Fireye 129-145 Owner's manual

  • Hello! I am an AI chatbot trained to assist you with the Fireye 129-145 Owner's manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
1
®
129-145 REMOTE MOUNTING KIT
The 129-145-1, -2 and -3 mounting kits provide an easy, efficient method to panel mount the ED510
display module. Each kit contains a mounting plate, gasket, two (2) 8-32 x 1 1/4" mounting screws,
and connection cable: ED580-4 (4 foot cable) with the 129-145-1, ED580-8 (8 foot cable) with the
129-145-2, and ED580-2 (2 foot cable) with the 129-145-3.
ED610 MULTI-PORT CABLE CONNECTOR WITH TERMINAL STRIP
The ED610 is a multi-port adapter with two RJ45 and one RJ12 (4P4C) telephone jack connectors
and a 10-connector terminal strip. It facilitates remote cable connections between the E110 control,
ED510 Display Module, and the E500 Communication Interface. The ED610 is mounted on a flat
surface with two screws and is recommended where cable runs greater than eight (8) feet are required.
ED580 REMOTE DISPLAY CABLES
The ED580 remote display cable is a cable in varying lengths (2', 4', and 8') with an RJ45 connector
on each end of the cable. The ED580 is used to mount the ED510 display module remote from the
Flame-Monitor control (with EP programmers, Engineering code 28 or later or EPD programmers,
Engineering code 02 or later).
ED512 REMOTE MOUNTING CABLES
The ED512 remote mount cable is a cable in varying lengths (2', 4', and 8') with an RJ12 (4P4C) con-
nector on each end of the cable. The ED512 is used with the ED610 multi-port connector for connect-
ing the Flame-Monitor control (with EP programmers, Engineering code 28 or later or EPD
programmers) to the E500 Communication Interface. The ED512 cables are also used to customize
E300 messages. Refer to bulletins E-3001 and EC-3451.
ED150 REMOTE RESET CABLES
The Remote Reset Cables are 10 conductor flat ribbon cables with a connector on one end and with
two stripped and tinned conductors on the opposite end. Maximum length available is 25 feet
(7.62m). A momentary contact switch connected to the stripped end of the cable will allow for remote
reset of the FLAME-MONITOR.
See CAUTION on Page 3.
FLAME-MONITOR™
SYSTEM ACCESSORIES
129-145 Remote Display Mounting Kit
ED610 Multi-port Cable Connector
and Terminal Strip
ED580 Remote Display Cables
ED512 Remote Mounting Cables
ED150 Remote Reset Cables
E-8002
MARCH 27, 2015
2
ORDERING INFORMATION
REMOTE MOUNT THE ED510 DISPLAY USING 129-145 MOUNTING KIT
See Figure 1. The 129-145-1, -2, or -3 is used to panel mount the ED510 display.
To install the ED510 display module using the remote mounting kit (129-145-1, -2 and -3):
1. Cut an opening in the front panel face 3.62 inches square (92.0 mm). The width of the panel face
cannot exceed 5/64."
2. Slide the gasket over the rear side of the display.
3. Insert the ED510 display and gasket through the panel opening.
4. Insert the mounting plate over the rear side of the display. Slide the two (2) mounting tabs on the
mounting plate over the slots on the ED510 display. Then move the mounting plate until the tab
on top of the ED510 display snaps into position under the opening on the mounting plate.
NOTE: Align the mounting plate so when the mounting screws are installed and tightened, the
threaded inserts are not pushed out of the mounting plate.
The mounting plate has a 1/2" circular opening to allow access to the contrast adjustment potentiom-
eter on the rear of the ED510 display.
5. Insert the mounting screws into the threaded inserts and tighten.
6. Insert the 2 foot cable (129-145-3), 4 foot cable (129-145-1) or 8 foot cable (129-145-2) into the
RJ45 style connectors on both the ED510 display and the EP Programmer Module (Engineering
code 28 or later). A ferrite core is provided on the ED580 cable to improve the electrical noise
immunity of the FLAME-MONITOR system.The connector nearest to the ferrite core must
be plugged into the EP Programmer.
