Trend RD-IQL Installation Instructions Manual

Type
Installation Instructions Manual
RD-IQL Installation Instructions TG200576 Issue 4, 23-May-2014 1
Installation Instructions
RD-IQL
Room Display
Important: Retain these instructions
These instructions shall be used by trained service personnel only
If the equipment is used in a manner not specied by these instructions, the protection provided by the equipment may be impaired.
1
Dimensions
2
Mounting Requirements
3 INSTALLATION
1 BOX CONTENTS 2 STORING (Altitude: <2000 m (6562’)
CONTENTS
1 Box contents ..................................................................1
2 Storing ...........................................................................1
3 Installation .....................................................................1
4 Disposal .........................................................................8
RD-IQL Installation
Instructions (TG200576)
HO
2
+50 °C
(+122 °F)
-10 °C
(+14 °F)
95 %RH
It is recommended that the installation should comply
with the local electrical safety installation practices (e.g.
HSE Memorandum of Guidance on Electricity at Work
Regulations 1989, USA National Electric Code).
IMPORTANT
To satisfy the requirements of a limited power source
(EN60950-1). The RD-IQL must only be powered by TREND
IQVAV, IQL11+, IQL13+, IQL15+.
RD-IQL Rating 24 Vdc, 40mA
continued over page
> 50 cm (1’6”)
1.5 m (5’)
90 mm (3.54”)
25 mm (0.98”)
30 mm
(1.18 )
150 mm (6”)
500 mm
(1’ 6”)
minimum
150 mm (6”)
90 mm (3.54”)
0
2 RD-IQL Installation Instructions TG200576 Issue 4, 23-May-2014
RD-IQL Installation Instructions
2
Mounting Requirements (continued)
4
Remove Front Panel
5
Route Cable
3
Check IQL+, IQLVAV Controller Compatibility
3 INSTALLATION (continued)
+45 °C
(+113 ° F)
-10 °C
(+14 °F)
Operating Altitude: <2000 m (6562’)
(maximum accuracy 0 to 40 °C, 32 to 104 °F)
HO
2
0 %RH
90%RH
 


