshown,itcanindicatethattheECA30/31is
nothavingcorrectcommunicationaddress.
SeeECAMENU>ECAsystem>ECAcommunication:ECLaddress.
InmostcasestheECLaddresssettingmustbe"15".
RegardingECAsettings:
WhenECA30/31isnotusedasremoteunit,theoffsetadjustments
menu(s)arenotpresent.
18DEN-SMT/DK
VI.GU.V1.02
DanfossDistrictEnergy
InstallationGuideECA30/31forECLComfort210/210B/310/310B
TheECLmenusareasdescribedfortheECLcontroller.
MostofthesettingsdonedirectlyintheECLcontrollercanbedone
viatheECA30/31too.
Allsettingscanbeseeneveniftheapplicationkeyisnotinsertedin
theECLcontroller.
Forchangingsettings,theapplicationkeymustbeinserted.
TheKeyoverview(MENU>'Commoncontrollersettings'>'Key
functions')doesnotshowtheapplicationsofthekey.
TheECA30/31willdisplaythisinformation(anXontheECA30/31
symbol)iftheapplicationintheECLcontrollerdoesnotcomplywith
theECA30/31:
Intheexample1.10iscurrentversionand1.42isdesiredversion.
DisplaypartofECA30/31:
Thisdisplayindicatesthatanapplicationhasnotbeenuploadedorthe
communicationtotheECLcontroller(master)isnotworkingproperly.
AnXontheECLcontrollersymbolindicateswrongsetupof
communicationaddresses.
WhenECA30/31isinECAMENUmode,thedateandmeasured
roomtemperatureisdisplayed.
ECAMENU>ECAsettings>ECAsensor
RoomTOffset
Settingrange
Factorysetting
–10.0...10.0K0.0K
Themeasuredroomtemperaturecanbecorrectedwith
anumberofKelvin.Thecorrectedvalueisusedbythe
heatingcircuitintheECLcontroller.
Minus
value:
Theindicatedroomtemperatureislower.
0.0K:
Nocorrectionofthemeasuredroomtemperature.
Plus
value:
Theindicatedroomtemperatureishigher.
Example:
RoomToffset:
0.0K
Displayedroomtemperature:
21.9°C
RoomToffset:
1.5K
Displayedroomtemperature:
23.4°C
DanfossDistrictEnergy
VI.GU.V1.02
DEN-SMT/DK19
InstallationGuideECA30/31forECLComfort210/210B/310/310B
ECAMENU>ECAsettings>ECAsensor
RHoffset(ECA31only)
Settingrange
Factorysetting
–10.0...10.0%0.0%
Themeasuredrelativehumiditycanbecorrectedwitha
numberof%-values.Thecorrectedvalueisusedbythe
applicationintheECLcontroller.
Minus
value:
Theindicatedrelativehumidityislower.
0.0%:
Nocorrectionofthemeasuredrelativehumidity.
Plus
value:
Theindicatedrelativehumidityishigher.
Example:
RHoffset:
0.0%
Displayedrelativehumidity:
43.4%
RHoffset:
3.5%
Displayedrelativehumidity:
46.9%
ECAMENU>ECAsystem>ECAdisplay
Backlight(displaybrightness)
Settingrange
Factorysetting
0...10
5
Adjustthebrightnessofthedisplay.
0:
Weakbacklight.
10:
Strongbacklight.
ECAMENU>ECAsystem>ECAdisplay
Contrast(displaycontrast)
Settingrange
Factorysetting
0...103
Adjustthecontrastofthedisplay.
0:
Lowcontrast.
10:
Highcontrast.
ECAMENU>ECAsystem>ECAdisplay
Useasremote
Settingrange
Factorysetting
OFF/ON*)
ECA30/31canactasasimpleornormalremotecontrol
fortheECLcontroller.
OFF:
Simpleremotecontrol,noroomtemperaturesignal.
ON:
Remotecontrol,roomtemperaturesignalisavailable.
*):
Differently,dependingonchosenapplication.
WhensettoOFF:TheECAmenushowsdateandtime.
WhensettoON:TheECAmenushowsdateandroomtemperature
(andforECA31relativehumidity).
20DEN-SMT/DK
VI.GU.V1.02
DanfossDistrictEnergy
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30

Danfoss ECA 30 / 31 Operating instructions

Type
Operating instructions

Danfoss ECA 30 / 31 is a remote control unit for room temperature control and override of ECL Comfort controllers. It features a built-in temperature sensor and supports connection of an external one. ECA 31 additionally has a built-in relative humidity sensor. The device can be connected to up to 10 ECL Comfort controllers and monitor their status. It allows for setting desired room temperature, switching between comfort, saving and holiday modes, and setting optimized start or stop times for heating or cooling.