TO ENSURE THE SYSTEM IS PROPERLY GROUNDED:
1. Connect the back plane of the mounting cabinet to a proper earth ground.
2. Ground the FLAME-MONITOR wiring base to the mounting cabinet by using mounting
screws with star washers to ensure proper electrical contact.
3. Connect the green grounding screw on the wiring base to a proper earth ground.
NOTE: A PROPER EARTH GROUND CONSISTS OF A METAL ROD DRIVEN INTO THE GROUND AT A
LOCATION NEAR THE ELECTRICAL DISTRIBUTION PANEL PROVIDING POWER TO THE FLAME-
MONITOR CONTROL SYSTEM. REFER TO SN-100.
Refer to the ED610 to remote mount the display greater than 8 feet away from the control.
PART NUMBER DESCRIPTION
129-145-1 Remote mounting kit (includes ED580-4)
129-145-2 Remote mounting kit (includes ED580-8)
129-145-3 Remote mounting kit (includes ED580-2)
ED610 Multi-port connector with terminal strip and phone jacks.
ED512-2 2 foot cable with RJ12 (4P4C) connectors for connection to E500.
ED512-4 4 foot cable with RJ12 (4P4C) connectors for connection to E500.
ED512-8 8 foot cable with RJ12 (4P4C) connectors for connection to E500.
ED580-2 2 foot cable with RJ45 connectors for remote display.
ED580-4 4 foot cable with RJ45 connectors for remote display.
ED580-8 8 foot cable with RJ45 connectors for remote display.
ED150-3 3 foot remote reset cable
ED150-6 6 foot remote reset cable
ED150-15 15 foot remote reset cable
ED150-25 25 foot remote reset cable
EC485 RS485 to RS232 Converter with optional RJ12 (4P4C) connector and power
supply
3
®
FIGURE 1. INSTALLATION AND MOUNTING DIAGRAM OF ED510 WITH 129-145
WIRING CONNECTIONS FOR ED610 AND ED510 REMOTE DISPLAY
See Figure 2. Use the ED610 multi-port connector to remote mount the ED510 display greater than
eight (8) feet away from the Flame-Monitor control. An eight (8) conductor, 18 gage, low capaci-
tance, overall shielded cable (Belden 9554 or equivalent) must be used between the ED610 at the
burner site and the ED610 at the remote site. An ED580 cable is required between the ED510 dis-
play module and the ED610 connector as well as the ED610 connector and FLAME-MONITOR
control. A ferrite core is provided on the ED580 cable to improve the electrical noise immunity of
the FLAME-MONITOR system.The connector nearest to the ferrite core must be plugged into
the EP Programmer.
MAKE SURE THE FLAME-MONITOR SYSTEM IS PROPERLY GROUNDED. REFER
TO THE WARNING BOX ON PAGE 2 TO ENSURE THE SYSTEM IS PROPERLY
GROUNDED.
The position of the ferrite core is not critical on the ED580 cable connected between the ED510 dis-
play and ED610 adapter. The Flame-Monitor control will drive two (2) ED510 display modules.
The Belden cable 9554 has 4 twisted pairs with an overall shield. Conductor pairs are color coded
red and black and numbered at one (1) inch intervals (e.g. 1-black, 2-red). Maximum cable distance
of the ED510 from the Flame-Monitor control is 700 feet. Do not ground shield at both ED610's.
CAUTION: When the remote display or the remote reset is installed, make sure that the
remote location is within sight and sound of the fired equipment. Safety procedures require
that the operator be at the burner to reset the safety controls in order that any unsafe condi-
tions can be discovered and corrected prior to resetting the safety controls or devices. Fireye
does not recommend remote reset locations beyond sight and sound of the burner.
