Raychem NGC-UIT2-ORD Installation guide

Category
Electrical enclosures
Type
Installation guide
DESCRIPTION
The nVent RAYCHEM NGC-UIT-ORD-12 is a wall-mounted display which
allows the User Interface Terminal (UIT) to be installed remotely.
The NGC-UIT-ORD-12 is used with RAYCHEM NGC-30 control and
monitoring systems.
The NGC-UIT-ORD-12 is rated NEMA 12 (IP 54), and is approved for
nonhazardous indoor locations. These instructions describe how to
mount the NGC-UIT-ORD-12 on a wall, how to make connections to
the User Interface Terminal and are intended for a qualified electrician.
TOOLS REQUIRED
Drill or hole punch for electrical conduit entries
Phillips (cross-head) screwdriver
Small flat-head screwdriver
ADDITIONAL MATERIALS REQUIRED
Wall fasteners for surface mounting (four screws)
RS-485 cable (Belden # 8761, or Carol # C2514)
KIT CONTENTS
Item Description
1 User Interface Terminal – NEMA 12
1 5 ft (1.5 m) RS-232 adaptor cable
4 Elastomeric washers
APPROVALS
Nonhazardous Locations
General
A
rea of Use Ordinary, Indoors (NEMA 12, IP54)
Supply Voltage 100 – 120 Vac –4/+10%, 1 A max. fused, 50/60 Hz
Operating Temperature –40°F to 149°F (–40°C to 65°C)
EMC Immunity – Industrial
Emission – Commercial / Light Industrial
Vibration Unit tested to IEC-60068-2-6
Shock Unit tested to IEC-60068-2-27
Dimensions 15" W X 11.8" H X 6.1" D
(381 mm W X 300 mm H X 155 mm D)
Alarm Outputs
Relay Outputs Three relay outputs, Form C contacts,
switching loads up to 277 Vac/3 A.
Relays may be assigned for alarm outputs.
Network Connection
Local Port/Remote RS-485/RS-232, selectable. Port may be used to
communicate with RAYCHEM Supervisor Software.
RS-232 A non-isolated, RJ-11 connection.
RS-485 2-wire isolated. Phoenix-style pluggable screw
terminal connector with retaining screws.
Maximum number of devices 256. Fail safe design
with optional termination resistors.
Data Rate 9600 to 57600 baud.
Maximum cable length For RS-485 not to exceed 4000 ft (1200 m).
Cable to be shielded twisted pair.
Field Port RS-485, 2-wire isolated. Used to communicate with
external devices, such as NGC-30-CRM/-CRMS, 5GF-C
and RMM2. Maximum cable length not to exceed
4000 ft (1200 m). Cable to be shielded twisted pair.
Signals Weidmuller terminal block #22 - #10 AWG.
Data Rate To 9600 baud
LAN 10/100 Base-T Ethernet port with Link and Activity
Status LEDs
USB Port USB 2.0 Host port Type A receptacle
Status LEDs
Relay Three LEDs showing the ON/OFF Status for each
relay, LED ON indicates relay is energized.
Field Transmit and Receive activity
Local/Remote Transmit and Receive activity
USB Host Three colors showing status:
Red = USB key fault
Green = USB key inserted
Yellow = USB in use
UIT Status Three colors showing system status:
Green = Normal Condition
Red = Fault Condition
Yellow = Loading software/configuration
LCD Display
Display LCD is a 6.5 inch QVGA, color TFT transflective
device with integral CCFL backlight.
Touch Screen
4-wire resistive touch screen interface for user entry.
NGC-UIT2-ORD
REMOTE USER INTERFACE TERMINAL FOR RAYCHEM NGC
SYSTEMS INSTALLATION INSTRUCTIONS
2 | nVent.com
15 in
(381 mm)
11.8 in
(300 mm)
10.24 in
(260 mm)
0.79 in
(20 mm)
0.79 in
(20 mm)
mounting hole
(four places)
8 mm (5/16 in)
Attachment points
for motherboard
(four places)
13.42 in
(341 mm)
TB1
1
FU1
2 3 4 5
H H N N
1 2 3 1 2 34 5 6 7 8 9
TB2 TB3
Line
Voltage
Alarm
Relay
Location of Line Voltage, Alarm Relay and RS-485 connections.
RS-485
AR
4 5 6
Grounding bar
Gland plate
Gasket
Screws
Mounting the Enclosure
Electrical Safety
Making Enclosure Entries Using the Removable Gland Plate
The RAYCHEM NGC-UIT-ORD-12 controller must be mounted in a
nonhazardous indoor location. Choose a location indoors where
the controller will be protected from the elements and kept above
–40°F (–40°C) and below 149°F (65°C).
Install the enclosure using the four screws (not provided) in the
prepunched 8 mm (5/16-inch) mounting holes with centers as
shown below. If plastic plugs are in the mounting holes, remove
them. Make sure the rubber elastomeric washers (provided in the
RAYCHEM NGC-UIT-ORD-12 shipping box) are aligned to
seal around the mounting screws to maintain the
NEMA 12 and IP54 ratings.
The removable gland plate on the bottom edge of the enclosure
provides a location to feed wires through. The plate is attached
with eight screws. Unscrew these to remove the gland plate. You
can drill or punch holes appropriate for your application. There is
sufficient width for up to five 1/2-inch or M20 holes. Remove all
metal filings and dust from the gland plate before remounting. Take
care not to damage the gasket or the gland plate. You must secure
the gland plate ground wire to the chassis ground lug.
Follow electrical safety procedures when installing and maintaining the
NCG-UIT-ORD-12 unit, as line voltage is present inside.