IQLs must have standard strategies or standard item allocations as follows:
S9, S10, S1, S2, S3 (IQLVAV, IQL11+, 13+, 15+)
I9 (IQL11+, 13+, 15+), I12 (IQLVAV)
S11, S7 (IQL13+, 15+)
IQLVAV, IQL11+ can use RD/IQL/K, /KOS
IQL13+, 15+ can use RD/IQL/K, /KOS, /KOSF
The RD’s potentiometer must be used (if potentiometer required); a direct connected potentiometer may not be used. A direct
connected temperature sensor may be used rather than the RD’s.
RD-IQL/K precludes use of PIR/pushbutton inputs and (on IQLVAV only) alarm contact input. A separate fan speed switch may
be used (IQL13+, 15+).
RD-IQL/KOS as RD-IQL/K except pushbutton is provided.
RD-IQL/KOSF as RD-IQL/KOS except Fan speed switch is provided (for IQL13+, 15+). A separate Fan Speed switch may be
used (rather than the RD’s).
Compatible with IQLVAV, IQL11+, 13+, 15+ only
RD-IQL Installation Instructions TG200576 Issue 4, 23-May-2014 3
Installation Instructions RD-IQL
6
Congure IQLVAV/IQL+ for use with RD
7
Congure IQLVAV link (IQLVAV only)
3 INSTALLATION (continued)
J5
RD
I5
A
S
Set link J5
Check link J6
Note that a PIN may be required to make changes. If
the PIN has been forgotten the users should contact
their supplier (installers contact Trend Technical
Support) quoting the generator number and neuron
id (both from Address module) whereupon a default PIN will
be supplied. This will only work for three attempts at entering
the PIN. After the default PIN is entered a new PIN should be
set up and remembered.
SET v5.1 IQLTool2
See IQLTool2
See PowerTool Manual (TE200163)
See Wupdn Manual (TE200162)
Connect Trend Tool for Text Communications
Congure parameters
The following parameters must be set up (their conguration is facilitated by IQLTool2 ‘Congure for RD-IQL’ feature):
Local Space Temp Type S9(Y=6) (use RD) - IQL11+, 13+, 15+, IQLVAV
Local SP Adjust Type S10(Y=6) (use RD) - IQL11+, 13+, 15+, IQLVAV
Local Fan Speed Type S11(Y=6) (use RD) - IQL13+, 15+
These settings are facilitated by IQLTool2.
If it is required to use a separate temperature sensor, leave Local Space Temp Type at default, S9(Y=1).
If it is required to use a separate fan speed switch, leave Local Fan Speed Type at default, S11(Y=3).
The following parameters should be set up if they have been changed from default:
Note that these parameters are in the standard strategies; equivalent parameters may have to be changed in non-standard strategies
Window Mode W5(S=O) (not window mode, default) - IQL11+
PIR Pb Select W6(S=O) (Pushbutton selected, default) - IQL11+, 13+, 15+
Remote Fan Spd K7(V=4) (auto, default) - IQL13+, 15+
The following command must be given:
R(z=1) :This writes changes to permanent ash memory, and causes the IQL/IQLVAV to start using the new settings
IQLVAV Installation Instructions
e.g. IQLVAV/xxx ../VAV (TG200704)
4 RD-IQL Installation Instructions TG200576 Issue 4, 23-May-2014
RD-IQL Installation Instructions
8
Connect ti IQQL+ Controller
11
Mount Unit
9
Check Start Up Reset
10
Engineer Temperature Offset
3 INSTALLATION (continued)
Either standard UK Pattress Box or Panel
2 off M3.5 x 35 mm
screws provided
M3.5 screw
46 mm (1.81”)
50 mm (1.97”)
60 mm
60 mm (2.36”)
°C
°F
%RH
Firmware version
if required to offset sensor value
a
b
c
d
or
ENG + 2
default = 0
°C
communications failure
°C
every 7 seconds
11+
L
24V
ac
LON
12
3
4
5
6
7
8
9
10
14 15
16 17 18
1
2
3
4
5
1
11
12
13
3
COM
LON
OK
SRV
PIN
C
24V
24V
2
Digital (TBus) input
First digital input:
IN3 for IQL11+,
IN4 for IQL13+ and IQL15+
IN5 for IQLVAV
Note that IQL+/IQLVAV may be connected while powered; if not power up IQL+/IQLVAV.
polarity independent
maximum distance 30 m (33 yds)
RD-IQL (rear view)
RD-IQL Installation Instructions TG200576 Issue 4, 23-May-2014 5
Installation Instructions RD-IQL
10
Engineer Display (if required)
3 INSTALLATION (continued)
a
b
c
d
,
ENG + 3
Select Temperature Units
if Temperature Units OK
°C
°F
e
f
g
,
Display Local Temperature
h
i
Use Local Sensor
j
k
Display Fan Mode
[Switch off for option /K, /KOS]
l
r
s
Display Occupation State
[Switch off for option /K]
t
u
Normal Mode
default = °C
,
On 1On 1
OnOff
if Local Temperature Display OK
if Fan Mode Display OK
if Occupation State Display OK
default =
default = On
default = On
if Local Sensor Use OK
On 6
Off
Off
m
n
o
p
q
default = On 4
On 2
On 3
On 4
On 5
On 2
On 3
On 4
On 5
On 2
On 3
On 4
On 5
WARNING: Do NOT switch off ‘Use Local Sensor (leave
at default = On). Switching Use Local Sensoroff will
cause IQL to cease controlling
On 6
1: 2 pos fan (Off/On)
2: 3 pos fan (Off/On/Auto)
3: 4 pos fan (Off/1/2/3)
4: 5 pos fan (Off/1/2/3/Auto)
5: 4 pos blind
6: 5 position blind
6 RD-IQL Installation Instructions TG200576 Issue 4, 23-May-2014
RD-IQL Installation Instructions
14
Replace Front Panel
13
Restore Defaults (if required)
3 INSTALLATION (continued)
a
b
c
d
ENG + 1 + 4
Restore Defaults
Normal Mode
RD checks settings valid - may declare errors - see step 13
Data Validation Mode
Defaults as shown in steps 9 and 10 plus
PIN default - no PIN
RD-IQL Installation Instructions TG200576 Issue 4, 23-May-2014 7
Installation Instructions RD-IQL
15
Check System
3 INSTALLATION (continued)
°C
S9 °C (°F) Temp
Dependent on option /K, /KOS, /KOSF see below
°C
°C
°C
°C
°C
S3 Occupation, Kc Fan Speed
S2 °C (°F) Setpoint
S3 Occupation
S7 Fan Speed
S2 °C (°F)
S2 °C (°F)
A
B
C
D
E
F
AUTO
/K, /KOS, /KOSF
/K, /KOS, /KOSF
/K, /KOS, /KOSF
/K, /KOS, /KOSF
/KOS, /KOSF
/KOSF only
If Fan Mode = 4



 

 


 





* Note that when using an IQL standard strategy, in step E the RD can override the occupation on, but not off. The strategy
will dene when the occupation switches off.
8 RD-IQL Installation Instructions TG200576 Issue 4, 23-May-2014
RD-IQL Installation Instructions
Please send any comments about this or any other Trend technical publication to [email protected]
© 2014 Honeywell Technologies Sàrl, ECC Division. All rights reserved. Manufactured for and on behalf of the Environmental and Combustion Controls
Division of Honeywell Technologies Sàrl, Z.A. La Pièce, 16, 1180 Rolle, Switzerland by its Authorized Representative, Trend Control Systems Limited.
Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content hereof without obligation
to notify any person of such revisions or changes.
Trend Control Systems Limited
Albery House, Springeld Road, Horsham, West Sussex, RH12 2PQ, UK. Tel:+44 (0)1403 211888 Fax:+44 (0)1403 241608 www.trendcontrols.com
Trend Control Systems USA
6670 185th Avenue NE, Redmond, Washington 98052, USA. Tel:(425) 869-3900 Fax:(425) 869-8445 www.trend-americas.com
4 DISPOSAL
WEEE Directive:
At the end of their useful life the packaging and
product should be disposed of by a suitable
recycling centre.
Do not dispose of with normal household waste.
Do not burn.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8