KEYPAD/DISPLAY
FRONT
GASKET
PEM NUT
INSIDE
MOUNTING
SCREW
MOUNTING
PLATE
MAXIMUM THICKNESS CONNECTOR
CABLE (2’, 4’, or 8’)
TO EP/EPD PROGRAMMER
5/64 INCH (2.0mm) PANEL
3.63
(92.0)
3.63
(92.0)
SUGGESTED PANEL CUTOUT DIMENSIONS
4
FIGURE 2. Wiring Connections for ED610 and ED510 Remote Display
WIRING FOR E500 COMMUNICATION INTERFACE
See Figure 3. Use an ED610 multi-port connector for each Flame-Monitor or E340 Boiler Control
unit connected in a multi-drop wiring configuration to the E500 Communication Interface. A two (2)
conductor, 22 gage, low capacitance shielded cable (Belden 8761 or equivalent) must be used
between the E500 Communication Interface and each ED610 multi-port connector and E340 Boiler
Control. An ED512 cable is required between the ED610 and the Flame-Monitor. A ferrite core is
provided on the ED512 cable to improve the electrical noise immunity of the FLAME-MONITOR
system.The connector nearest to the ferrite core must be plugged into the EP Programmer.
MAKE SURE THE FLAME-MONITOR SYSTEM IS PROPERLY GROUNDED. REFER
TO THE WARNING BOX ON PAGE 2 TO ENSURE THE SYSTEM IS PROPERLY
GROUNDED.
Ground the shield at one end only of each individual wiring run. Total maximum cable distances
shall not exceed 4,000 feet.
NOTE: Cable should be routed within the cabinet so that it doesn’t come in close proximity with
ignition wires, high energy contactors or solenoids.
ED610
109 87654321
J5
J1
ED510 REMOTE
E110 FLAME-MONITOR
ED580-2, -4, -8 ED580-2, -4, -8
8 CONDUCTOR TSP
BELDEN 9554
ED580-2, -4, -8
TO RJ45 CONNECTOR
ON EP/EPD PROGRAMMER
FLAME ON
ED510 DISPLAY MODULE
MOUNTED LOCALLY
FLAME ON
ED610
1098 76 54321
J5
J1
9554
1 - RED
1 - BLACK
2 - RED
2 - BLACK
3 - RED
3 - BLACK
4 - RED
TERMINAL CONNECTIONS ON ED610
CONNECT CABLE SHIELD TO TERMINAL 8
ON ONE ED610 ONLY
NOTE: To disable the reset function on
the remote display, move the jumper
on EITHER ED610 multi-port connec-
tor from position 1-2 to position 2-3.
1
2
3
J4
J2 J2
DISPLAY MODULE
1
2
3
4
5
6
7
1
2
3
4
5
6
7
BELDEN CABLE
9554 HAS
4 TWISTED
PAIRS, EACH
PAIR COLOR
CODED RED
AND BLACK.
E110 ED510
FERRITE
CORE
5
®
FIGURE 3. Wiring for E500 Communication Interface
WIRING FOR E110’SFOR MODBUS PROTOCOL
See Figure 4. Use an ED610 multi-port connector for each Flame-Monitor unit connected in a multi-
drop wiring configuration. A two (2) conductor, 22 gage, low capacitance shielded cable (Belden
8761 or equivalent) must be used between each ED610 multi-port connector. An ED512 cable is
required between the ED610 and the Flame-Monitor. A ferrite core is provided on the ED512 cable
to improve the electrical noise immunity of the FLAME-MONITOR system.The connector nearest
to the ferrite core must be plugged into the EP Programmer.
Each Flame Monitor must be assigned its own unique address. Refer to bulletin E-1101 for specific
information. The baud rate of each Flame Monitor is fixed at 4800 bits per second. Modbus is avail-
able on all EP programmers having an engineering code of 38 or greater and EPD programmers hav-
ing and engineering code of 4 or greater.