FIRE Hazard: Do not mount the
NGC-UIT-ORD-12 in a hazardous
location.
IMPORTANT: The NGC-
UIT-ORD-12 is an electronic
unit. During installation, take
the following precautions to
avoid damage to its electronic
components.
Handle with care to avoid
mechanical damage.
Keep electronics dry.
Avoid exposure to static
electricity.
Avoid contamination with
metal filings, liquids, or other
foreign matter.
Take care to protect the
user interface board on the
enclosure door.
Use agency-approved conduit
bushings, adapters, and cable
glands to keep the enclosure
protected from dust and
fluids.
WARNING:
IMPORTANT:
nVent.com | 3
TB1
1
FU1
2 3 4 5
H H N
Ground bar
AC in
100 – 120 Vac -4/+10%
Ø or N
GØ
N
RS-485 +
Shield
RS-485 –
To DCS
or PC
4 5 6
TB3
RS-485 +
Shield
RS-485 –
To downstream devices
(NGC-30-CRM’s, RMM2’s)
Refer to “As Built” drawings
for connection details.
For RS-485 cable type, reference
Belden # 8761, or Carol # C2514
1 2 3
TB3
Refer to the NGC-30 Program-
ming Guide (H58186), and the
NGC-30 Installation Manual
(H57878) for further details.
1 2 3 4 5 6 7 8 9
TB2
Relay 1Relay 2Relay 3
To Alarm Relay/Light
(100 – 120 Vac)
Connecting Main Power
Connecting RS-485 Remote Port Communication
Connecting RS-485 Field Port Communication
Alarm Light and Option Alarm Relays
Use only copper conductors for field wiring. A close-up of the power
connection terminals is shown below. This connection energizes
the RAYCHEM NGC-UIT-ORD-12 electronics only; it does not provide
power to the heat tracing or contactor coils.
Note: If the RAYCHEM NGC-UIT-ORD-12 controller has a different
source of power than the heat tracing, it may be worthwhile to
install an uninterruptible power supply (UPS) so the unit can
continue to control and/or monitor the heat tracing in the event of a
localized power failure.
The NGC-UIT-ORD-12 can communicate with distributed control
systems (DCS) or other host computers through the remote
communication port.
Note: The above relays are shown
in the energized position without
an alarm condition.
The relay will change state
with an alarm condition or
loss of power.
The NGC-30-CRM/-CRMS and RMM2 communicate with the
NGC-UIT-ORD-12 over an RS-485 network, which may have a
total cable length of 4,000 ft (1,200 m).
The RS-485 communicating cable shall be a shielded, two
conductor (twisted pair) cable.
Relay 1 on the NGC-UIT-ORD-12 is factory-configured and wired for
Any Alarms”. It will energize a push to test light on the front of the
panel if any alarm occurs. Relay 1 was also wired to a common
alarm relay/terminal block for remote annunciation of “Any Alarms”.
The NGC-UIT has two other Form C alarm relays (Relays 2 and
3, configurable through the NGC-UIT program ) for external alarms.
Each relay can be connected to an annunciator light or distributed
control system. Each relay's contacts have been wired for the
NGC-UIT to a terminal block in the panel.
©2018 nVent. All nVent marks and logos are owned or licensed by nVent Services GmbH or its affiliates. All other trademarks are the property of their respective owners.
nVent reserves the right to change specifications without notice.
Raychem-IM-H57925-NGCUITORD12-EN-1805
nVent.com
North America
Tel +1.800.545.6258
Fax +1.800.527.5703
Europe, Middle East, Africa
Tel +32.16.213.511
Fax +32.16.213.604
Asia Pacific
Tel +86.21.2412.1688
Fax +86.21.5426.3167
Latin America
Tel +1.713.868.4800
Fax +1.713.868.2333
TB1
1
FU1
RS-485 +
RS-485 –
2 3 4 5
H H N
Grounding bar
RS-485 Ports
Field Remote
AC in
100 – 120 Vac -4/+10%
(Note: Relay shown in the energized
position without alarm condition)
G
Ø or N
Ø
Relay 2 Relay 3
N
1 2 3 1 2 34 5 6 7 8 9
TB2 TB3
AR
Relay 1
4 5 6
Shield
RS-485 +
RS-485 –
To
PC
To downstream devices
(NGC-30-CRM’s, RMM2’s)
Shield
To Alarm Relay/Light
(100 – 120 Vac)
Fail Safe Relay Outputs AC inputRS-485 Ports
10/100
Ethernet
RS-232
(DCE)
Local
N/L2
Line/L1
SIG –
SIG +
Shield
SIG –
SIG +
Shield
11109 321876543
Relay 3Relay 2Relay 1
RemoteField
21654321
To TB3
To TB2
To TB1
RS-485
cable
RS-232
cable
Ethernet
cable
PC
Select either RS-232, RS-485 or
Ethernet.
Refer to the NGC-30
Programming Guide (H58186), and
the NGC-30 Installation Manual
(H57878) for further details.
Note: When using RS-485 communication,
use Belden cable 8761 or equivalent.
RS-485 cable must not exceed 4000 ft.
Connecting RS-485/232 Local Port and Ethernet (optional)
Overview of Wiring
1. This port is used to communicate to a host
computer and is user selectable for either
RS-232, RS-485 or Ethernet.
2. If the RS-232 port is utilized, the supplied
RJ-11 to RS-232 adaptor cable must be used.
For more information, refer to the NGC-30
Programming Guide (H58186) and the NGC-30
Installation Manual (H57878).