MAKE SURE THE FLAME-MONITOR SYSTEM IS PROPERLY GROUNDED. REFER
TO THE WARNING BOX ON PAGE 2 TO ENSURE THE SYSTEM IS PROPERLY
GROUNDED.
Ground the shield at one end only of each individual wiring run. Total maximum cable distances
shall not exceed 4,000 feet.
NOTE: Cable should be routed within the cabinet so that it doesn’t come in close proximity with
ignition wires, high energy contactors or solenoids.
BELDEN 8761
TERMINAL CONNECTIONS
E500 ED610 E340
BLACK 4 (B) 9 80
CLEAR 5 (A) 10 81
ED610
10 9 8 7 6 5 4 3 2 1
J5
J1
ED610
10 9 8 7 6 5 4 3 2 1
J5
J1
E110
E500 COMMUNICATION
INTERFACE
ED512-2, -4, -8
FLAME-MONITOR
E340 BOILER
ROOM CONTROL
BELDEN 8761
CLEAR
BLACK
BLACK
CLEAR
To terminals
80 (BLACK)
81 (CLEAR)
E110
ED512-2, -4, -8
FLAME-MONITOR
E340 BOILER
ROOM CONTROL
BELDEN 8761
BLACK
CLEAR
To terminals
80 (BLACK)
81 (CLEAR)
CLEAR
BLACK
1 2 3 4 5 6 7 8
B A
TO RJ12 (4P4C) CONNECTOR
ON EP/EPD PROGRAMMER
TO RJ12 (4P4C) CONNECTOR
EP/EPD PROGRAMMER
DISTANCE FROM ED610 TO E340
MUST BE LESS THAN 10 FEET.
J2
J2
FERRITE
CORE FERRITE
CORE
ON
6
FIGURE 4. Wiring for Modbus Protocol
WIRING FOR REMOTE RESET
A remote reset button can be added when using the ED610 multi-port connector. Wire a normally
open momentary push button across terminals 8 & 4 on the ED610. Jumper J4 must be in position 1-
2. Refer to Figure 6.
REFER TO “CAUTION” FOR REMOTE RESET ON PAGE 3.
FIGURE 5. ED610 DIMENSIONS FIGURE 6: WIRING FOR REMOTE RESET
The ED611 multi-port connector provides for remote reset at the terminal block, but inhibits the
lockout reset capability at the ED510. This is useful for applications that may want to use a key lock
switch in lieu of the reset button located on the ED510 display. Connect the E110 and ED510 as
shown using the ED580 cables. Wire a normally open momentary push button switch across termi-
nals 8 & 4. Jumper J4 on the ED611 must be in position 1 to 2. Refer to Figure 8.
REFER TO “CAUTION” FOR REMOTE RESET ON PAGE 3.
ED610
10 9 8 7 6 5 4 3 2 1
J5
J1
ED610
10 9 8 7 6 5 4 3 2 1
J5
J1
E110
OPTION 1 TO PC, PLC, ETC.
ED512-2, -4, -8
FLAME-MONITOR
BELDEN 8761
E110
ED512-2, -4, -8
FLAME-MONITOR
CLEAR
BLACK
TO RJ12 (4P4C) CONNECTOR
ON EP/EPD PROGRAMMER
TO RJ12 (4P4C) CONNECTOR
ON EP/EPD PROGRAMMER
J2
J2
FERRITE
CORE FERRITE
CORE
EC485
RS485 TO
RS232
CONNECTOR
RS485
OPTION 2
TO CONTROL
SYSTEM
B
A
OR
BA
SEE FIG. 7
12345678910
1
2
3
J1 J2 J5
J4
H1 H2
ED610
J3
A B
2.00
1.00
2.4
3.00
76.2
50.8
60.9
25.4
E110
ED580 -2, -4, -8
FLAME-MONITOR
TO RJ45 CONNECTOR ON
EP/EPD PROGRAMMER
FERRITE
CORE
ED610
10 9 8 7 6 5 4 3 2 1
J5
J1 J2
MOMENTARY CONTACT CLOSURE
J4
1
2
7
®
FIGURE 7: REMOTE RESET CONNECTION
REFER TO “CAUTION” FOR REMOTE RESET ON PAGE 3.
FIGURE 8: WIRING FOR REMOTE RESET
COMMUNICATING WITH THE E340 BOILER CONTROL
The E340 Boiler Control also communicates over an RS485 communication data link. The data link
uses a single, twisted shielded pair wire (Belden 8761) with the E340 controls wired in a multi-drop
(e.g. daisy-chain) wiring configuration. The Fireye communication software program (P/N E720)
running on an IBM compatible PC is required for communication with the E340 controls.
Fireye recommends using the E500 Communication interface when communicating with the E340
controls, since the E500 provides communication with the Flame-Monitor™ flame safeguard con-
trols as well. However, the EC485 converter can be used to communicate only with the E340 con-
trols.
FLAME
MONITOR
REMOTE RESET
SWITCH N.O.
DEPRESS AND
HOLD 1 SEC.
FOR RESET
ED150 CABLE
TO ED510
ED580
NO RESET
ED611
10 9 8 7 6 5 4 3 2 1
J5
J1 J2
KEYLOCK RESET SWITCH
J4
1
2
ED580
AVAILABLE
FROM ED110
FLAME ON
8
Wire the EC485 converter to the E340 controls in the following manner:
FIGURE 9:
For complete details on wiring and communicating with the E340 controls refer to bulletin BW-1000
(BoilerWorx™ Communication Software Program).
NOTICE
When Fireye products are combined with equipment manufactured by others and/or integrated into
systems designed or manufactured by others, the Fireye warranty, as stated in its General Terms and
Conditions of Sale, pertains only to the Fireye products and not to any other equipment or to the
combined system or its overall performance.
WARRANTIES
FIREYE guarantees for one year from the date of installation or 18 months from date of manufacture
of its products to replace, or, at its option, to repair any product or part thereof (except lamps, elec-
tronic tubes and photocells) which is found defective in material or workmanship or which otherwise
fails to conform to the description of the product on the face of its sales order. THE FOREGOING
IS IN LIEU OF ALL OTHER WARRANTIES AND FIREYE MAKES NO WARRANTY OF
MERCHANTABILITY OR ANY OTHER WARRANTY, EXPRESS OR IMPLIED. Except as
specifically stated in these general terms and conditions of sale, remedies with respect to any product
or part number manufactured or sold by Fireye shall be limited exclusively to the right to replace-
ment or repair as above provided. In no event shall Fireye be liable for consequential or special dam-
ages of any nature which may arise in connection with such product or part.
FR. GRD
SHLD
TD (A)
TD (B)
RD (A)
RD (B)
+12VDC
GND
ECHO
ON
OFF RTS
SD
CONTROL
ED612
120VAC
50/60Hz
COMMUNICATION TERMINATOR
ON LAST E340 CONTROL
(COM B) TERMINAL 80
(COM A) TERMINAL 81
TO E340 CONTROLS
(COM B) TERMINAL 80
(COM A) TERMINAL 81
DATA COMMUNICATION LINK
DB25 CONNECTOR
TO COMPUTER’S
RS232 SERIAL
COMMUNICATION
PORT
NOTE:
1. ECHO OFF
2. RTS
WHITE STRIPE
TO +12VDC
EC485 CONVERTER
Note: The two jumpers on the 485CON converter should be set to “RTS” and “Echo Off.”
Note: TD (A) and RD (A) on EC485 converter connected to Terminal 80 (COM B) of E340 control.
TD (B) and RD (B) on EC485 converter connected to Terminal 81 (COM A) of E340 control.
61-6689
(USUALLY NOT REQUIRED)
FIREYE E-8002
3 Manchester Road MARCH 27, 2015
Derry, New Hampshire 03038 USA Supersedes April 3, 2013
www.Fireye.com
/